Page 186
Fc215 MUL Symbol
Multiply register by constant in binary (8 bits × 8 bits) (MULtiply) Fc215 MUL n
S1
〔Example for use〕
D
Function
The contents of the register S are multiplied by the octal constant "n" in binary and its results are stored in the registers D and D+1.
Operation
S1×n→D, D+1
Range of S1
コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777
01000
Fc215 09100 MUL
123
Condition
09100 11011000
コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776
× Octal constant 123 01010011 1
2
3
Rising edge of input signal (OFF to ON) 19001
Contents Unchanged of S1 Contents Lower digits of result of D After operation Contents Upper digits of result of D+1
Flag
19000
When the input condition 01000 changes from OFF to ON, the contents of the register 09100 are multiplied by the octal constant 123 in binary and its results are stored in the registers 19000 and 19001.
Range of "n" 000 to 377 (8)
Range of D
Instruction 01000 STR Fc215 09100 123 19000
19000
0100011000001000
9
Zero 07357
Carry 07356
Error 07355
Non-carry 07354
0
0
0
0
Similarity insturctions: F-215, F-215w, Fc215w
9・ 111
Page 187
Fc215w MUL
Multiply register by constant in binary (16 bits × 16 bits) (MULtiply) Fc215w MUL
Symbol n
S1
〔Example for use〕
D
Function
The 16 bits contents of the registers S1 and S1 +1 are multiplied by an octal content "n" in binary and its results are stored in the registers D, D+1, D+2 and D+3.
Operation
(S1, S1+1)×n→D, D+1, D+2, D+3
Range of S1
コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776
01000
Fc215w 09100 006430 19000 MUL
When the input condition 01000 changes from OFF to ON, the 16 bits contents of the registers 09100 and 09101 are multiplied by the octal constant 006430 in binary and its results are stored in the registers 19000 to 19003. 09101
Range of "n" 000000 to 177777 (8)
Range of D
Condition
× Octal constant 006430 0000110100011000 0
0
6
4
3
0
Rising edge of input signal (OFF to ON)
Contents of D Contents of D+1 After operation Contents of D+2 Contents of D+3
Flag
09100
0000010111000110
コ0000 to コ1574 b0000 to b0774 09000 to 09774 19000 to 19776 29000 to 29774 39000 to 39774
Contents of S1, S1+1
9
Instruction 01000 STR Fc215w 09100 006430 19000
Unchanged 19003
Lower digits of result
19002
19001
19000
00000000010010111001100010010000
Result Result Upper digits of result Zero 07357
Carry 07356
Error 07355
Non-carry 07354
0
0
0
0
Note 1: Be sure to use even addresses for registers S1 and D. Similarity insturctions: F-215, F-215w, Fc215
9・ 112
Page 188
F-216 DIV
Divide register by register in binary (8 bits ÷ 8 bits) (DIVide) F-216 DIV
Symbol
S1
S2
〔Example for use〕
D
Function
The 8 bits contents of the register S1 are divided by the 8 bits contents of the register S2 in binary and its quotient is stored in the register D and remainder in the register D+1.
Operation
S1÷S2→D, D+1
Range of S1
Range of S2
Range of D
Condition
F-216 09000 09001 09002 DIV
When the input condition 10000 changes from OFF to ON, the contents of the register 09000 are divided by the contents of the register 09001 in binary and its quotient is stored in the registers are 09002 and remainder in the register 09003.
コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777 コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777 コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776
Before operation
After operation
09000 1 1 0 0 0 1 1 1
Quotient 0 0 0 0 1 0 0 1 09002
09001 0 0 0 1 0 1 0 1
Remainder 0 0 0 0 1 0 1 0 09003
9
Rising edge of input signal (OFF to ON)
Contents of S1 Contents of S2 Contents After of D operation Contents of D+1
1 0 1 0 1
Unchanged Unchanged Quotient
Unchanged if the contents of the registers, S2 is 000 (8).
Remainder Contents of S2
Flag
10000
Instruction 10000 STR F-216 09000 09001 09002
000 (8) Other than above
Zero 07357
Carry 07356
0
0
Error Non-carry 07354 07355
1 0
0
Similarity insturctions: F-216w, Fc216, Fc216w
9・ 113
1 0 0 1 1 1 0 0 0 1 1 1 1 0 1 0 1 1 1 1 1 1 1 0 1 0 1 1 0 1 0
Page 189
Divide register by register in binary (15 bits ÷ 15 bits) (DIVide)
F-216w DIV
F-216w DIV
Symbol
S2
〔Example for use〕
D
Function
The 15 bits contents of the registers S1 and S1+1 are divided by the 15 bits contents of the registers S2 and S2+1 in binary and its quotient is stored in the registers D and D+1 and the remainder in the registers D+2 and D+3.
Operation
(S1, S1+1) ÷ (S2, S2+1) →D, D+1, D+2, D+3
Range of S1
Range of S2
Range of D
9
S1
Condition
F-216w 19000 19002 19004 DIV
When the input condition 10000 changes from OFF to ON, the 15 bits contents of the registers 19000 and 19001 are divided by the 15 bits contents of the registers 19002 and 19003 in binary and its quotient is stored in the registers 19004 and 19005 and the remainder in 19006 and 19007.
コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776 コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776 コ0000 to コ1574 b0000 to b0774 09000 to 09774 19000 to 19774 29000 to 29774 39000 to 39774
19001
19000
110110011100100
÷ 19003
19002
000010000101100
Rising edge of input signal (OFF to ON)
Contents of S1, S1+1 Contents of S2, S2+1
19005
19004
0000000000011010
Unchanged
Quotient
Unchanged
Contents Lower digits of quotient of D Contents Upper digits of After quotient of D+1 operation Contents Lower digits of remainder of D+2 Contents Upper digits of remainder of D+3
Flag
10000
Instruction 10000 STR F-216w 19000 19002 19004
Contents of S2, S2+1 000000 (8) Other than above
19007
Unchanged if the contents of the registers S2 and S2+1 are 000000 (8).
Zero 07357
Carry 07356
0
0
Remaider
MSB (bit 7) of the registers 19001 and 19003 will be disregarded.
Error Non-carry 07354 07355
1 0
19006
0000000001101100
0
Note 1: Be sure to use even addresses for registers S1, S2 and D. Similarity instructions: F-216, Fc216, Fc216w
9・ 114
Page 190
Fc216 DIV Symbol
Divide register by constant in binary (8 bits ÷ 8 bits) (DIVide) Fc216 DIV
S1 n
〔Example for use〕
D
Function
Contents of the register S1 are divided by an octal constant "n" in binary and its quotient is stored in the register D and the remainder in D+1.
Operation
S1÷n→D, D+1
Range of S1
コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777
02000
Fc216 コ0000 DIV
123
Condition
コ0000 11111111
÷
コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776
Octal constant 123 01010011
1
2
3
Rising edge of input signal (OFF to ON)
Contents Unchanged of S Contents Quotient of D After Contents Remainder operation of D+1 Contents of S2
Flag
09000
When the input condition 02000 changes from OFF to ON, the contents of the register コ0000 are divided by the octal constant 123 and its quotient is stored in the register 09000 and the remainder in 09001.
Range of "n" 000 to 377 (8)
Range of D
Instruction 02000 STR Fc216 コ0000 123 09000
000 (8) Other than above
09001
09000
0000011000000011
Unchanged if "n" =000.
Zero 07357
Carry 07356
0
0
Error Non-carry 07354 07355
1 0
0
Similarity insturctions: F-216, F-216w, Fc216w
9・ 115
Remainder
Quotient
9
Page 191
Fc216w DIV
Divide register by constant in binary (15 bits ÷ 15 bits) (DIVide) Fc216w DIV
Symbol
S1 n
〔Example for use〕
D
Function
The 15 bits contents of the registers S1 and S1+1 are divided by an octal constant "n" in binary and its quotient is stored in the registers D and D+1 and the remainder in D+2 and D+3.
Operation
(S1, S1+1) ÷ n→D, D+1, D+2, D+3
Range of S1
コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776
02000
Instruction 02000 STR Fc216w コ0000 073064 09000
Fc216w コ0000 073064 09000 DIV
When the input condition 02000 changes from OFF to ON, the 15 bits contents of the registers コ0000 and コ 0001 are divided by the octal constant 073064 in binary and its quotient is stored in the registers 09000 and 09001 and the remainder in 09002 and 09003.
コ0001
Range of "n" 000000 to 077777 (8)
コ0000
111111111111111
Range of D
Condition
9
コ0000 to コ1574 b0000 to b0774 09000 to 09774 19000 to 19774 29000 to 29774 39000 to 39774
0111011000110100
0
Rising edge of input signal (OFF to ON)
Contents of S1, S1+1
Contents of D Contents of D+1 After Contents operation of D+2 Contents of D+3
Flag
÷ Octal constant 073064
Unchanged
3
0
09001
6
4
09000
0000000000000001
Lower digits of quotient Upper digits of quotient Lower digits of remainder Upper digits of remainder Octal constant "n" 000000 Other than above
7
Quotient
Unchanged if "n" =000000.
09003
09002
0000100111001011 Remainder
Zero 07357
0
Carry 07356
0
Error Non-carry 07354 07355
1 0
MSB of the register コ0001 will be disregarded.
0
Note 1: Be sure to use even addresses for registers S1 and D. Similarity insturctions: F-216, F-216w, Fc216
9・ 116
Page 192
9-4
Ladder design precautions Since the programmable controller operates in the serial sequence, the ladder chart designed for the relay board may not be directly executed by the programmable controller. Also, it may not require the use of the relay board one-way control diode for the programmable controller, but it allows the use of unlimited number of auxiliary contact points. Difference in ladder design between the relay board and the programmable controller should be well understood to comprise more effective ladder chart.
[1] Relay circuit that needs revision Example 1: 00000
00002
00400
(a)−1 (a)
00001
00003
00401 00000
The programmable controller can not execute the ladder chart (a) without revising it. 00000
00002
00002
00400
00003
00401
00001
00000
00400 00001
(b)
00001
STR OR AND OUT STR OR AND OUT
00000 00001 00002 00400 00000 00001 00003 00401
Instruction STR OR AND OUT
9
00000 00001 00002 00400
(a)−2 00000 F-30 MCS 00001
The part (b) can be executed with the program shown.
00002
00400
00003
00401
Figure below shows transition in the accumulator contents, when the program (b) is executed. F-31 MCR
Instruction
00000
STR OR OUT STR AND OUT STR AND OUT
00000 00001 04000 04000 00002 00400 04000 00003 00401
00002 00400 00003 00401
(a)−3
00000
00001
Result of
AND 00002
Result of
00000
04000
00001 00001
00000 00002 00001
04000
00002
00400
04000
00003
00401
00000 00002
OUT 00100
00000 00001
Accumulator contents
STR 00000 OR
STR OR F-30 STR OUT STR OUT F-31
Result of
00001
As the result represented by 0 or 1 is stored every time one programmable step is executed in the accumulator, execution up to AND 00002 deletes the result of so that it could not be reflected on 00003. So, it has to be revised in the following was for a programmable controller ladder chart.
(Use as auxiliary relay for 04000.)
00000 00001
9・117
Page 193
Example 2: As current flows to 00002 from both 00000 and 00001 with the relay board ladder chart of (a), it does the action identical to the ladder chart that revised for the programmable controller program (b). (a)
(b)
Instruction 00400
00000 00400
00000
00001
00001 00002 00002
00000 00002
00401
00401
00001
STR 00000 STR 00001 AND 00002 OR STR OUT 00400 STR 00000 AND 00002 OR 00001 OUT 00401
There is no concept applicable for the programmable controller that the current flows to one contact symbol from both lines as in 00002 of (a) above. Because execution takes place serial from the address 00000 to the END instruction for the programmable controller, it is not possible to go through the same contact symbol once again on the ladder chart. Example 3: On account of the one-way control diode D1 in the relay board circuit (a), the current does not flow from 00001 through 00002, but it performs the same action as the programmable controller ladder chart that revised for the programmable controller program (b). (a)
(b) 00000
00002 D1 00003
00002
00400
00000
00003
00401
00400
9 00001
Instruction 00000
00401
00001
STR AND OUT STR OR AND OUT
00000 00002 00400 00000 00001 00003 00401
It is not possible for the programmable controller to program the one-way control diode D1 as in (a). Three examples given are often used for the relay board to permit use of the relay with less contacts and simple wiring. On the other hand, with the programmable controller, there is no need of paying attention for number of contacts used as it has the data memory that offers unlimited number of contacts. It is preferable to have the ladder chart designed for recognition at a glance.
With the relay method, the following is required every time a contact is added. ① Addition of a relay
Unlimited
Space, cost, reliability ② Addition of wirings
9・118
The data memory of the programmable controller does not affect space, costs, and reliability even if more contacts are used because it can be a relay that have unlimited number of contacts.
Page 194
[2] Input and output batch processing • As already discussed in "8-1 Operational cycle," the JW10 performs data exchange between the data memory and the I/O port at every scan cycle. • The I/O processing is scanned from a younger number first of relay number. ① For the input port, the ON/OFF state of the external contact connected to the input port is read into the data memory. ② For the output port, the ON/OFF state of the respective data memory is transferred to the output port. • After completing the above operation to the all I/O module, it enters the user program execution. • Because the programmable controller executed I/O processing in the batch mode, it will be necessary to pay attention to the following points designing the ladder. (1) As ON/OFF transition of the external contact is read into the data memory one at a time of every scan cycle during the I/O processing, a change in the ON/OFF state of the external device during that scan cycle may not affect the data memory contents (assigned to the input). Therefore, the "Input racing phenomenon" discussed in the following passage does not occur. (2) For the resultant ON/OFF state is written from the data memory to the output port once in each scan cycle of the I/O processing, the result is therefore sent to the output port during the I/O processing of a next scan cycle.
Input racing phenomenon The following phenomenon may occur in the program controller that the input port ON/OFF state is read every time an instruction is executed. B
①
C
②
B
③
D
④
Scanning order
The program that sets the coil C ON when the input B is ON and the coil D ON when the input B is OFF. In the above program, C=D should be established. But, assume now that B was ON (C=ON) when the state of the input B is read from the input port to the accumulator at step ① . If the state of the input B has changed to OFF before the operation at ③ , B is handled OFF during the operation at ③ . This will establish a contradiction that the coil D is ON, while both C and D are ON. It may result in the trouble whose cause is unknown as malfunction may or may not be evoked depending on the input timing. However, such a problem may not occur with the batch I/O processing programmable controller.
9・119
9
Page 195
[3] Influence by programmed sequence The programmable controller performs operation in serial sequence from the top to the end of the program step, and the same operation is repeated (cyclic scan method). (1) Swapping orders programmed
(a)
00000
00400
00400
00401
I/O
User program execution
I/O
User program execution
(b)
00401
00000
00400
I/O
I/O
User program execution
I/O
User program execution
I/O
Contact
Contact
00000
00000 Data memory
Data memory
Data memory
Data memory
00400
00400
9
00400
Output port
Output port
Data memory
Data memory
00401
00401
1 scan time Output port
Output port
When the input 00000 turns ON for the program of (a), the outputs 00400 and 00401 turn ON in the same scan cycle, but 00401 turns ON with a delay of 1 scan cycle for with (b). To use a coil auxiliary contact, consideration must be given when programming that "a change in the state of the auxiliary contact before the coil, comes effective in a next scan cycle that the change took place for the coil." (2) Multiple use of the coil If a 55(H) is stored in the register #055 in the system memory, multiple use of the coil (OUT instruction) will be possible. (The option is available in version 1.4 or later ROM code.) If the same relay number is used more than once as a coil, the contents of data memory will change according to the program's contents. In this case, the JW10 will read the operation results of the program step that was written from data memory to the output section. ①
00000
00400
I/O Contact
00400
00000 Data memory
②
OFF Contact OFF
00001
00002
Data memory
00400
③
Contact
00002 Data memory
Data memory
00400 Output port
9・120
③
User program process
① 00001
②
I/O