Page 183

Troubleshooting the i2200 Repeater Errors are easily diagnosed using the status indicators built-into the i2200 repeater. The illustration below points out the locations of the indicators

RS-232 Status Indicators The RD and TD indicators located at the top of the unit represent activity to and from a device connected to the RS-232 port.

RS-485 Status Indicators for Ports 2 through 5 The RD and TD indicators for ports 2 through 5 flash on and off to indicate their corresponding ports are receiving and transmitting Infinet signals.

RS-485 Status Indicators for Port 1 The RD and TD indicators for port 1 flash on and off to indicate the CX or NetController is receiving and transmitting Infinet signals. Note: You must use Port 1 for the connection to the CX or NetController.

i2 Controller Technical Reference

177

Page 184

Baud Rate Setting ƒ

The baud rate set via the switch on the right of the i2200 should match the rate set for Infinet in the software.

ƒ

Check the CommPort Baud attribute setting using PRINT on the Command line.

ƒ

Open the CommPort editor from the Continuum Explorer.

ƒ

Check the baud rate setting on the front of i2200.

Power Fuses If AC power to the i2200 fails but power is actually available, check the 2A, 250V, PICO, fuse Schneider Electric P/N 01-2100-440. You can use the same fuse on 115 V links as well as on 230 V links.

178

Schneider Electricn

Page 185

Troubleshooting the i2210 Repeater Errors are easily diagnosed using the status indicators built-into the i2210 repeater. The illustration below points out the locations of the indicators

RS-485 Status Indicators The RD and TD indicators flash on and off to indicate the CX or NetController is receiving and transmitting Infinet signals.

RS-485 Fiber Link Indicators The RD and TD indicators flash on and off to indicate their corresponding ports are receiving and transmitting Infinet signals.

Baud Rate Setting ƒ

The baud rate set via the switch on the right of the i2210 should match the rate set for Infinet in the software.

ƒ

Check the CommPort Baud attribute setting using PRINT on the Command line.

ƒ

Open the CommPort editor from the Continuum Explorer.

ƒ

Check the baud rate setting on the front of i2210.

Power Fuses If AC power to the i2210 fails but power is actually available, check the 2A, 250V, PICO, fuse Schneider Electric P/N 01-2100-440. i2 Controller Technical Reference

179

Page 186

Attaching the Infinet (RoamIO2) Service Tool RoamIO2 Hardware Adapter The RoamIO2 hardware adapter serves as an interface between the Infinet bus and a PC laptop or a hand-held Pocket PC. It allows you to view the configuration of the system and allows you to make local changes to points to facilitate troubleshooting.

The Service Port Each Andover Continuum controller and sensor includes a built-in Service Port for use during troubleshooting and for connecting to the wireless adapter. The Service Port is basically a special connection to the RS-485 Infinet network. There are several types of Service Port connectors. Controllers typically have a four-pin connector that is located next to or behind the RS485 Infinet connection. Some of the older models have an RJ11 telephone-type connector for the Service Port. Sensors have a mixture of types but the most common type is a round phono-style connector. The RoamIO2 includes cables and adapters for every type of Service Port connection. 180

Schneider Electricn

Page 187

CAUTION: Service Ports are used for troubleshooting and connecting to the wireless adapter. Connect only Schneider Electric approved troubleshooting tools to these ports.

Connecting the RoamIO2 to the Controller Connect the serial port of the PocketPC using an RS-232 adapter or directly from your laptop to the RoamIO2 hardware adapter. The connector on the RoamIO2 is a standard DB-9 male connection. Using an appropriate combination of cables and adapters connect the RoamIO2 to any Infinet controller’s service port. For complete instructions and information, see the Infinet Service Tool User’s Guide, 303001-989.

i2 Controller Technical Reference

181

Page 188

182

Schneider Electricn

Page 189

Andover Continuum I2 Controller Technical Reference

Page 190

Andover Infinet™ i2 Controller Technical Reference Document Number 30-3001-861 Revision E

30-3001-861

Andover Continuum I2 Controller Technical Reference