Andover Infinet i2 Controller Technical Reference: Operation/Programming, pages 155 to 162

Pages 155 to 162 of 190, from Andover Infinet i2 Controller Technical Reference

The original document is the PDF (8.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls i2850 and Schneider i2850

Page 155

i2920 Series I/O Point Assignments Function

Input Point Assignment

Electrical Type

Input 1 - 16

1 - 16

Voltage ACCTemp(DegF) ACCTemp(DegC) Digital Counter Supervised

Input 17

17

ACCTemp(DegF) ACCTemp(DegC) Digital

Function

Output Point Assignment

Electrical Type

Output 1-8

1-8

Digital, Tri-State

Output 9-16

9-16

Voltage and Current i2 Controller Technical Reference

149

Page 156

Expansion Point Assignments xP Expansion Module points add to the existing points within a controller. The point assignment in the first xP module connected to a controller will be one more than the highest point number that exists in the controller. Example: When adding 8 Digital inputs (xPDI8) to an i2853 controller, the first point in the DI8 will be assigned point # 9 (one higher than the highest input (Airflow 1)). Subsequent Expansion modules plugged into other expansion modules assume point assignments that are one higher than the previous module. The following table lists the first expansion input and output point assignments for each controller:

FIRST EXPANSION POINT ASSIGNMENTS Controller i2810 i2814 i2850 i2851 i2853 i2920*

First Expansion Point INPUT OUTPUT 10 9 10 9 9 6 6 6 9 6 18 17

* On Infinity systems using the SX8000 workstation, the i2920 does not support expansion modules. The SX8000 had a limitation to the number of inputs/outputs it supported on a single controller.

Actuator Programming & Use [i2865, 866, 885] The actuator motor provided in the i2 controllers that include a built-in actuator is controlled by sending a pulse to the actuator output (positive or negative) that corresponds to the desired position of the damper blade. Your program should limit the minimum pulse width to 1 second. Note: If the damper has reached its limit of motion, the manual override button is pressed and the actuator is moved manually it is necessary that you toggle the value of the LCDState attribute of output 1 (the actuator) to provide a damper reset. CAUTION: Be sure that the actuator has come to a full stop before changing directions.

150

Schneider Electricn

Page 157

Changing Actuator Rotation Direction [i2865/i2866] The i2865/866 controller actuator may be mounted in any of several orientations with respect to the damper. A small switch is provided inside the plastic cover of the controller that allows you to change the direction that the actuator moves when positive pulses are applied.

i2 Controller Technical Reference

151

Page 158

Changing Actuator Rotation Direction [i2885] The i2885 controller actuator may be mounted in any of several orientations with respect to the damper. A small jumper is provided on the controller that allows you to change the direction that the actuator moves when positive pulses are applied.

152

Schneider Electricn

Page 159

Actuator Programming & Use [i2865-V/866-V, 885-V] The actuator motor provided in the i2 controllers that include a built-in actuator is controlled by sending a pulse to the actuator output (positive or negative) that corresponds to the desired position of the damper blade. Your program should limit the minimum pulse width to 1 second. Note: If the damper has reached its limit of motion, the manual override button is pressed and the actuator is moved manually. It is necessary that you toggle the value of the LCDState attribute of output 1 (the actuator) to provide a actuator clutch release. CAUTION: Be sure that the actuator has come to a full stop before changing directions.

i2 Controller Technical Reference

153

Page 160

Changing Actuator Rotation Direction i2865-V/866-V & i2885-V The i2865-V/866-V, and 885-V controller actuator may be mounted in any of several orientations with respect to the damper. A small jumper is provided on the controller that allows you to change the direction that the actuator moves when positive pulses are applied.

154

Schneider Electricn

Page 161

Plain English Function Changes [i2885, i2885-V, and i2887(L) ONLY] The following Plain English system functions are not supported in the i2885, i2885-V and i2887(L) controllers:

UNSUPPORTED ACOS ARCCOSINE ARCSINE ARCTANGENT ARCTANGENT2 ASC ASIN ATAN ATAN2 CEILING CHR CLOSELIST COS COSINE

SINE STANDARD_DEVIATION STR_TO_DATE STR_TO_NUM STR_TO_TIME STRINGFILL TAB TAN TANGENT VAL

EXP EXPONENTIAL FACT FACTORIAL FIRST FLOOR GETOBJECT LAST LEFT LEN LENGTH LN LOG MID NUM_TO_STR OPENLIST RANDOM RIGHT RND ROUND SD SEARCH SIN i2 Controller Technical Reference

155

Page 162

Pre-Operation Checks 1. 2. 3. 4. 5.

Make sure the internal battery is present and the protective tab is removed. Make sure the power is wired properly (both wires have been connected). Make sure the controller is connected to a true earth ground. Make sure you have used the proper cables and wires at correct lengths. Make sure Infinet cables and shields have been properly wired.

Initial Power-Up Enable the external power source (or close the power connection). The controller starts automatically. If the controller has been off, outputs remain off. If you have pressed the internal RESET button, outputs turn off.

CPU Indicators Each device (controller or expansion module) includes a CPU indicator that can be used to determine the relative health of the unit. The following table indicates the nominal blink pattern of the CPU indicator LED for each device. Any blink rate other than that listed below might be considered abnormal, however, many factors affect the blink pattern. Refer to the Troubleshooting section for a complete discussion on “abnormal” blink rates. Device

Normal Blink Pattern i2 controllers xP I/O modules xP Display

5 times/second blinks the board number based upon position every 2 seconds 2 times per second

156