Sharp Programmable Controller New Satellite JW10 User's Manual: Chapter 13 How to Use Communication Port, pages 235 to 243

Pages 235 to 243 of 307, from Sharp Programmable Controller New Satellite JW10 User's Manual

The original document is the PDF (5.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Sharp jW-10CM

Page 235

Stop PC operation

Function

Stop PC operation.

Communication format

HLT

Command

S S A ・ ・ A D D ? R H L T C C C I ・ ・ (H) (L) (H) (L) R

Response

S S A ・ ・ A D D ♯ R H L T C C C I ・ ・ (H) (L) (H) (L) R

Write mode Mode 0, Mode 1, Mode 2 Execution condition PC operation state Stop, Run

Stop operation of PC03. (Response time: 10 ms) Example for use

Command

03?1HLT45C R Station Response number time

Response

Sum check code

03♯1HLT61C R Station Response number time

Sum check code

Note 1: A PC which has been stopped by HLT command cannot start operation again by support tool such as JW-13PG.

Restart PC operation

Function

Release HLT (stop PC operation) command, restart PC operation.

Communication format

RUN

Command

S S A ・ ・ A D D ? R R U N C C C I ・ ・ (H) (L) (H) (L) R

Response

S S A ・ ・ A D D ♯ R R U N C C C I ・ ・ (H) (L) (H) (L) R

13

Write mode Mode 0, Mode 1, Mode 2 Execution condition PC operation state Stop, Run

Restart operation of PC03. (Response time: 10 ms) Example for use

Command

03?1RUN38C R Station Response number time

Response

Sum check code

03♯1RUN54C R Station Response number time

Sum check code

Note 1: RUN command restarts a PC which has been stopped by HLT command. When the PC has stopped by other causes such as set to program mode by JW-13PG, it cannot restart operation even RUN command is executed. In these cases, response returns normally.

13-19

Page 236

SWE

Read out current write mode status.

Command

A S S ・ ・ A D D ? R S W E C C C I ・ ・ (H) (L) (H) (L) R

Response

A ・ ・ A D D ♯ R S W E I ・ ・ (H) (L)

Data

Data

Communication format

Function

Read out write mode status

S S C C C (H) (L) R

0: Mode 0 .... Write prohibited for all memories 1: Mode 1 .... Write enable only for data memory 2: Mode 2 .... Write enable for all memories

Write mode Mode 0, Mode 1, Mode 2 Execution condition PC operation state Stop, Run Read out write mode status of PC06. (Response time: 10 ms)

Example for use

06?1SWE3B C R

Command

Station Response number time

Response

Sum check code

06♯1SWE03B C R Station Response time number

Sum check code Mode 0

Note 1: Be mode 0 (write prohibited), at power ON.

EWR

Set PC write mode.

Command

A ・ ・ A D D ? R E W R I ・ ・ (H) (L)

Response

A S S ・ ・ A D D ♯ R E W R C C C I ・ ・ (H) (L) (H) (L) R

Data

Data

13

Communication format

Function

Set write mode

S S C C C (H) (L) R

0: Mode 0 .... Write prohibited for all memories 1: Mode 1 .... Write enable only for data memory 2: Mode 2 .... Write enable for all memories

Write mode Mode 1, Mode 2 Execution condition PC operation state Stop, Run Set write mode of PC22 to mode 2 (write allowed for all memories). (Response time: 40 ms)

Example for use

Command

22?4EWR209C R

Station Response time number

Response

Sum check code Mode 2

22♯4EWR57 C R

Station Response time number

Sum check code

Note 1: In order to prevent inadvertent accident, set the mode to "mode 0" (write prohibited) while not writing data.

13-20

Page 237

TST

Communication format

Function

Turn back the message Send back the received command as it is.

Command

A ・ ・ A D D ? R T S T M1 I ・ ・ (H) (L)

…………

S S Mn C C C (H) (L) R

Response

A ・ ・ A D D ♯ R T S T M1 I ・ ・ (H) (L)

…………

S S Mn C C C (H) (L) R

Message visible character strings (20H to 7EH of ASCII code) Max. 1024 characters Data Write mode Mode 0, Mode 1, Mode 2 Execution condition PC operation state Stop, Run

Test sending and returning of a message toward PC01. (Response time: 50 ms) Example for use

Command

01?5TSTTESTCOMMANDF1C R

Station Response time number

Response

Message

01♯5TSTTESTCOMMAND0DC R Station Response time number

Command

A ・ ・ A D D ? R P A S I ・ ・ (H) (L)

Response

A ・ ・ A D D ♯ R P A S I ・ ・ (H) (L)

Data

Sum check code

Release secret function, register password. Data

Communication format

Function

Message

Release secret/password registration

Data

PAS

Sum check code

Password

S S C C C (H) (L) R

13

S S C C C (H) (L) R

0: Release‥‥Release the secret function. 1: Temporary registration‥‥Set before regular registration 2: Regular registration‥‥Set after temporary registration

Pass word Alphanumeric 4 characters Execution condition

Data = 0 Mode 0, Mode 1, Mode 2 Write mode PC operation state Stop, Run

Data = 1, 2 Mode 2 Stop by HLT command

Regularly register password 15AE to PC05. (Response time: 20 ms) Example for use

Command

05?2PAS215AE28 C R Station Response time number

Response

Password Sum check code Regular registration

05♯2PAS62C R

Station Response time number

Sum check code

Note 1: If secret function is set, the following commands cannot be used: RPM, WPM, WSM, CTC, HLT, RUN, SES. In addition, setting of secret function on the JW10 requires a support tool such as JW-13PG to set its password which is connected to the JW10. 13-21

Page 238

Communication format

Function

Set secret function Set secret function.

A ・ A Command ・ D D ? R S E S I ・ ・ (H) (L)

Data

SES

S S C C C (H) (L) R

A S S ・ A D D ♯ R S E S C C C Response ・ I ・ ・ (H) (L) (H) (L) R

Data Execution condition

1: Enable secret function ‥‥Enable secret function by the registered password. F: Delete ‥‥Delete registered password of JW10. Data = 1 Write mode Mode 0, Mode 1, Mode 2 PC operation state Stop, Run

Data = F Mode 2 Stop by HLT command

Enable secret function of PC07. (Response time: 10 ms) Command Example for use

07?1SES10D C R Station Response number time

Response

Sum check code Enable secret function

07♯1SES5A C R Station Response number time

Sum check code

Note 1: If secret function is set, the following commands cannot be used: RPM, WPM, WSM, CTC, HLT, RUN, SES. In addition, setting of secret function on the JW10 requires a support tool such as JW-13PG to set its password which is connected to the JW10.

SEI

Check secret function (enable/disable).

A S S ・ A D D ? R S E I C C C Command ・ I ・ ・ (H) (L) (H) (L) R A ・ A D D ♯ R S E I Response ・ I ・ ・ (H) (L)

Data

Data

13

Communication format

Function

Check secret function

S S C C C (H) (L) R

0: Disable secret function 1: Enable secret function

Write mode Mode 0, Mode 1, Mode 2 Execution condition PC operation state Stop, Run Check secret function (enable/disable) of PC03. (Response time: 30ms)

Example for use

Command

03?3SEI4AC R

Station number

Response

Response time

Sum check code

03♯3SEI135C R

Station Response time number

13-22

Sum check code Enable secret function

Page 239

13-3 Data link [1] Communication specifications • Data link can communicate between one JW10 master station and maximum of seven JW10 slave stations. Master station

Slave station 1 Slave station 2

#234 = 01(H) #235 = 007(D) #237 = 000(8)

#234 = 01(H) #237 = 001(8)

Slave station 7

#234 = 01(H) #237 = 002(8)

#234 = 01(H) #237 = 007(8)

• Data link area of master station and slave station are allocated as shown below. Master station link area

▲

▲

コ1400 to コ1407 コ1410 to コ1417 Slave station 2 link area

▲

▲

コ1400 to コ1407 コ1410 to コ1417

Slave station 7 area

▲

▲

Slave Transmitting コ1400 to コ1407 station 1 Receiving コ1410 to コ1417 Slave Transmitting コ1420 to コ1427 station 2 Receiving コ1430 to コ1437 Slave Transmitting コ1440 to コ1447 station 3 Receiving コ1450 to コ1457 Slave Transmitting コ1460 to コ1467 station 4 Receiving コ1470 to コ1477 Slave Transmitting コ1500 to コ1507 station 5 Receiving コ1510 to コ1517 Slave Transmitting コ1520 to コ1527 station 6 Receiving コ1530 to コ1537 Slave Transmitting コ1540 to コ1547 station 7 Receiving コ1550 to コ1557

Slave station 1 link area

コ1400 to コ1407 コ1410 to コ1417

Note: Data are transferred between master station and slave station. They cannot be transferred between slave stations.

Item Data transfer standard Transfer rate No. of slave stations connected Link area No. of link bytes per station Communication line

Specifications EIA RS-422A or equivalent 76800, 38400 bits/s Max. 7 sets Master station: コ1400 to コ1557, slave station: コ1400 to コ1417 Master station to slave station: 8 bytes Slave station to master station: 8 bytes Shielded twisted pair cable. Party line connection. 2-wire system. Total length: 500 m (76800 bits/s), 1 km (38400 bits/s)

13-23

13

Page 240

[2] Wiring JW10 (001)

JW10 (002)

L1 L2

L1 L2

L1 L2

SHLD

SHLD

SHLD

Class-3 grounding

Class-3 grounding

〜 〜 〜 〜〜 〜〜 〜

JW10 (000)

JW10 (006)

JW10 (007)

L1 L2

L1 L2

SHLD

Class-3 grounding Shielded twisted pair cable

SHLD Class-3 grounding Class-3 grounding

Total cable length: Less than 1 km RS-422A

Note 1 : Do class-3 grounding for SHLD terminal. The operation without class-3 grounding may cause malfunction due to noise. Note 2 : Never branch a communication cable into more than 3 lines.

Good

Bad

Conjunction terminal

Connection using a connector

[3] Setting system memory • When data link function is used, set the following system memory in master and slave stations. (1) System memory of master station #234 Communication mode 01(H): Data link mode #235 No. of slave stations 001 to 007(D) #236 Transfer rate

*Note 1

00(H): 76800 bits/s, 01(H): 38400 bits/s

*Note 2

#237 Own station number 000(8) (2) System memory of slave station

13

#234 Communication mode

01(H): Data link mode

#236 Transfer rate

00(H): 76800 bits/s, 01(H): 38400 bits/s

#237 Own station number 001 to 007(8)

*Note 1 *Note 2

*Note 3

*Note 1 : To quit data link communication, set #234 as 00(H). (Computer link mode) *Note 2 : Set identical communication speed for the master station and slave stations. *Note 3 : Allocate slave station ID numbers for each with sequential numbers from 001. *Note 4 : Communication mode and station number are set on system memory. We recommend to mark these settings on a label and stick it on each case for [Example of label] Data link easily readable the set contents. #001

[4] Communication flag • Communication condition of a master station and each slave station can be confirmed by communication flag. (1) Communication flag of master station (2) Communication flag of slave station Communication flag

Contents

Communication flag

Contents

07340

While normally communicating with all slave stations: ON

07340

While normally communicating with the master station: ON

07341

While normally communicating with slave station 1: ON

07341

Not in use: OFF

07342

While normally communicating with slave station 2: ON

07342

Not in use: OFF

07343

While normally communicating with slave station 3: ON

07343

Not in use: OFF

07344

While normally communicating with slave station 4: ON

07344

Not in use: OFF

07345

While normally communicating with slave station 5: ON

07345

Not in use: OFF

07346

While normally communicating with slave station 6: ON

07346

Not in use: OFF

07347

While normally communicating with slave station 7: ON

07347

Not in use: OFF

13-24

Page 241

[Example of communication flag state] Master station

Slave station 1

Slave station 2

Slave station 3

#234 = 01(H) #235 = 003(D) #236 = 00(H) #237 = 000(8)

#234 = 01(H)

#234 = 01(H)

#234 = 01(H)

#236 = 00(H) #237 = 001(8)

#236 = 00(H) #237 = 002(8)

#236 = 00(H) #237 = 003(8)

1) In case of normal communication (Master station communicates to all save stations normally.) Master station 07340 07341 07342 07343 07344 07345 07346 07347

ON ON ON ON OFF * OFF * OFF * OFF *

Slave station 1 07340 07341 07342 07343 07344 07345 07346 07347

ON OFF * OFF * OFF * OFF * OFF * OFF * OFF *

Slave station 2 07340 07341 07342 07343 07344 07345 07346 07347

ON OFF * OFF * OFF * OFF * OFF * OFF * OFF *

Slave station 3 07340 07341 07342 07343 07344 07345 07346 07347

ON OFF * OFF * OFF * OFF * OFF * OFF * OFF *

* Not in use

2) When master station is error (Power OFF, disconnect, stop mode, module error) Master station OFF OFF OFF OFF OFF * OFF * OFF * 07347 OFF * 07340 07341 07342 07343 07344 07345 07346

Slave station 1 07340 07341 07342 07343 07344 07345 07346 07347

OFF OFF * OFF * OFF * OFF * OFF * OFF * OFF *

Slave station 2 07340 07341 07342 07343 07344 07345 07346 07347

OFF OFF * OFF * OFF * OFF * OFF * OFF * OFF *

Slave station 3 07340 07341 07342 07343 07344 07345 07346 07347

OFF OFF * OFF * OFF * OFF * OFF * OFF * OFF *

13

* Not in use

3) When slave station 1 is error (Power OFF, disconnect, stop mode, module error) Master station Slave station 1 Slave station 2 Slave station 3 OFF OFF ON ON OFF * OFF * OFF * 07347 OFF * 07340 07341 07342 07343 07344 07345 07346

07340 07341 07342 07343 07344 07345 07346 07347

OFF OFF * OFF * OFF * OFF * OFF * OFF * OFF *

07340 07341 07342 07343 07344 07345 07346 07347

ON OFF * OFF * OFF * OFF * OFF * OFF * OFF *

07340 07341 07342 07343 07344 07345 07346 07347

ON OFF * OFF * OFF * OFF * OFF * OFF * OFF *

* Not in use

Note : When slave station 1 has an error (such as power OFF, disconnection, stop mode, or module error), the master station continues communication with other normal slave stations. When slave station 1 recovers from error condition, the master station restart communication with slave station 1. 13-25

Page 242

[5] Communication timing and transmission time required (1) Communication timing of master station • The master station communicates with each slave station asynchronous with master station's scan cycle. • The master station exchanges data for data link and refreshes communication flag with scan cycle after completion of communication with slave stations. Scan time of the master station increases with the interval required for these procedures (approximately 0.2 ms).

▼

Data exchange Refresh communication flag

・・・・・・

I/O

▼

▼

▼

▼

▼

▼

I/O

▼

▼

I/O

▼

Master station PC scan cycle

Data exchange Refresh communication flag

No data exchange

▼

▼

▼

▼

One scan time

▼

Slave Slave Slave Slave Slave station 1 station 2 station 3 station 4 ・・・・ station 7

▼

Slave Slave ・・ station 1 station 2

One communication cycle

• When an error occurs during communication between the master station and slave stations, the master station does not exchange data for data link with the error occurred slave station, and turns OFF this slave station's communication flag. However, the master station exchanges data with other normal slave stations. Possible causes of errors are as follows: ① Occurrence of sum check error. ② Slave station is in stop mode or abnormal condition. ③ Slave station is not connected or there is disconnection of a cable. • When the master station is in stop mode or is in abnormal condition, it does not communicate with any slave station.

▼

▼

One scan time

Data exchange Refresh communication flag

I/O

I/O

・・・・・・

▼

Slave station PC scan cycle

Data exchange Refresh communication flag

No data exchange

I/O

▼

13

(2) Communication timing of slave station • A slave station communicates with the master station asynchronous with slave station's scan cycle. • A slave station exchanges data for data link and refreshes communication flag with scan cycle after completion of communication with the master stations. Scan time of a slave station increases with the interval required for these procedures (approximately 0.2 ms).

▼

▼

Master station

Master station

• When an error occurs during communication between the master station, the slave station does not exchange data for data link, and turns OFF its own communication flag. Possible causes of errors are as follows: ① Occurrence of sum check error. ② Slave station is in stop mode or abnormal condition. ③ Master station is in stop mode or abnormal condition. ④ Slave station is not connected or there is disconnection of a cable. 13-26

Page 243

(3) Transmission time required • Interval that a data linked master station needs to communicate with all of slave stations "T" (one communication cycle time) is as follows:

3.6 ms 7.2 ms 10.8 ms 14.4 ms 18.0 ms 21.6 ms 25.2 ms

1 2 3 4 5 6 7

38400 bits/s (#236 = 01(H))

76800 bits/s (#236 = 00(H))

Number of slave stations

7.6 ms 15.2 ms 22.8 ms 30.4 ms 38.0 ms 45.6 ms 53.2 ms

3.6 × number of slave stations [ms]

7.6 × number of slave stations [ms]

(4) Communication delay time • To receive data with data link, the following delays will occur. a) Communication from master station to slave station

14000

14000

00000

(Master station) Turns ON Input 00000

Master station

One scan time

I/O

T1

Data exchange I/O

I/O

I/O

T3

T2

00400 (Slave station 1)

I/O

I/O

I/O

T4

One scan time

Slave station 1

I/O

I/O

Data exchange I/O

T5

I/O

I/O

I/O

T6

T7

13 Turns ON Output 00400

T1: Delay on input port T2: Time until a PC detects input condition (maximum one scan time) T3: Operation time (one scan time) of data transmitting side PC (master station) T4: Time to complete transmitting operated result (maximum [one communication cycle time + one scan time]). T5: Time that data receiving side PC (slave station 1) completes writing received data onto PC's data memory (maximum one scan time) T6: Operation time of data receiving side PC (slave station 1) (one scan time) T7: Delay of output port Total delay time = T1 + T2 + T3 + T4 + T5 + T6 + T7

13-27