Page 145
Using the ACCStatusFlash Variable The ACCStatusFlash variable indicates the current state (empty, valid or failure) of the Flash memory device. The controller stores status information into this variable. A system variable called ACCStatusFlash is automatically created when the controller is defined. ACCStatusFlash can have the following values: ACCFlashEmpty
There is no valid database in Flash memory
ACCFlashValid
There is a valid database in Flash memory
ACCFlashFailure
An error was encountered while trying to perform a backup to Flash. In this state, the data in flash is unusable
Using the ACCStatusBackup Variable The ACCStatusBackup variable indicates the operational state (backup needed, backup done, backup in progress, etc.) of the memory. It is also used to initiate a backup operation. The controller stores status information into this variable and the user initiates a manual backup operation through this variable. Note: The CyberStation user interface includes the ability to initiate a flash backup as well as the method presented below. A system variable called ACCStatusBackup is automatically created when the controller is defined. ACCStatusBackup, when used as an indicator, can have the following values: ACCBackupDone
A backup to Flash memory has been successfully completed, or the controller has not been configured.
ACCBackupNeeded
A configuration item has changed value since the last successful backup to Flash memory.
ACCBackupInProgress A backup to Flash memory operation is underway. Note: The database is available on a read-only basis during the backup operation. ACCBackupDisabled
The database has been saved to Flash memory 2,000 times and the user has attempted further backup operations without re-setting the Flash Circuit Breaker (see BackupEnable). For as long as this condition persists, further backup operations are disabled.
i2 Controller Technical Reference
139
Page 146
ACCStatusBackup, when used to initiate a backup can have the following values:
ACCBackupEnable
A command from the user. This allows you to override the Flash Circuit Breaker and perform further backup operations. Further backup operations will be uninhibited until an additional 2,000 Flash write cycles have been incurred.
ACCBackupNow
A command from the user. This causes the system to initiate a backup of the current database to Flash memory.
Using the ACCFlashWRCount Variable The ACCFlashWRCount variable stores a running tally of the number of write operations performed on the flash memory. The controller stores the count information into this variable. A system variable called ACCFlashWRCount is automatically created when the controller is defined.
140
Schneider Electricn
Page 147
I/O Point Assignments The following pages list the input and output point assignments for each controller:
i2600 Series I/O Point Assignments Function
Input Point Assignment
Electrical Type
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8
1 2 3 4 5 6 7 8
* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1
Input 9 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16
9 10 11 12 13 14 15 16
* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1
Input 17 Input 18 Input 19 Input 20 Input 21 Input 22 Input 23 Input 24
17 18 19 20 21 22 23 24
* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 i2608 i2624
* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised i2 Controller Technical Reference
141
Page 148
i2800 Series I/O Point Assignments Function
Input Point Assignment
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8
1 2 3 4 5 6 7 8
* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1
Input 9 (Smart Sensor)
9
* see note 2
Function
Output Point Assignment
Electrical Type
Output 1 Output 2 Output 3 Output 4
1 2 3 4
Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital, Tri-State
Output 5 (i2800 only) Output 6 (i2800 only) Output 7 (i2800 only) Output 8 (i2800 only)
5 6 7 8
Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital
Output 5 (i2804 only) Output 6 (i2804 only) Output 7 (i2804 only) Output 8 (i2804 only)
5 6 7 8
Voltage Voltage Voltage Voltage
* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised
142
Electrical Type
Schneider Electricn
* Note 2: valid ElecTypes are: ACCTemp(DegF) ACCTemp(DegC) Digital
Page 149
i2810 Series I/O Point Assignments Function
Input Point Assignment
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8
1 2 3 4 5 6 7 8
* see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1 * see note 1
Input 9 (Smart Sensor)
9
* see note 2
Function
Output Point Assignment
Electrical Type
Electrical Type
Output 1 Output 2 Output 3 Output 4
1 2 3 4
Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital, Tri-State
Output 5 (i2810 only) Output 6 (i2810 only) Output 7 (i2810 only) Output 8 (i2810 only)
5 6 7 8
Digital, Tri-State Digital, Tri-State Digital, Tri-State Digital
Output 5 (i2814 only) Output 6 (i2814 only) Output 7 (i2814 only) Output 8 (i2814 only)
5 6 7 8
Voltage Voltage Voltage Voltage
* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised
* Note 2: valid ElecTypes are: ACCTemp(DegF) ACCTemp(DegC) Digital i2 Controller Technical Reference
143
Page 150
i2850 Series I/O Point Assignments Function
Input Point Assignment
Input 1 Input 2 Input 3 Input 4 Input 5
1 2 3 4 5
* see note 1 * see note 1 * see note 1 * see note 1 * see note 2
Airflow 1 (i2850 & i2853) Airflow 2 (i2853 only)
8 7
Voltage Voltage
Function Output 1 Output 2 Output 3 Output 4
Output Point Assignment 1 2 3 4
* Note 1: valid ElecTypes are: Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised * Note 2: valid ElecTypes are: ACCTemp(DegF) ACCTemp(DegC) Digital
144
Schneider Electricn
Electrical Type
Electrical Type Digital, Tri-State Digital, Tri-State Digital Tri-State
Page 151
i2865/866, i2865-V/866-V Series I/O Point Assignments Function Universal Input 1 Universal Input 2 Universal Input 3 Universal Input 4 Smart Sensor Input Airflow Sensor Input
Actuator Output 3 Output 4 Output 5 Output 6 Output 7
Input Point Assignment i2865/-V i2866/-V 1 1 2 2 3 3 4 4 5 5 7
7
* See Note 1 * See Note 1 * See Note 1 * See Note 1 * See Note 2 Voltage
Output Point Assignment i2865/-V i2866/-V 1 1 3 4 5 − −
Electrical Type
3 4 5 6 7
Tri-State Digital, Tri-State Digital, Tri-State Digital Voltage Voltage
* Note 1: Valid ElecTypes are:
Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter
* Note 2: Valid ElecTypes are:
ACCTemp(DegF) ACCTemp(DegC) Digital
Actuator LCDState Attribute Note: Toggling the value of the LCDState attribute of Output 1 (the Actuator) performs the same action as pressing the Actuator Clutch button.
i2 Controller Technical Reference
145
Page 152
i2867 Series I/O Point Assignments Function
Input Point Assignment
Input 1 Input 2 Input 3 Input 4 Input 5
1 2 3 4 5
Function
Output Point Assignment
* see note 1 * see note 1 * see note 1 * see note 1 * see note 2
Electrical Type
Output 1 Output 2 Output 3 Output 4 Output 5
1 2 3 4 5
* see note 3 * see note 3 Digital, Tri-State Digital, Tri-State Digital
Output 6 Output 7
6 7
Voltage Voltage
* Note 1: valid ElecTypes are: Voltage ACC(Temp(DegF) ACCTemp(DegC) Digital Counter * Note 2: valid ElecTypes are: Digital ACCTemp(DegF) ACCTemp(DegC) * Note 3: valid ElecTypes are: When using CyberStation: Digital, Tri-State When using SX8000: Tri-State only
146
Electrical Type
Schneider Electricn
Page 153
i2885 and i2885-V Series I/O Point Assignments Function Universal Input 1
Input Point Assignment 1
Electrical Type
Universal Input 2
2
Airflow Sensor Input
7
Voltage
Actuator
Output Point Assignment 1
Tri-State
Output 3 Output 4
3 4
Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter
Digital, Tri-State Digital i2 Controller Technical Reference
147
Page 154
i2887(L) Series I/O Point Assignments Function Universal Input 1
Input Point Assignment 1
Universal Input 2
2
Universal Input 3
3
Smart Sensor Input
4
Triac Output 1 Triac Output 2 Triac Output 3 Triac Output 4
Output Point Assignment 1 2 3 4
Relay Output 5
5
Electrical Type Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter ACCTemp(DegF) ACCTemp(DegC) Digital
* see note 1 * see note 1 * see note 1 * see note 1 Digital
* Note 1: valid ElecTypes are: When using CyberStation: Digital, Tri-State When using SX8000: Tri-State only
148