Andover Infinet i2 Controller Technical Reference: Troubleshooting, pages 163 to 172

Pages 163 to 172 of 190, from Andover Infinet i2 Controller Technical Reference

The original document is the PDF (8.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls i2850 and Schneider i2850

Page 163

9 . . . . . . Troubleshooting i2 Controller Technical Reference

157

Page 164

158

Schneider Electricn

Page 165

General Troubleshooting CPU Indicator Is Not Blinking If the CPU indicator is not blinking then the unit is not operating. This could be due to the loss of primary AC power or other internal dysfunction. Check that power is available and connected properly to the power terminals. This can be done using a multimeter reading the voltage across the L and N terminals. If power appears to be OK, remove power and all other connections from the unit. The fuse within the unit may have failed. To access the fuse, the controller housing itself must be disassembled. The housing consists of two pieces that are snapped together. Follow the illustrations below to open the housing of any controller and gain access to the fuse area of the printed circuit board. The cover of all i2 series controllers (except the i2865-V/866-V, i2885-V and the i2867) is designed the same. The illustration below depicts the i2850 controller:

i2850 Series example

The power fuse of all i2 series controllers is located adjacent to the input power terminals. Remove the plug-in power fuse component and check it for continuity with an Ohm meter. If the fuse is blown, replace it with a similar size fuse (it resides in a socket). A table listing the fuse types per controller model is listed on the following page. After replacement, take care re-mounting the cover.

i2 Controller Technical Reference

159

Page 166

Gaining Internal Access to the i2867 Follow the illustrations below to open the housing and gain access to the fuse area of the printed circuit board:

FUSE

Depress tabs found on both sides of the case

Fuse Location on the i2885

160

Schneider Electricn

Fuse Location on the i2887

Page 167

Fuse Location on the i2865-V/866-V/885-V

COVER LATCH

COVER LATCH

FUSE COVER LATCH

Controller Main Power Fuse Types Controller

Fuse Type

Part # i2850 Series

2A @ 125VAC, NANO

01-2180-006

3A @ 125VAC, SLOBLO, NANO

01-2180-010 i2887

1A @ 125VAC, SLOBLO, PICO

01-2100-491 i2887

3A @ 250VAC, 3AG

01-2100-207 i2920

3A @ 250VAC, 3AG i2865/866 i2865-V/866-V i2885 i2885-V i2867 i2600 Series i2800 Series i2810 Series

01-2100-207 i2 Controller Technical Reference

161

Page 168

Unit Appears Functional But Is Not Responding To CX Controller If the CPU indicator is blinking normally chances are that the unit is operational. However, in that the controller is a programmable unit, it is possible that there is a programming problem. Monitoring Infinet Activity Infinet communications can be monitored simply by observing the status of the TXD (transmit) and RXD (receive) LED indicators. During Infinet communications, both of these LEDs should show activity.

One Input or Output Appears to Be Not Working If the CPU indicator is operating and other inputs/outputs are operating properly there could be two reasons for the failure: ƒ

The Input or Output has been damaged. In this case contact a Schneider Electric representative for assistance.

ƒ

If this is the first time using the controller, perhaps the program controlling the input/output is not correct. Re-check your program.

CPU Indicator Is Not Blinking its “Normal Rate” The CPU indicator is affected by many internal conditions. Errant Plain English programs can change the blink pattern. It is important to realize that an “abnormal” blink pattern does not always indicate a hardware failure. The following are some suggestions of where to look when the blink pattern changes. Blink Pattern 2.5 times/second, equal time on and off

Symptom BOOT MODE (application is being uprevved, is not present or is corrupt.

2.5 times/second, short on, long off blink

NORMAL OPERATION ,however, the Error system variable*<>0 and there are entries in the error log.

*The Error System variable is incremented as errors are encountered. When its value is not zero it affects the blink rate. The variable can be cleared (set to zero) using the CyberStation workstation. This should clear the unusual blink condition. However, whenever there are errors in the system log, it is a good idea to determine the source of the error to prevent them from reoccurring. Most errors are not hardware-related. Your Plain English programs may be the source of the problem. Check to see if you have any disabled Plain English programs and then check the ErrorCode attribute for the particular program to view the reason for being disabled.

162

Schneider Electricn

Page 169

Internal Restart Button Should the controller appear to be non-responsive and all other attempts to revive it fail, try pressing the Restart button. The button is recessed behind the cover and is accessed using a non-metallic probe. Note: The i2865-V, i2866-V, i2885-V and i2887(L) have no Restart button. To restart these controllers, cycle the power.

i2 Controller Technical Reference

163

Page 170

Infinet Troubleshooting Troubleshooting Methodology The troubleshooting methodology described below shows you how to efficiently identify problems and their causes throughout the network. The first two steps in troubleshooting require the most time, but are the most crucial. The more thoroughly and accurately you complete those steps, the sooner you can isolate and correct the problem, and minimize the amount of time that the impaired network leg is disabled.

Define the Problem The first step in troubleshooting a communications problem is to define the problem. To do this, you must know how your network is configured. This is a good time to review the network documentation. If it does not exist or is incomplete, then take the time to complete it. The documentation should include: ƒ

The exact wiring configuration, with approximate distances for all lengths of cable.

ƒ

Notes detailing any deviations from specified cable types.

ƒ

A list of all symptoms. Run tests to make the symptoms list is as complete as possible. This list and the network documentation combined enable you to define the problem and focus your troubleshooting.

Identify the Cause Now the troubleshooting begins. You need to isolate each problem and associate it with an individual device or wire segment. You can accomplish this only by: ƒ

Segmenting the network to eliminate the symptom or ƒ

Using test equipment to identify the problem.

Fix the Problem Once you know the wire segment or device (controller or repeater, for example) that is causing the problem, you can fix the problem by repairing or replacing the malfunctioning device or defective cable.

164

Schneider Electricn

Page 171

Verify the Solution Now is the time to verify that your solution has really fixed the problem. To verify the solution, you need to: ƒ

Rerun tests for communications problems and ƒ

Compile a new symptoms list.

If your tests and symptoms list identify no symptoms, then the problem has been fixed. If symptoms persist, repeat the troubleshooting process from the beginning.

Defining the Problem on Infinet Defining any communications problem within Infinet requires preparing a network “asbuilt” map, compiling a list of symptoms, and comparing the two documents.

Preparing an Asbuilt Map An asbuilt map documents every network component and presents the network as it is actually constructed, identifying: ƒ

Every network connection in the order of its installation.

ƒ

Approximate distances of all twisted pair and fiber optic cable runs throughout the network.

ƒ

The part or model number of every cable.

An asbuilt map differs from the network map that usually reflects the network’s configuration guide. Preparing and thoroughly documenting an asbuilt map can save you time when troubleshooting, and becomes particularly useful when you need to: ƒ

Segment the network to isolate problems.

ƒ

Verify that no wiring rule violations exist.

i2 Controller Technical Reference

165

Page 172

Recognizing Symptoms Common to Infinet Problems The most common symptoms pointing to a problem with Infinet communications are: ƒ

Random or constant Infinet reconfigures

ƒ

Infinet controller randomly or constantly off-line

ƒ

Group of Infinet controllers randomly or constantly off-line

ƒ

Replaced Infinet controller off-line

ƒ

The CX or NetController’s inability to locate newly added Infinet controllers during LEARN

ƒ

Data corruption errors, also known as invalid Cyclic Redundancy Check (CRC) errors

ƒ

Programs that use point-to-point communications disabling

ƒ

Some Infinet controllers are missing Export information

ƒ

The Infinet controller fails to come back online after a PowerFail

Recognizing Infinet Error Messages The CX or NetController logs two types of Infinet error messages:

166

ƒ

Failed to respond to token pass

ƒ

Received invalid CRC

Schneider Electricn