Page 1

LC1D25M7

Product data sheet Characteristics

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 220 V AC coil

Main Range

TeSys

Product name

TeSys D

Product or component type

Contactor

Device short name

LC1D

Contactor application

Motor control Resistive load

Utilisation category

AC-1 AC-3 AC-4

Poles description

3P

Pole contact composition

3 NO

[Ue] rated operational voltage

<= 300 V DC for power circuit <= 690 V AC 25...400 Hz for power circuit

[Ie] rated operational current

25 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit 40 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit

Motor power kW

11 kW at 380...400 V AC 50/60 Hz AC-3 15 kW at 500 V AC 50/60 Hz AC-3 15 kW at 660...690 V AC 50/60 Hz AC-3 5.5 kW at 220...230 V AC 50/60 Hz AC-3 11 kW at 415...440 V AC 50/60 Hz AC-3 5.5 kW at 400 V AC 50/60 Hz AC-4

Motor power hp

2 hp at 115 V AC 50/60 Hz for 1 phase motors 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors

Control circuit type

AC 50/60 Hz

[Uc] control circuit voltage

220 V AC 50/60 Hz

Auxiliary contact composition

1 NO + 1 NC

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Overvoltage category

III

Nov 27, 2018

1

Page 2

[Ith] conventional free air thermal current

40 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit

Irms rated making capacity

450 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1

Rated breaking capacity

450 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

120 A <= 40 °C 1 min power circuit 240 A <= 40 °C 10 s power circuit 380 A <= 40 °C 1 s power circuit 50 A <= 40 °C 10 min power circuit 100 A 1 s signalling circuit 120 A 500 ms signalling circuit 140 A 100 ms signalling circuit

Associated fuse rating

40 A gG at <= 690 V coordination type 2 for power circuit 63 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1

Average impedance

2 mOhm at 50 Hz - Ith 40 A for power circuit

[Ui] rated insulation voltage

600 V for power circuit certifications CSA 600 V for power circuit certifications UL 690 V for power circuit conforming to IEC 60947-4-1 690 V for signalling circuit conforming to IEC 60947-1 600 V for signalling circuit certifications CSA 600 V for signalling circuit certifications UL

Electrical durability

1.65 Mcycles 25 A AC-3 at Ue <= 440 V 1.4 Mcycles 40 A AC-1 at Ue <= 440 V

Power dissipation per pole

3.2 W AC-1 1.25 W AC-3

Protective cover

With

Mounting support

Plate Rail

Standards

CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508

Product certifications

BV CCC CSA DNV GL GOST LROS (Lloyds register of shipping) RINA UL

Connections - terminals

Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end Power circuit : screw clamp terminals 1 cable(s) 1.5...10 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 1 cable(s) 2.5...10 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 2 cable(s) 2.5...10 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 1 cable(s) 1...10 mm² - cable stiffness: flexible - with cable end Power circuit : screw clamp terminals 2 cable(s) 1.5...6 mm² - cable stiffness: flexible - with cable end Power circuit : screw clamp terminals 2 cable(s) 2.5...10 mm² - cable stiffness: solid - without cable end

Tightening torque

Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2

Operating time

4...19 ms opening

2

Page 3

12...22 ms closing Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

15 Mcycles

Operating rate

3600 cyc/h at <= 60 °C

Complementary Coil technology

Without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz 0.8...1.1 Uc operational at 60 °C, AC 50 Hz 0.85...1.1 Uc operational at 60 °C, AC 60 Hz

Inrush power in VA

70 VA at 20 °C (cos ϕ 0.75) 60 Hz 70 VA at 20 °C (cos ϕ 0.75) 50 Hz

Hold-in power consumption in VA

7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz 7 VA at 20 °C (cos ϕ 0.3) 50 Hz

Heat dissipation

2...3 W at 50/60 Hz

Auxiliary contacts type

Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1 Type mirror contact (1 NC) conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching current

5 mA for signalling circuit

Minimum switching voltage

17 V for signalling circuit

Non-overlap time

1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact

Insulation resistance

> 10 MOhm for signalling circuit

Environment IP degree of protection

IP20 front face conforming to IEC 60529

Protective treatment

TH conforming to IEC 60068-2-30

Pollution degree

3

Ambient air temperature for operation

-5...60 °C

Ambient air temperature for storage

-60...80 °C

Permissible ambient air temperature around the device

-40...70 °C at Uc

Operating altitude

3000 m without derating in temperature

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

Vibrations contactor open 2 Gn, 5...300 Hz Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor closed 15 Gn for 11 ms Shocks contactor open 8 Gn for 11 ms

Height

85 mm

Width

45 mm

Depth

92 mm

Product weight

0.37 kg

Offer Sustainability Sustainable offer status

Green Premium product

RoHS (date code: YYWW)

Compliant - since 0627 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity

REACh

Reference not containing SVHC above the threshold Reference not containing SVHC above the threshold

Product environmental profile

Available

Product end of life instructions

Available

Product environmental End of life manual 3

Page 4 read from a scan by OCR; it may hold reading errors

Contractual warranty

Warranty period 18 months

4 Schneider

Page 5

Product data sheet Dimensions Drawings

LC1D25M7

Dimensions

(1) (2)

Including LAD 4BB Minimum electrical clearance

LC1

D25…D38 (3-pole)

b without add-on blocks

85 b1 with LAD 4BB

98 with LA4 D●2

114 with LA4 DF, DT

123 with LA4 DW, DL

130 c without cover or add-on blocks with cover, without add-on blocks

92 c1 with LAD N or C (2 or 4 contacts)

123 c2 with LA6 DK10, LAD 6K10

135 c3 with LAD T, R, S

143 with LAD T, R, S and sealing cover

147

(1)

Including LAD 4BB.

(1) (1)

(1)

90

5

Page 6 read from a scan by OCR; it may hold reading errors

Product data sheet LC1D25M7

Connections and Schema

Wiring

~ 32 5/L3

13/NO 21/NC

A2 A 271 oll 4/T2 6/T3

14

22 ectric