Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 28 of 37

Sharp Programmable Controller New Satellite JW10 User's Manual: Chapter 13 How to Use Communication Port, pages 217 to 225

Pages 217 to 225 of 307, from Sharp Programmable Controller New Satellite JW10 User's Manual

The original document is the PDF (5.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Sharp jW-10CM

Page 217

Chapter 13. How to Use Communication Port 13-1 Communication port [1] Function of communication port • The JW10 has a communication port for using any of computer link, data link or remote I/O. • Each function is determined by values set on system memory (#234).

#234 00(H) 01(H) 02(H)

Communication mode Computer link mode Data link mode Remote I/O mode

(1) Computer link mode • The JW10 can communicate to a host computer or an LCD control terminal. (The JW10 can receive host computer's commands and response to the host computer.) • The JW10 can communicate even in stop mode or error mode. (Except communication functional failure.) (2) Data link mode • The JW10 (master) can communicate to the JW10 (salve). (Programless communication) • Even one slave station of the JW10 is not connected, or is in stop mode or error, a master station of the JW10 communicates with other normal slave stations of JW10. (3) Remote I/O mode • The JW10 (master) can communicate to JW10 (slave) as remote I/O. • If one slave station of JW10 is not connected or is error, the JW10 master station stops operation and communication with all the other slave stations.

[2] Wiring

13

• Communication port of the JW10 is L1, L2, and SHLD terminals of the basic module. (Lower terminals of JW-1624K) AC-L AC-N COM.B COM.C COM.D COM.E 405 407 410 412 COM.G 415 417 420 422 424 426 COM.I HLT-C L2 FG 400 401 402 403 404 406 COM.F 411 413 414 416 COM.H 421 423 425 427 HLT L1 SHLD

Insulation tape

(Note 1) Class-3 grounding Twisted wire (Note 2)

• See "6-1 Precautions for wiring." • Make sure to use our recommended shielded twist pair wires for communication lines. Recommended cable: S-IREV-SB 2 × 0.5 (Hitachi Cable Ltd.) Note 1: FG terminal and SHLD terminal are not connected inside. Note 2: Connecting in relay shield of shield cables externally using 0.5 mm2 sectional area or so twisted wires (shorter than 30 mm) offers easy wiring to terminals.

13-1

Page 218

13-2 Computer link [1] Communication specifications • A host computer can communicate with maximum 63 modules of JW10. • With this communication, you can monitor operation, collect data, instruction operation, and change setting value of the connected JW10 modules in personal computer or the like.

Host computer

JW10 (slave station 001) JW10 (slave station 002) JW10 (slave station 077)

RS-232C

RS-232C/422 converter (Z-101HE)

RS-422A Total length max. 1 km

Max. 63 stations

Item

Specifications

Data transfer standard Transfer rate Data style

13

EIA RS-422A or equivalent, Start-stop sychronous system 38400, 19200, 9600, 4800, 2400, 1200, 600, 300 bits/s Start bit : 1 bit Data length : 7, 8 bits Parity bit : 1 bit (odd, even, none) Stop bit : 1, 2 bits Character used ASCII, alphanumeric characters Error check Parity check, sum check No. of stations connected Max. 63 sets Communication line Shielded twisted pair cable. Cable total length: 1 km (party line connection) 2-wire system

[2] Wiring RS-232C/422 converter Z-101HE

Frame ground

FG 1 FG RD(+) Transmit data TD 2 TD RD(-) Receive data RD 3 RD SHIELD Request to send RS 4 RS Signal ground SG 7 SG

JW10 (001)

JW10 (002)

L1 L2

L1 L2

SHLD

SHLD

Class-3 grounding

Class-3 grounding

〜 〜 〜 〜〜 〜〜 〜

Host computer

JW10 (076)

JW10 (077)

L1 L2

L1 L2

SHLD

SHLD Class-3 grounding Class-3 grounding Class-3 grounding Shielded twisted pair cable

Total cable length: Less than 1 km

Less than 15 m RS-232C

RS-422A

Note 1: Do class-3 grounding for SHLD terminal. The operation without class-3 grounding may cause malfunction due to noise. Note 2: Never branch a communication cable into more than 3 lines.

Good

Bad

Conjunction terminal

Connection using a connector

13-2

Page 219

[3] Setting system memory • When using computer link mode, set system memory as follows. #234 Communication mode

00(H): Computer link mode D7 D6 D5 D4 D3 D2 D1 D0 0

#236 Transfer specifications

Transfer rate (300 to 38400 bits/s) Parity (none, odd, even) Stop bit (1 bit, 2 bits) D7 Data length D5 Stop bit 0 0 7 bits 1 bit 1 1 8 bits 2 bits

#237 Local number

Data length (7 bits, 8 bits) D4 D3 Parity D2 D1 D0 Transfer rate (bit/s) 1 1 1 0 0 None 38400 0 0 0 0 1 Odd 19200 0 0 1 1 0 Even 9600 1 1 Disable 0 1 0 4800 0 1 1 2400 1 0 0 1200 1 0 1 600 1 1 0 300

001 to 077(8)

Note 1: Communication mode and station number are set on system memory. We recommend to mark these settings on a label and stick it on each case for easily readable the set contents.

[Example of label]

Computer link #001

[4] Communication format • When the JW10 receives “command” from a host computer, the JW10 executes processing in accordance with its command contents and sends “response” to the host computer. • If an error occurs in the processing contents, the JW10 sends “error response.” ① Command (host computer to JW10) Sum check area A A R S S C D D ? Command content C C I (H) (L) (H) (L) R

② Response (JW10 to host computer) Sum check area A A R S S C D D # Response content C C I (H) (L) (H) (L) R

Error response where an error occurs Sum check area A A R E E S S C D D % C C C C I (H) (L) (H) (L) (H) (L) R

13-3

13

Page 220

(1) Identification symbol ASCII character ASCII code : ? # % CR

3A(H) 3F(H) 23(H) 25(H) 0D(H)

Contents Header (indicates start of command or response) Indicates “command” Indicates “response” at normal operation Indicates “error response” Termination symbol (indicates termination of command or response)

(2) AD(H), AD(L): Slave station number, ASCII character 00 to 77(8) • Inside "command," set ID number of a JW10 slave station attempting to control with 00 to 77(8). • Inside "response," set ID number 01 to 77(8) of a JW10 slave station which is attempted to transmit data to the host computer. • When slave station number is assigned as "00" on writing command such as SRR (set and reset of relays) or WRG (writing to register), all the stations can be simultaneously controlled. This slave station number "00" is called "global address." • For global address usable commands, see "kinds of command" on page 13・7. • A "command" having global address is not given "response." • If global address is assigned to a command which is not available global address, the JW10 does nothing. (It does not return response, either.) (3) RI: Response time, ASCII character 0 to F(H) • Set interval from processing of "command" contents from a host computer to transmitting "response." • Set this time in accordance with processing performance of the host computer. Response Response Response Response RI(H) RI(H) RI(H) RI(H) time (ms) time (ms) time (ms) time (ms) 0 0 4 40 8 80 C 300

1 2 3

13

10 20 30

5 6 7

50 60 70

9 A B

90 100 200

D E F

400 500 600

• Response time in actual use is total of the above setting time and waiting time of PC scan cycle. Ex.: Monitoring relay 02000 of PC01 (in case where scan cycle is 10 ms and response time is 40 ms) Command : : 0 1 ? 4 M R L 0 2 0 0 0 4 F C R Scan cycle 10 ms

Waiting time Receiving command

Set response time 40 ms

Reading

Transmitting response

Note 1: For actual design, you may face the problem of how long a response time should be set. It is not as simply as using an optimum setting time which varies with type of the host computer, kind of programming language, and programming method. Therefore, we recommend to first set a rather long response time. Then, shorten it gradually by testing. Note 2: Number of processing bytes is restricted with some commands. Communication buffer is also restricted with the type of host computer used. Be careful for number of processing bytes.

13-4

Page 221

(4) Sum check codes SC(H), SC(L) • The communication port detects error using sum check as well as parity check in order to increase the reliability. • The contents of the sum check are as follows: 1Add data from slave station No. (AD(H)) to the last data of the command contents or response contents (just before sum check code) that are summed up in ASCII code. 2Convert the sum check code (2 digits hex.) to 8 bits data and add 1 to the result. When the grand total is "00(H)" (disregarded figure up), the message is regarded as correct, when the grand total is not "00(H)," the message is regarded as an error.

Ex.: In case of setting relay 07030 of PC02 (0 as reset, 1 as set). Command which should be sent to a host computer (in case of response time 50 ms) ASCII code 0 2 ? 5 S R R 0 7 0 3 0 1 0 … 30(H) Command contents 2 … 32 Response time (50 ms) ? … 3F 5 … 35 Address (slave station number) S … 53 Add from top address (slave station number) to end of command contents R … 52 at their ASCII code format, and take complement of this total. This is sum R … 52 0 … 30 check code. 7 … 37 Complement of 2 0 … 30 3 … 33 Complement of 2 can be obtained by reversing all of data ex0 … 30 pressed by binary (0 to 1, 1 to 0) and incrementing by one. +) 1 … 31 F8(H)→11111000 2F8(H) ↓ ↓Reversing bit F8(H) 00000111 Complement ↓ of 2 08(H) ↓Add by one 00001000 → 08(H) Therefore, "command" will be as follows: : :

0

2

? 5

S

R

R

0 7 0 3 0 1

0 8

C R

Sum check code When this "command" is received, PC02 sends the following "response." : :

0 2

# 5 S R R 0

7 0 3 0

5 5

C R

Sum check code

After receiving this response, the host computer adds from the top of slave station number to the last of the response contents in their ASCII code format, and adds sum check code "55." If lower 2 digits of the total become "00(H)" (300(H)), the JW10 judges that this response is correct.

ASCII code … 30(H) … 32 … 23 … 35 … 53 … 52 … 52 … 30 … 37 … 30 … 33 … 30 2AB(H) +)Sum check code 55(H) 300(H) 0 2 # 5 S R R 0 7 0 3 +) 0

• If sum check is not needed, set two @ (at sing : 40(H)) on SC(H) and SC(L) positions on the command line. The JW10 does not execute sum check. Even if this is set, the JW10 adds sum check code on response. You may make program to ignore these codes at the host computer.

13-5

13

Page 222

(5) EC(H), EC(L): Error code • When an error occurs, the JW10 sends the following codes as error response. Error code (EC(H), EC(L))

Contents

01

Format error.

02

Designated address is not TMR/CNT setting value.

05

Number of transfer bytes is not correct.

06

JW10 does not stop by HLT (stop PC processing).

07

Writing to JW10 memory is not executed correctly.

0A

Parity error.

0B

Framing error.

0C

Overrun error.

0D

Sum check error.

0E

Prohibit program memory write.

10

Not match write mode.

11

Not program area.

12

Tried to write in ROM.

1B

System memory error.

30

Password is not registered.

31

Secret function is not released.

32

Wrong password is input.

33

Password error (attempted to register characters other than alphabetical and numeric figures).

13

Note 1: In any of the following cases, the JW10 will do nothing and transmit no response. 1) Assigned slave station number in the command and own station number do not match. C 2) If the JW10 cannot find " : " " ? " or " R " in the command. In order to recover from any of these errors, create a program to check by time out with the host computer.

(6) Contents of command and response • See next item "[5] Description of command."

13-6

Page 223

[5] Description of command (1) Kinds of command • Commands are largely classified into read-out command, write command, and control command. Command name

Global address

See page

Relay monitor

MRL

×

13•9

Current value monitor of timer/counter

MTC

×

13•10

Register current value monitor

MRG

×

13•11

Read out program memory

RPM

×

13•13

Read out system memory

RSM

×

13•15

Read out date

MDY

×

13•16

Read out time

MTM

×

13•17

Set/reset relay

SRR

○

13•9

Set/reset timer/counter

SRT

○

13•11

Write in register

WRG

○

13•12

Write the same data in register

FRG

○

13•12

Write in program memory

WPM

○

13•13

Write in system memory

WSM

○

13•15

Change setting value of timer/counter

CTC

○

13•14

Set date

SDY

○

13•16

Set time

STM

○

13•17

Correct, run, and stop clock

ACL

○

13•18

Monitor operation conditions

MPC

×

13•18

Stop PC operation

HLT

○

13•19

Restart PC operation

RUN

○

13•19

Read out write mode status

SWE

×

13•20

Set write mode

EWR

○

13•20

Turn back the message

TST

×

13•21

Release secret/password registration

PAS

○

13•21

Set secret function

SES

○

13•22

Check secret function

SEI

×

13•22

Control command

Write command

Read-out command

Function

Note: For details of "global address" see page 13-4 (2) Write mode • Write mode of JW10 is "mode 0" (write prohibited for all memories) at power ON. Prior to writing program from the host computer, change write mode to "mode 1" or "mode 2" using EWR command (setting of write mode). SWE command read out current status of writing mode. • Set write mode to "mode 0" as much as possible, except when writing data into JW10. • Each mode has restrictions as follow: Mode 0

Write prohibited for all memories

Mode 1

Write enable only for data memory

Mode 2

Write enable for all memories

13-7

13

Page 224

(3) Address expression system • In each command, the setting value in the following table is set in the address module of communication format. Address Setting value Using command (octal)

(octal)

Relay number

00000 to 15777

00000 to 15777

MRL, SRR

Timer/counter point of con-

T000 to T377

T0000 to T0377

MRL tact number

C000 to C377 000 to 377

0000 to 0377

MTC, SRT

コ0000 to コ1577

A0000 to A1577

MRG, WRG, FRG b0000 to b0777

B0000 to B0777

09000 to 09777

09000 to 09777

19000 to 19777

19000 to 19777

29000 to 29777

29000 to 29777

39000 to 39777

39000 to 39777

0000 to 2777

000000 to 002777

0000 to 7777

000000 to 007777

#000 to #377

0000 to 0377

Timer/counter number Register address

Program

JW-1324K/1342K address

JW-1424K/1442K JW-1624K/1642K

System memory address

RPM, WPM, CTC

RSM, WSM

Note: Set with octal notation regardless of setting value on system memory #115. (4) Data expression system • Data are expressed by hexadecimal. Program contents are also expressed by hexadecimal based on machine language. • Contents of bit configuration of program memory is not available.

13

13-8

Page 225

[6] Description of each command MRL

Monitor ON/OFF state of the designated relay.

Command

A S S ・ ・ A D D ? R M R L Relay number C C C I ・ ・ (H) (L) (H) (L) R

Response

A ・ ・ A D D ♯ R M R L Relay number I ・ ・ (H) (L)

Data

Communication format

Function

Relay monitor

S S C C C (H) (L) R

00000 to 15777 Relay T0000 to T0377 (Octal) number 1:ON 0:OFF Data Write mode Mode 0, Mode 1, Mode 2 Execution condition PC operation state Stop, Run

Monitor auxiliary relay 04033 of PC01. (Response time: 40 ms) Example for use

Command

01?4MRL0403347 C R Station Response number time

Response

Relay number

01♯4MRL04033132 C R Station Response number time

SRR

Relay number

ON Sum check code

Set/reset relay Set/reset the relay.

Command

A ・ ・ A D D ? R S R R Relay number I ・ ・ (H) (L)

Response

A S S ・ ・ A D D ♯ R S R R Relay number C C C I ・ ・ (H) (L) (H) (L) R

Data

Communication format

Function

Sum check code

S S C C C (H) (L) R

13

Relay number 00000 to 15777 (Octal) 1: Set 0: Reset Data Mode 1, Mode 2 Write mode Execution condition PC operation state Stop, Run Reset auxiliary relay 07001 of PC03. (Response time: 40 ms) Command Example for use

03?4SRR0700100B C R Station Response number time

Response

Relay number

Sum check code Reset

03♯4SRR0700157C R

Station Response number time

Relay number

Sum check code

Note 1: Relays which are used for input relay, special relay, special register and link system (data link, remote I/O) cannot be set/reset.

13-9