Andover Infinet i2 Controller Technical Reference: Operation/Programming, pages 145 to 154

Pages 145 to 154 of 190, from Andover Infinet i2 Controller Technical Reference

The original document is the PDF (8.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls i2850 and Schneider i2850

Page 145

Using the ACCStatusFlash Variable The ACCStatusFlash variable indicates the current state (empty, valid or failure) of the Flash memory device. The controller stores status information into this variable. A system variable called ACCStatusFlash is automatically created when the controller is defined. ACCStatusFlash can have the following values: ACCFlashEmpty

There is no valid database in Flash memory

ACCFlashValid

There is a valid database in Flash memory

ACCFlashFailure

An error was encountered while trying to perform a backup to Flash. In this state, the data in flash is unusable

Using the ACCStatusBackup Variable The ACCStatusBackup variable indicates the operational state (backup needed, backup done, backup in progress, etc.) of the memory. It is also used to initiate a backup operation. The controller stores status information into this variable and the user initiates a manual backup operation through this variable. Note: The CyberStation user interface includes the ability to initiate a flash backup as well as the method presented below. A system variable called ACCStatusBackup is automatically created when the controller is defined. ACCStatusBackup, when used as an indicator, can have the following values: ACCBackupDone

A backup to Flash memory has been successfully completed, or the controller has not been configured.

ACCBackupNeeded

A configuration item has changed value since the last successful backup to Flash memory.

ACCBackupInProgress A backup to Flash memory operation is underway. Note: The database is available on a read-only basis during the backup operation. ACCBackupDisabled

The database has been saved to Flash memory 2,000 times and the user has attempted further backup operations without re-setting the Flash Circuit Breaker (see BackupEnable). For as long as this condition persists, further backup operations are disabled.

i2 Controller Technical Reference

139

Page 146

ACCStatusBackup, when used to initiate a backup can have the following values:

ACCBackupEnable

A command from the user. This allows you to override the Flash Circuit Breaker and perform further backup operations. Further backup operations will be uninhibited until an additional 2,000 Flash write cycles have been incurred.

ACCBackupNow

A command from the user. This causes the system to initiate a backup of the current database to Flash memory.

Using the ACCFlashWRCount Variable The ACCFlashWRCount variable stores a running tally of the number of write operations performed on the flash memory. The controller stores the count information into this variable. A system variable called ACCFlashWRCount is automatically created when the controller is defined.

140

Schneider Electricn

Page 147

I/O Point Assignments The following pages list the input and output point assignments for each controller:

i2600 Series I/O Point Assignments Function

Input Point Assignment

Electrical Type

Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8

1 2 3 4 5 6 7 8

* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1

Input 9 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16

9 10 11 12 13 14 15 16

* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1

Input 17 Input 18 Input 19 Input 20 Input 21 Input 22 Input 23 Input 24

17 18 19 20 21 22 23 24

* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 i2608 i2624

* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised i2 Controller Technical Reference

141

Page 148

i2800 Series I/O Point Assignments Function

Input Point Assignment

Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8

1 2 3 4 5 6 7 8

* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1

Input 9 (Smart Sensor)

9

* see note 2

Function

Output Point Assignment

Electrical Type

Output 1 Output 2 Output 3 Output 4

1 2 3 4

Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital, Tri-State

Output 5 (i2800 only) Output 6 (i2800 only) Output 7 (i2800 only) Output 8 (i2800 only)

5 6 7 8

Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital

Output 5 (i2804 only) Output 6 (i2804 only) Output 7 (i2804 only) Output 8 (i2804 only)

5 6 7 8

Voltage Voltage Voltage Voltage

* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised

142

Electrical Type

Schneider Electricn

* Note 2: valid ElecTypes are: ACCTemp(DegF) ACCTemp(DegC) Digital

Page 149

i2810 Series I/O Point Assignments Function

Input Point Assignment

Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8

1 2 3 4 5 6 7 8

* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1

Input 9 (Smart Sensor)

9

* see note 2

Function

Output Point Assignment

Electrical Type

Electrical Type

Output 1 Output 2 Output 3 Output 4

1 2 3 4

Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital, Tri-State

Output 5 (i2810 only) Output 6 (i2810 only) Output 7 (i2810 only) Output 8 (i2810 only)

5 6 7 8

Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital

Output 5 (i2814 only) Output 6 (i2814 only) Output 7 (i2814 only) Output 8 (i2814 only)

5 6 7 8

Voltage Voltage Voltage Voltage

* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised

* Note 2: valid ElecTypes are: ACCTemp(DegF) ACCTemp(DegC) Digital i2 Controller Technical Reference

143

Page 150

i2850 Series I/O Point Assignments Function

Input Point Assignment

Input 1 Input 2 Input 3 Input 4 Input 5

1 2 3 4 5

* see note 1 * see note 1 * see note 1 * see note 1 * see note 2

Airflow 1 (i2850 & i2853) Airflow 2 (i2853 only)

8 7

Voltage Voltage

Function Output 1 Output 2 Output 3 Output 4

Output Point Assignment 1 2 3 4

* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised * Note 2: valid ElecTypes are: ACCTemp(DegF) ACCTemp(DegC) Digital

144

Schneider Electricn

Electrical Type

Electrical Type Digital, Tri-State Digital, Tri-State Digital Tri-State

Page 151

i2865/866, i2865-V/866-V Series I/O Point Assignments Function Universal Input 1 Universal Input 2 Universal Input 3 Universal Input 4 Smart Sensor Input Airflow Sensor Input

Actuator Output 3 Output 4 Output 5 Output 6 Output 7

Input Point Assignment i2865/-V i2866/-V 1 1 2 2 3 3 4 4 5 5 7

7

* See Note 1 * See Note 1 * See Note 1 * See Note 1 * See Note 2 Voltage

Output Point Assignment i2865/-V i2866/-V 1 1 3 4 5 − −

Electrical Type

3 4 5 6 7

Tri-State Digital, Tri-State Digital, Tri-State Digital Voltage Voltage

* Note 1: Valid ElecTypes are:

Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter

* Note 2: Valid ElecTypes are:

ACCTemp(DegF) ACCTemp(DegC) Digital

Actuator LCDState Attribute Note: Toggling the value of the LCDState attribute of Output 1 (the Actuator) performs the same action as pressing the Actuator Clutch button.

i2 Controller Technical Reference

145

Page 152

i2867 Series I/O Point Assignments Function

Input Point Assignment

Input 1 Input 2 Input 3 Input 4 Input 5

1 2 3 4 5

Function

Output Point Assignment

* see note 1 * see note 1 * see note 1 * see note 1 * see note 2

Electrical Type

Output 1 Output 2 Output 3 Output 4 Output 5

1 2 3 4 5

* see note 3 * see note 3 Digital, Tri-State Digital, Tri-State Digital

Output 6 Output 7

6 7

Voltage Voltage

* Note 1: valid ElecTypes are: Voltage ACC(Temp(DegF) ACCTemp(DegC) Digital Counter * Note 2: valid ElecTypes are: Digital ACCTemp(DegF) ACCTemp(DegC) * Note 3: valid ElecTypes are: When using CyberStation: Digital, Tri-State When using SX8000: Tri-State only

146

Electrical Type

Schneider Electricn

Page 153

i2885 and i2885-V Series I/O Point Assignments Function Universal Input 1

Input Point Assignment 1

Electrical Type

Universal Input 2

2

Airflow Sensor Input

7

Voltage

Actuator

Output Point Assignment 1

Tri-State

Output 3 Output 4

3 4

Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter

Digital, Tri-State Digital i2 Controller Technical Reference

147

Page 154

i2887(L) Series I/O Point Assignments Function Universal Input 1

Input Point Assignment 1

Universal Input 2

2

Universal Input 3

3

Smart Sensor Input

4

Triac Output 1 Triac Output 2 Triac Output 3 Triac Output 4

Output Point Assignment 1 2 3 4

Relay Output 5

5

Electrical Type Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter ACCTemp(DegF) ACCTemp(DegC) Digital

* see note 1 * see note 1 * see note 1 * see note 1 Digital

* Note 1: valid ElecTypes are: When using CyberStation: Digital, Tri-State When using SX8000: Tri-State only

148