Page 299
Appendix-3 Binary/octal/decimal/hexadecimal/BCD code correspondence table Decimal
APP
Binary
Octal
Hexadecimal
Binary Coded Decimal (4 digits)
0
00000000 00000000
0
0000
0000 0000 0000 0000
1
00000000 00000001
1
0001
0000 0000 0000 0001
2
00000000 00000010
2
0002
0000 0000 0000 0010
3
00000000 00000011
3
0003
0000 0000 0000 0011
4
00000000 00000100
4
0004
0000 0000 0000 0100
5
00000000 00000101
5
0005
0000 0000 0000 0101
6
00000000 00000110
6
0006
0000 0000 0000 0110
7
00000000 00000111
7
0007
0000 0000 0000 0111
8
00000000 00001000
10
0008
0000 0000 0000 1000
9
00000000 00001001
11
0009
0000 0000 0000 1001
10
00000000 00001010
12
000A
0000 0000 0001 0000
11
00000000 00001011
13
000B
0000 0000 0001 0001
12
00000000 00001100
14
000C
0000 0000 0001 0010
13
00000000 00001101
15
000D
0000 0000 0001 0011
14
00000000 00001110
16
000E
0000 0000 0001 0100
15
00000000 00001111
17
000F
0000 0000 0001 0101
16
00000000 00010000
20
0010
0000 0000 0001 0110
17
00000000 00010001
21
0011
0000 0000 0001 0111
18
00000000 00010010
22
0012
0000 0000 0001 1000
19
00000000 00010011
23
0013
0000 0000 0001 1001
20
00000000 00010100
24
0014
0000 0000 0010 0000
21
00000000 00010101
25
0015
0000 0000 0010 0001
22
00000000 00010110
26
0016
0000 0000 0010 0010
23
00000000 00010111
27
0017
0000 0000 0010 0011
24
00000000 00011000
30
0018
0000 0000 0010 0100
25
00000000 00011001
31
0019
0000 0000 0010 0101
26
00000000 00011010
32
001A
0000 0000 0010 0110
27
00000000 00011011
33
001B
0000 0000 0010 0111
28
00000000 00011100
34
001C
0000 0000 0010 1000
29
00000000 00011101
35
001D
0000 0000 0010 1001
30
00000000 00011110
36
001E
0000 0000 0011 0000
31
00000000 00011111
37
001F
0000 0000 0011 0001
63
00000000 00111111
77
003F
0000 0000 0110 0011
255
00000000 11111111
377
00FF
0000 0010 0101 0101
9999
00100111 00001111
23417
270F
1001 1001 1001 1001
65535
11111111 11111111
177777
FFFF
Appendix・10
Page 300
Appendix-4 JW-13PG key operation Below shows operation procedure to
Mode use JW-13PG for the JW10. Function
P: Program mode M: Monitor mode C: Change mode
T: Terminal mode I: Initial mode Mode
Operation procedure
P M C T I Buzzer ON/ OFF select
(ON)
EL backlight ON/OFF select
(ON)
Contrast adjustment
(Darker)
○○○×○
(OFF)
○○○×○
(OFF)
○○○×○
(Brighter)
Auto repeat function
Monitoring of program address or data memory address
1 second or longer ON 1 second or longer ON
Display mode selection
1PG mode
2PG mode
Repetition of address +1. Repetition of address -1.
○○○××
○○○×× (Program mode) (Monitor mode)
Operation mode setting
(Change mode)
Program mode
○○○×○
(Initial mode)
3rd
EL backlight ON/OFF
○○○×○
Buzzer ON/OFF
○○○×○
Monitor clock (JW-1424K/1624K)
○○○××
Error monitor
×○○××
Display mode selection
○○○××
Initial mode
○××××
Monitor mode
○○○×○
Change mode
○○○×○
Program mode
○○○×○
1st
2nd
4th
Operation screen selection
Key operation
5th
6th
7th
Program check
Appendix・11
○××××
APP
Page 301
Function
Mode
Operation procedure
P M C T I
System memory clear
Program memory clear
Memory clear
○××××
Data memory clear
Program memory and data memory clear
All initialize
(Read in address incrementing direction)
System memory read
System memory write
Set the system memory address
System memory write
○○○××
(Read in address decrementing direction)
(1 byte unit)
Set data HEX, OCT, DCML, bit pattern
○××××
(1 word unit)
System memory check code write
○××××
Program address set
APP
Basic and application instruction entry
Entry method for basic instructions
○○○××
Address set
Instruction key
Relay number
Setting value
TMR/CNT number
TMR/CNT instruction entry
Setting value changes constants or register area by pressing
0000 コ0000 (Constant)
b000
09000
○××××
• F-xx instruction Function number
• Fcxx instruction
Application instruction entry key.
F-××(Fc××)
F-××w(Fc××w)
Function number
Register/constant
(Repetition of number of instruction word setting)
Appendix・12
Page 302
Function
Mode
Operation procedure
P M C T I
Basic and application instruction entry
• Press the
Register area selection
コ0000
Indirect address designation
Register number
Setting the register address key to change the register area.
b000
09000
@Register number ○××××
Display コ0000
Address
Display b000
Address Register number set (0 to 3)
Display 09000
Address
• Write from address 00000 Instruction word
• Write from a specified address Program write
Instruction word
Program address set
○××××
• Write from an address where no program is written
Search for NOP instruction
Instruction word
• Read by specifying an address Program address setting
(Read in address incrementing direction) (Read in address decrementing direction)
• Read by searching for an instruction
Program read
Instruction search
(Read in address incrementing direction) (Read in address decrementing direction)
• Read by searching data memory Data memory search
(Read in address incrementing direction) (Read in address decrementing direction)
Appendix・13
○○○××
APP
Page 303
Function
Mode
Operation procedure
P M C T I Specify search start address
Specify instruction to be searched for.
Address incrementing direction
Instruction search
○○○××
Address decrementing direction
Continuous search
○○○××
(Increment address)
Specify search address
Non-NOP instruction search
Program search
(Increment address) (Decrement address)
Specify search address
NOP instruction search
(Decrement address)
○○○××
Continuous
Data memory address set
(Address incrementing direction)
Data memory address
Data memory search
(
)
Address decrementing direction
○○○×× • Press the key to change the data memory area.
Relay number (00000 to 15777)
TMR/CNT number (000 to 377)
Byte address (コ0000 to コ1577)
Label number (LB0000 to LB0177)
Byte address (b000 to b777)
Register (09000 to 39777)
Searching with the changed contents (Address incrementing direction) Instruction search
Re-execution of search
Program correction
Data memory search
(
)
Address decrementing direction
Searching with the contents before the change (Address incrementing direction)
(
○○○××
)
Address decrementing direction
APP
Program correction
(Continuous search)
Instruction change
Specify address to be corrected
Specify instruction to be corrected
○××××
Instruction insert
Specify address to be inserted
Specify instruction to be inserted
○××××
Instruction delete
Read the instruction to be deleted
○××××
Appendix・14
Page 304
Function
Mode
Operation procedure
Program correction
P M C T I TMR/CNT setting value change
Read setting value in program
Application instruction constant change
Program address search
○×○××
Setting value change
Setting value change
○×○××
Continuous check
Program check
○××××
(Address incrementing direction) (Address decrementing direction)
Setting program address
Program monitor
Instruction search
×○○××
Data memory search
Continuous monitor Setting data memory address (Address incrementing direction) (Address decrementing direction)
Data memory monitor
Press the key to change the data memory area.
Relay number TMR/CNT number (00000 to15777) (000 to 377)
Byte address (コ0000 to コ1577)
Byte address (b000 to b777)
○○○××
Register (09000 to 39777) Display コ0000
Address
Display b000
Address
Display 09000
Register number set
Address
Data memory change
(0 to 3)
Relay set or reset
Relay monitor
(Set)
○×○×× (Reset)
TMR/CNT set or reset
TMR or CNT monitor
(Set)
××○×× (Reset)
Current register value change
Register monitor
Current value
Appendix・15
○×○××
APP
Page 305
Function
Mode
Operation procedure
P M C T I Change to initial mode
Change to program mode
(Select clock)
Set the "year"
Set the "month"
Set the "day"
(Lower 2 digits of A.C.)
××××○ Setting the time (JW-1424K/ 1624K)
Set the "day-ofthe-week"
Set the "hours"
Set the "seconds"
Set the "minutes"
Day of the week SUN MON TUE WED THU FRI SAT Setting 0 1 2 3 4 5 6 value
(Monitor) Time monitor
○○○×× Clear the monitor with the key. (Write)
Writing a program to an EEPROM
○××××
(Stop)
Reading a program from ROM
(Read)
○×××× (Stop)
(Step incrementing direction monitor) (Step decrementing direction monitor)
Error monitor
×○○××
Password register (4 digits)
Password register
(Register)
(0 to F)
Password delete
(Delete)
Secret ON
(ON)
○××××
(Stop)
○××××
(Stop)
○××××
(Stop)
APP Secret OFF
JW-13PG is connected with JW10's MMI port
Password (4 digits) (Secret OFF)
(0 to F) All initialize
Clear the system memory, program memory, and data memory
(
Appendix・16
)
○○○××
Page 306
Appendix-5
Connection with an LCD control terminal
Below shows wiring method and setting value of the system memory when a SHARP's LCD control terminal (ZM-30E/L, ZM-40D/L, ZM-61E/T, ZM-70D/T) is connected to the JW10.
[1] In case of connecting communication port (1) Wiring ZM-30E/L
ZM-40D/L
CN2
ZM-61E/T, ZM-70D/T
CN2
CN1
TB2
Shielded twisted pair cable
Signal Signal Terminal Signal name Pin no. name Pin no. name Pin no. name
+RXD +TXD -RXD -TXD FG
10 12 11 13 1
+RD +SD -RD -SD FG
24 12 25 13 1
24
+RD +SD -RD -SD
12 25 13 1
FG
JW10 communication port Terminal name
+RD +SD -RD -SD
L1 L2 SHLD
FG
Note 1: Connection to a ZM-30E/L, ZM-40D/L, or ZM-61E/T can be done on models with version 1.13 or later ROM code. Note 2: The termination resistance switches on the ZM-40D/L, ZM-61E/T, or ZM-70D/T must be set to "No termination resistance." If they are set to " termination resistance present," the JW10 may not communicate correctly. (2) Setting of JW10 system memory Setting System Contents value memory no. #234 00(H) Computer link mode #236 30(H) 19200 bits/s, even parity, stop bit 2 bits, data length 7 bits #237
001(8)
Station No. 001
(3) Setting of screen image creation software (ZM-31SE) Setting contents
Item SHARP (JW series)
Setting PLC model
Communication parameter Baud rate [19200] bps., signal level [RS422]
[2] In case of connecting with MMI port (1) Wiring ZM-30E/L
ZM-40D/L
CN2
CN2
ZM-61E/T , ZM-70D/T CN1
TB2
Signal Signal Signal Pin no. Terminal name name Pin no. name Pin no. name
+TXD -TXD +RXD -RXD FG
12 13 10 11 1
+SD -SD +RD -RD FG
12 13 24 25 1
+SD -SD +RD -RD FG
12 13 24 25 1
+SD -SD +RD -RD FG
Shielded twisted pair cable
JW10 MMI port Pin no.
Signal name
2 7 3
RX /RX TX /TX PG/COM GND
8 4 5
Note 1: The termination resistance switches on the ZM-40D/L, ZM-61E/T, or ZM-70D/T must be set to "No termination resistance." If they are set to " termination resistance present," the JW10 may not communicate correctly. Appendix・17
APP
Page 307
(2) Setting of JW10 system memory System memory no.
Setting value
#226
30(H)
19200 bits/s, even parity, stop bit 2 bits, data length 7 bits
#227
001(8)
Station number 001(8)
Contents
(3) Setting of screen image creation software (ZM-31SE) Setting contents
Item Setting PLC model
SHARP (JW series)
Communication parameter Baud rate [19200] bps., signal level [RS422]
APP
Appendix・18