The text of a manual · part 2 of 20
Andover Infinet i2 Controller Technical Reference, pages 5 to 14
Pages 5 to 14 of 190: Contents; Introduction
The original document is the PDF (8.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Andover Controls i2850 and Schneider i2850
Page 5
Contents Introduction ............................................................................................ 1 i2 Controller Overview ................................................................................... 3 Wireless Support ........................................................................................... 4 i2 vs Infinet I Controller Compatibility Issues ................................................. 4 Special System Characteristics.............................................................. 6
Mechanical Installation ........................................................................ 19 Power Connections.............................................................................. 37 24 VAC Connections.............................................................................. 40 12-28 VDC Connections ........................................................................ 45 115 - 230VAC Connections .................................................................. 45 Battery Connection & Replacement ..................................................... 47 Building Ground Requirements............................................................ 49
RS-485 Infinet ...................................................................................... 51 Controller Inputs................................................................................... 65 Universal Inputs..................................................................................... 67 Measuring Temperature..................................................................... 72 Measuring DC Voltages ..................................................................... 74 Sensing Contact Closures................................................................. 76 Counting Pulsing Signals or Contact Closures............................... 77 Supervised Inputs.................................................................................. 78 Measuring Airflow.................................................................................. 83 Smart Sensor Bus Interface.................................................................. 86
Andover Continuum i2 Controller Technical Reference v
Page 6
Controller Outputs................................................................................ 89 Digital Outputs ....................................................................................... 94 Tri-state Output ...................................................................................... 95 Form A Triac Outputs ............................................................................ 98 Form K Triac Outputs .......................................................................... 101 Analog Outputs .................................................................................... 103 Voltage Output ..................................................................................... 105
Expansion Interface ........................................................................... 107 Operation/Programming .................................................................... 119 All Controllers except i2885, i2885-V, & i2887 ................................... 121 Programming only the i2885, i2885-V & i2887 ................................... 133 I/O Point Assignments......................................................................... 141 Expansion Point Assignments............................................................ 150 Actuator Programming ........................................................................ 150 Plain English Function Changes (i2885 & i2887 only) ...................... 155 CPU Indicators ..................................................................................... 156
Troubleshooting ................................................................................. 157 vi
Schneider Electric
Page 7
1 . . . . . . Introduction i2 Controller Technical Reference
1
Page 8
2
Schneider Electric n
Page 9
This manual describes the installation, and use of all Andover Infinet™ II (i2) controllers. The i2 family of intelligent, programmable, stand-alone controllers provides cost-effective Direct Digital Control of individual terminal units: VAV boxes, fan powered induction units, unit ventilators, heat pumps, etc. The Infinet’s true peer-to-peer communications protocol provides the series with the ability to instantly communicate with an Infinity CX controller, Andover Continuum NetController, Andover Continuum bCX1 9640 controller, as well as its entire network of Andover Continuum Infinet field bus controllers. Up to 254 i2 controllers (127 per Infinet port) can be networked with the Infinity family of controllers. Note: For complete information on bCX1 controllers, see the bCX1 Series Controller Technical Reference, 30-3001-890, and the Continuum online help.
i2 Controller Overview The following lists the basic features included in the i2 series controllers. Specific information on each controller may be found in other parts of this reference: Model
Inputs i2608 i2624
8 Universal 24 Universal
None None i2800
8 Universal 1 Smart Sensor 8 Universal 1 Smart Sensor
8 Form C i2804 i2810 i2814 i2850 i2851 i2853 i2865 i2865-V iI2866
Outputs
Other Features
4 Form C 4 Analog
8 Universal 1 Smart Sensor 8 Universal 1 Smart Sensor
8 Form C
Output Override control Expansion Interface Output Override control Expansion Interface
4 Form C 4 Analog
4 Universal 1 Smart Sensor 4 Universal 1 Smart Sensor 4 Universal 1 Smart Sensor
3 Form A 1 Form K Tri-state 3 Form A 1 Form K Tri-state 3 Form A 1 Form K Tri-state
1 Airflow Sensor Expansion Interface Expansion Interface
4 Universal 1 Smart Sensor 4 Universal 1 Smart Sensor 4 Universal 1 Smart Sensor
3 Form A Triac 1 Tri-state Actuator control 3 Form A Triac 1 Tri-state Actuator control 3 Form A Triac 1 Tri-state Actuator control 2 Analog 3 Form A Triac 1 Tri-state Actuator control 2 Analog
1 Airflow Sensor Built-in Actuator 1 Airflow Sensor Built-in Actuator 1 Airflow Sensor Built-in Actuator
2 Airflow Sensors Expansion Interface i2866-V
4 Universal 1 Smart Sensor i2867
4 Universal 1 Smart Sensor
5 Form A Triac 2 Analog i2885
2 Universal i2885-V
2 Universal
2 Form A Triac 1 Tri-state Actuator control 2 Form A Triac 1 Tri-state Actuator control
1 Airflow Sensor Built-in Actuator
1 Airflow Sensor Built-in Actuator 1 Airflow Sensor Built-in Actuator i2 Controller Technical Reference
3
Page 10
i2887 i2887-L i2920
3 Universal 1 Smart Sensor 3 Universal 1 Smart Sensor
4 Form A Triac 1 Form A Relay 4 Form A Triac 1 Form A Relay
16 Universal 1 Smart Sensor
8 Form C 8 Analog
Aux power output Output Override control Expansion Interface
The following pages illustrate the major connection areas for each controller. Subsequent sections detail power, network, input and output specifications and connections.
Wireless Support The i2 field bus controllers can also be configured in an Infinet wireless field bus mesh network with its Ethernet-level wireless parent bCX1 9640 controller. A Wireless Adapter is connected to each controller’s COMM2 port via the controller’s service port interface. Network signals are strengthened, where necessary, via Wireless Repeaters to carry the data between nodes in a wireless network. The i2 controllers are configured as wireless controllers through CyberStation. For more information, please see the Andover Continuum CyberStation Configurator’s Guide, 30-3001-781, and the CyberStation online help. For more information on Andover Continuum wireless products and technology, please see: •
Wireless Adapter/Repeater Installation Instructions, 30-3001-887
•
Wireless Mesh Network Concepts and Best Practices Guide, 30-3001-912
•
Wireless Maintenance Tool User’s Guide, 30-3001-913 i2 vs Andover Infinet™ I Controller Compatibility Issues If you are replacing older Andover Infinet™ controllers with i2 equivalents, there may be some slight compatibility issues. The following lists all known differences between the two:
All Models: Controller Memory i2 controllers include flash memory that may be accessed via program control. This addition does not affect existing programs ported from Infinet I devices.
All Models: System Variables i2 controllers include several new system variables (described later in the programming section). This addition does not affect existing operation or programs ported from Infinet I devices.
4
Schneider Electric n
Page 11
All Models: Output Connections i2 controllers may switch outputs differently than the controllers you are replacing. Refer to the wiring diagrams included in this document.
xP Modules: Different from EMX Some i2 controller models include expansion capability that looks similar to the old EMX system but it operates on a very different addressing principle. Complete information on the new expansion modules may be found later in this document.
i2920: Different from SCX920 The i2920 includes eight Digital/Tri-state pair outputs on channels #1-8 and eight voltage/current outputs on channels 9-16 The SCX920 has eight universal outputs on channels #1-8 i2 Controller Technical Reference
5
Page 12
Special System Characteristics Smoke Control Operation (UL 864) i2 controllers available through Schneider Electric that are listed with UL for Smoke Control applications are the following: i2608-S i2624-S i2800-S i2804-S i2850-S i2851-S i2853-S i2865-S i2866-S i2867-S i2920-S The Smart Sensor connection and the Expansion Options available for many controllers are not listed for UL 864 applications. i2 Repeaters available through Schneider Electric that are listed with UL for Smoke Control applications are the following: i2210 AC-S i2210 DC-S i2200 AC-S i2200 DC-S
SX8000 Smoke Control Although it is possible to operate the i2 family of controllers with the SX8000 workstation, this type of system is not approved for smoke control applications. Pulsed Outputs Although i2 series controllers are capable of pulsed output, using pulsed output is not allowed for UL864 applications.
6
Schneider Electric n
Page 13
i2600 Series The following diagram indicates the locations of each of the main connection points.
i2 Controller Technical Reference
7
Page 14
i2800 Series The following diagram indicates the locations of each of the main connection points.
8
Schneider Electric n