The text of a manual · part 25 of 37
Sharp Programmable Controller New Satellite JW10 User's Manual: Chapter 10 System Design
Pages 197 to 199 of 307, from Sharp Programmable Controller New Satellite JW10 User's Manual
The original document is the PDF (5.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Sharp jW-10CM
Page 197
Chapter 10. System Design 10-1 System design procedure The system design procedure is virtually as the same as those of the other conventional relay controllers. The following is an example of the system design procedure of the JW10.
Start System design
Select of module
Preparation of operation flow chart
Address allocation
Individual operation check
Ladder design of each module
Wiring input/output
Programming
10 device with JW10
Debugging Revise program
Trial operation
NG
OK Save program
Run
10・1
Store in FD,HD and ROM
Page 198
10-2 Cautions on system design A principle difference between a programmable controller (PC) and a conventional relay circuit is that a PC controls each operation cyclically (in series), whereas relay circuit controls it in parallel. Therefore, relay circuits limit the effect of an abnormal operation to a block. However, a PC allows abnormal operations of the whole system when an abnormal condition occur. In order to create a fail-safe system, we recommend preparing independent external protective circuits for following functions, which may cause a breakdown of machine or injury to workers. • Emergency stop circuit, • Protection circuit, • Operating circuit of high voltage device. Also, be aware of the operation response time, as a PC operates using cyclic control.
85 to 250 VAC
10
JW10 basic module Input port
(−) (+)
85 to 250VAC • Connecting the input port and output port for lighting lamps in front of emergency stop circuit makes it possible to grasp the stop condition of devices. • Output status while the JW10 stops operation is determined by setting value of system memory #206. #206 = 00(H): Reset all outputs (initial value) #206 = 55(H): Latch the status just before the stoppage.
COM
24 VDC
Output port
Operation Emergency stop preparation
JW10 stop MC
Thermal MC switch Output port
• Emergency stop circuit 1) In case of JW-1424K/1442K/1624K/1642K Connect halt output of the JW10 (Relay output 250 VAC/30 VDC, 1A) 2) In case of JW-1324K/1342K Normally turns ON output relay and connects it with an emergency stop circuit. In this case, set system memory #206 as 00(H) 07366
Output relay
MS1
MS2 MS2
MS1
10・2
• Interlock circuit Prepare external interlock circuit to prevent reverse operation, damage of machines and injury of workers.
Page 199
10-3 Allocation of relay number • Relay numbers are allocated with sequential allocation taking 00000 and 00400 as top number for input relay and output relay, respectively. • The below shows relay number allocation when the system is configured to maximum for each basic module.
Basic module
Input/output relay address (upper section: relay number, lower section: byte address) Expansion module Basic module
(At maximum configuration)
JW-1324K/1342K
JW-1424K/1442K
JW-1624K/1642K
00000 to 00017 コ0000 to コ0001 00400 to 00413 ※1 Output relay コ0040 to コ0041 ※1 00000 to 00027 Input relay コ0000 to コ0002 00400 to 00417 Output relay コ0040 to コ0041 00000 to 00043 ※2 Input relay コ0000 to コ0004 ※2 00400 to 00427 Output relay コ0040 to コ0042 Input relay
Not connectable Not connectable 00030 to 00067 コ0003 to コ0006 00420 to 00457 コ0042 to コ0045 00050 to 00107 コ0005 to コ0010 00430 to 00467 コ0043 to コ0046
※ 1 In case of JW-1324K/1342K, output relays 00414 to 00417 are dummy areas (auxiliary relay). ※ 2 In case of JW-1624K/1642K, input relays 00044 to 00047 are dummy areas (auxiliary relay). ■ Allocation example of relay number
Example 4
Example 3
Example 2
Example 1
Configuration of module JW-1424K
JW-114S
Basic module
Expansion module (1)
JW-1624K
JW-112N JW-1124NS
Basic module JW-1624K
Basic module JW-1624K
Basic module
Expansion Expansion module (1) module (2) JW-1324NS JW-1124NS
Expansion Expansion module (1) module (2) JW-1324NS JW-1324NS
Expansion Expansion module (1) module (2)
10 Input/output relay address (upper section: relay number, lower section: byte address) Basic module Expansion module (1) Expansion module (2) 00000 to 00027 コ0000 to コ0002 00400 to 00417 00420 to 00437 Output relay コ0040 to コ0041 コ0042 to コ0043 00000 to 00043 00050 to 00067 00070 to 00077 Input relay コ0000 to コ0004 コ0005 to コ0006 コ0007 00430 to 00437 00400 to 00427 Output relay コ0043 コ0040 to コ0042 00000 to 00043 00050 to 00067 00070 to 00077 Input relay コ0000 to コ0004 コ0005 to コ0006 コ0007 00400 to 00427 00430 to 00447 00450 to 00457 Output relay コ0040 to コ0042 コ0043 to コ0044 コ0045 00000 to 00043 00050 to 00067 00070 to 00107 Input relay コ0000 to コ0004 コ0005 to コ0006 コ0007 to コ0010 00400 to 00427 00430 to 00447 00450 to 00467 Output relay コ0040 to コ0042 コ0043 to コ0044 コ0045 to コ0046 Input relay
Note 1: Second and third digit figures of input and output relays can be marked using oil-based ink on the address writing column of the expansion module. Note 2: Analog input module (JW-14AD) and analog output module (JW-12DA) are not occupied input/ output relays. 10・3
07 0 1 2 3
Address writing column
4 5 6 7
IN
45 0 1 2 3 OUT 4 5 6 7
JW-1124NS