Compiling a Symptoms List A symptoms list helps you: ƒ
Focus troubleshooting efforts in the area of the network where the problem actually occurs.
ƒ
Determine the actions you need to take or tools you need to apply to isolate the problem.
You can generate a complete symptoms list in the following ways: ƒ
Using system information.
ƒ
Running a Plain English program that monitors the following object attributes:
ƒ
Comm port Reconfigures
ƒ
Infinet Controller Attributes:
ƒ
Infinet Error
ƒ
InfinetErrCount
ƒ
InfinetErrTime
ƒ
Running a program that disables itself.
Programs that utilize point-to-point communications may disable in response to unsuccessful attempts at retrieving information. Unsuccessful attempts at retrieving information can include, for example, trying to retrieve information that the controller cannot have, or attempting to perform an illegal function, such as dividing by zero. When unsuccessful, the program sets its own state to Disable.
Notes on Point-to-Point Communication ƒ
Point-to-point communication occurs whenever a program on one controller explicitly requests a point’s attribute (the point’s actual value or state, for example) from the controller where the point resides.
ƒ
When the program refers to a point’s attribute, the program directly contacts the controller where that point resides and requests the current information for the point.
ƒ
Programs that use point-to-point communication automatically disable if the controller you are retrieving the point’s attribute information from does not respond.
i2 Controller Technical Reference
167
Page 174
Identifying the Cause of an Infinet Problem Once you have your symptoms list, you can try to identify the cause of the problem.
Identifying the Problem Type Use the data from the symptoms list and the asbuilt map to determine if the problem belongs to one of the following: ƒ
Single node
ƒ
Network segment
ƒ
Global network
Understanding Common Causes of Infinet Problems Common causes of Infinet problems include the following:
168
ƒ
Wiring open (physical break in the network wiring)
ƒ
Wiring short (wiring physically connects to other wiring or shield, or shorts to ground)
ƒ
Cabling rule violation
ƒ
Controller at different ground potential
ƒ
Repeater set to incorrect baud rate
ƒ
Controller in hardfail (software making the controller shut itself down)
ƒ
Duplicate ID due to incorrect replacement procedure
ƒ
Controller constantly resetting
ƒ
Controller hardware failure
Schneider Electricn
Page 175
Infinet Troubleshooting Tools and Techniques Use the following tools and techniques to help identify the causes of Infinet communications problems: ƒ
Segment the Infinet.
ƒ
Observe LEDs on i2200, i2210 repeaters and on Infinet controllers.
ƒ
Verify the integrity of the wire run (also called ringing out cable runs) with a meter.
ƒ
Measure ground potential with a meter.
ƒ
Observe Infinet waveforms with an oscilloscope.
ƒ
Test Infinet controller transceivers with a meter.
ƒ
Test other communication devices.
The order in which you apply troubleshooting tools and techniques depends on the symptoms that you identify. For example, if a controller does not come on line, you might first look at LEDs on that controller. However, if you know that the wiring preceding the controller is not defective, then you might choose to segment the network beyond the controller as a first step.
Segmenting Infinet Segmenting the network is a technique that helps you identify the location and cause of the problem. The easiest method to follow when segmenting is to disconnect one leg of a repeater at a time. With each disconnect, determine if the symptoms disappear. Continue segmenting until you can isolate the problem. The figure below illustrates this methodology.
If the problem continues, test the segment before the break
If the problem stops, segment again
Segmenting a Bus Topology i2 Controller Technical Reference
169
Page 176
Physically Segmenting Infinet To segment a network, disconnect one leg of the network at a time. As the example on the previous page shows, you usually break the network at equal intervals, as follows: Check your network documentation to determine the best location to segment the network. If your network is wired as a:
170
•
Star or distributed star - disconnect a single star.
•
Bus topology Problems can usually be found in Bus-based networks using a method called the “binary chop”. This technique involves identifying the offending leg of the network, disconnecting the physical connection approximately half way down the line and observing if the problem remains. Moving down the network in this manner usually isolates the problem equipment of wire. The diagram below indicates this technique graphically.
Schneider Electricn
Page 177
Testing an Infinet Cable with a Digital Multimeter A common practice for verifying that a length of cable is working is to twist the two conductors together at one end, go to the other end of the cable, and expect to measure a short. (0 Ω) A far better method is to use two resistors and: 1. Place one resistor value between plus (+) and minus (–) at one end of the cable. (250Ω) 2. Place the second resistor value between plus (+) and shield at the other end of the cable. (500Ω) 3. Go to the other end and measure from plus to minus (+ to –) and plus (+) to shield. Use this process to test for the following conditions: ƒ
Open - Plus (+), minus (–), or shield
ƒ
Short - Plus (+) to minus (–)
ƒ
Short - Plus (+) to shield
ƒ
Short - Minus (–) to shield
Measuring Ground Potential with a Digital Multimeter Signal potential refers to the horizontal plane along which signals are sent and received with respect to ground. RS-485 requires that all devices communicating with each other be at a reasonable ground potential. To measure the ground potential of any Infinet controller: ƒ
Use a voltmeter to measure between the Earth ground connection (for power) and the Infinet shield connection.
ƒ
This process lets you measure the ground difference between the Infinet controller and the ground at the repeater or CX or NetController where the shield connects to ground.
ƒ
Measure each voltage - AC as well as DC. A reading higher than 2 to 3V on either voltage indicates a grounding problem.
ƒ
Measure combined voltages using the formula below. If the result is greater than 7V, a grounding problem exists. Combined Voltage = DC + (1.4 x AC)
i2 Controller Technical Reference
171
Page 178
Evaluating Infinet Signal Levels with an Oscilloscope Note: When using the oscilloscope, be sure you begin testing at the CX, NetController or at a repeater port.
An oscilloscope is a valuable tool for troubleshooting Infinet, and can also improve your efficiency in solving intermittent wiring problems. Infinet is an RS-485 local area network operating at 19.2 Kbps. RS-485 is a differential signal, driven 0 to 5 V by older Infinet devices and 0 to 3.3 V by i2 devices.
+ − RS-485 Transceiver
Transorbs
172
Schneider Electricn
Page 179
The Ideal Signal On long cable runs with many Infinet devices attached, signal levels often attenuate (weaken). This situation does not present any problems as long as the positive (low) signal maintains a lower amplitude than the negative (high) signal. ƒ
It is not important to try to read or analyze the data using the scope. (You can use a protocol analyzer for that.) Rather, you are concerned with overall signal amplitude levels at this time.
ƒ
Ideally, i2 RS-485 signal levels are approximately .5 to 3.3V (.5 to 4.5 V for older Infinet devices and InfiLink repeaters), with the positive connection appearing as a true representation of data (data 0 = low; data 1 = high) and the negative connection being the opposite (inverted) of the positive connection, as shown in the example below:
.1 ms/Div
Note: i2 RS-485 signal levels are approximately .5 to 3.3V (.5 to 4.5 V for older Infinet devices and InfiLink repeaters)
i2 Controller Technical Reference
173
Page 180
Signal Trace - Short of the Minus (–) Connection to Ground The signal trace shown below indicates that a short from ground or a short to ground exists on the leg of the Infinet.
.1 ms/Div
Signal Trace - Shorted Transceiver on an Infinet Device The signal trace shown below indicates that at least one Infinet controller has a shorted transceiver (+).
.1 ms/Div
Note: i2 RS-485 signal levels are approximately .5 to 3.3V (.5 to 4.5 V for older Infinet devices and InfiLink repeaters)
174
Schneider Electricn
Page 181
Signal Trace - Infinet Device at a Different Ground Signal potential refers to the horizontal plane along which signals are sent and received with respect to ground. Signal transmission and receipt must occur within the same range of potential.
.1 ms/Div
Note: i2 RS-485 signal levels are approximately .5 to 3.3V (.5 to 4.5 V for older Infinet devices and InfiLink repeaters)
i2 Controller Technical Reference
175
Page 182
Signal Trace - Open on the Plus (+) Connection A signal with an open on the positive (+) connection displays a disintegrating signal trace, as shown. ƒ
A predominantly disintegrating trace pattern displaying on the oscilloscope indicates that you have segmented beyond the problem. Segment closer to the controller.
ƒ
A predominantly non-disintegrating trace pattern displaying on the oscilloscope indicates that you have segmented between the controller and the problem.
.1 ms/Div
Note: i2 RS-485 signal levels are approximately .5 to 3.3V (.5 to 4.5 V for older Infinet devices and InfiLink repeaters)
176