The text of a manual · part 15 of 18

I/O link master module JW-31LMH Instruction Manual: §11 Slave module, pages 90 to 99

Pages 90 to 99 of 123, from I/O link master module JW-31LMH Instruction Manual

The original document is the PDF (3.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sharp JW-31LMH

Page 90 read from a scan by OCR; it may hold reading errors

@ ZW-162MH (transistor output, 24 VDC input module)

Item Specifications No. of slave station occupied bytes 2 bytes No. of output points 8 points Rated load voltage 24 VDC Allowable load voltage 20.4 to 26.4 VDC Rated max. output power 0.3 A/point, 1 A/common S | Surge ON current 0.5 A {10 ms) 8 Minimum load current _ - = | Leakage current (when OFF) 0.1 mA or less a. Voltage drop at turning ON 0.5 V or less (0.3 A) + | Response time (module alone) | OFF, ON: 1 ms or less = ON, OFF: 1 ms or less (resistance load) O | Surge killer Zener diode Rated fuse Built-in 1.25 A fuse (unable replacement) Meltdown detection function is provided (When melted down or load power is turned OFF, the FUSE lamp lights) Common terminal 1 common per 8 points No. of input point 8 points Rated input voltage 24 VDC c_ | Allowable input voltage 20.0 to 26.4 VDC (ripple factor: Less than 15%) 2 Rated input current 4.6 mA TYP. (at 24 VDC) = | Input voltage level ON level: 18.0 V or less, OFF level: 8.0 V or up 3 input current level! ON level: 3 mA orless, OFF level: 1.5 mA or up = input impedance 5.2 k ohm (TYP.) & | Surge current, Response time (Module alone)

OFF, ON: 1.0 ms or less (24 VDC)

ON, OFF: 1.5 ms or less (24 VDC)

Common terminal

1 common line for 8 points (no polarity)

- 83-

Page 91 read from a scan by OCR; it may hold reading errors

Outside connection drawings

Surface view

24V 5

24 VDC “OWT ypc | OY power rt supply Ov ite

(Isolated)

Out fdkeator lamp ie

=

5

£ o

© Jive = intlicato ® p a4

= nd

Photo-coupler

¢ "COM.A" is assigned at the output side, and at 1/0 link master module lower number of the communication area.

¢ We recommend to install applicable fuse to every output for safety.

al

RCO) ON IS] = wit)| Avz| ON

0

@ gRoo

1 |vwool ao | o4 lotus} 11 | O é

9 i]

A %

I [=] ?

‘

Apz00 INdNiNd NO, ~ 84

Page 92 read from a scan by OCR; it may hold reading errors

11-4 ZW-324NH/322SH/322MH

The switch settings, installation method, and errors, and their troubleshooting measures are the same for models ZW-161N to 164M. (See page 56 to 63.)

[1] Name and function of each part

@ Module © Mode setting switch retention h @) Station an number (ST No.) @ Switch cover

6 00000000 090000000 ere ele S relies mr ay a wA (©) Terminal block @)DIN rail lever

) Terminal block

“SEES ‘i | [pe 0 Oo e _| © © DIN rail lever, 85-

@ Indicator lamp

Display each operation condition. (See the below)

@ Terminal block cover (integral with case) Protective cover for termina! block Detachable by cutting off fixing portion.

@) Switch cover

Protective cover of station number (ST No.) setting switch @ and mode setting switch ©.

@) Station number (ST No.) setting switch Set the station number of slave module.

Setting at delivery ON 40.2010 4 2 1

| (daira

-OFF-

) Terminat block

Connect power source wire, signal wire and other cables.

© Mode switch Switch to set operation mode of slave module.

Setting at delivery of Setting at delivery of output module input module

MODE MODE

- Temination ~ Termination LI resblance LI resistance

- - Functional _ selling ma | setting EL] | - Output hold Li | invalid

- Invall

- Prohibit output LM | ifronptcuoa | | |, rON, - »ON

@ Module retention hole (49) Mounting holes of M3 screws.

Rating plate

© DIN rail lever For detaching from and attaching to DIN rail.

Page 93 read from a scan by OCR; it may hold reading errors

[Indicator lamp]

° ZW-324NH ERROR lamp, RUN lamp I \ WA Li ee I SHARP [O| “98999 en ERROR ZW-324NH ( STNo. MOOE _ Input lamp POWER lamp, - - P 20 (1zo9e 56701245 67 eases 7 e224 * 9"), (0107: 4 places) LG eo ee eee QOOO OOP OO OOOOH HOO 9g Ol) BOOOSHSHOHO8HHo09gs SOOO ey ° ZW-322SH ERROR lamp RUN lamp It aN OPun Cr Ct [0] SO099% ERROR ZW-322SH POWER lamp, - are Output lamp

FUSE lamp, _ - - 7

OL

¢ ZW-322MH

POWER lamp - - |frnmeronso@ 12 2 4

| (0 to 7 : 4 places)

a) Ye ERROR ame RUN lamp 809990" suarp Fo SHIELD Lz 1 © ERROR ZW-322MH [OUTPUTANPUT 0C24V] ADDRESS [ = - - - - - a, S ST.No. MODE c >, _ Input lamp 567 0 mE KEED) nore aTararer=rs a ails

FUSE lamp, - - - 1

Output lamp |

(0 to 7 : 2 places)

555GH5H5O0050005000 SOOHOH OHO HS OOOVOOOOGg, | ey wey

RUN Green | Lighting during normal operation Lights up when slave station is error or when impossible to ERROR Red communicate with the master station. It is lit when the 24 VDC power is ON. POWER Green |. The POWER lamp will not be tit when the DC power fuse is blown, or if the power source polarity is reversed. . When the ZW-324NH is used, this lamp will light when any of the input signals (32 points) is ON - When the ZW-322SH is used, this lamp will light when any of 0 to 7 (4 places) Red the output signals (32 points) is ON - When the ZW-322MH is used, this lamp will light when any of the I/O signals (16 points) is ON Lights when the common fuse for the output circuit (inside the FUSE Red module) is blown, or the load power is OFF.

- There is a FUSE lamp on the ZW-322SH/322MH models, but not on the ZW-324NH model., 86

Page 94 read from a scan by OCR; it may hold reading errors

[2] Wiring method

(1) Wiring cautions ¢ Use crimp-style terminals for connections to the limit switch, solenoid valve, and other external devices. Tightening torque: 10 kgfecm max.

M3.5 X 7 self lock-up screw

(2) Connecting communication cables

Grounding cable (accessory)

Control panel chassis

For wiring to L,, L,, and SHIELD terminals, use our recommended twisted pair wire with shield. For shielding of the shield wire, relay with a twisted air of about 0.5 mm? outside, and then wiring to the terminal block will be easier.

Keep the wire coming out of the shield as short as possible (30 mm or less), and connect to SHIELD terminal.

Do not connect signal cables to terminals other than the L,, L,, or SHIELD terminals. SHIELD and FG terminals are already shoted. Attach a ground wire between the FG terminal and the control panel chassis.

~87-

Page 95 read from a scan by OCR; it may hold reading errors

(3) Power supply wiring Twist DC power input lines with each other. As DC input power supply uses an insulation type

DC/DC converter inside the module, it is also applicable as power for input signal or output signal. Control panel chasis rounding line (accessory)

Class-3 grounding, - Om SHARP [O| SO8O9 Q Enron ZW-324NK [weutocev ] 24 TY +5V iS SS SS == DC power |_| SS SS er | loci _ - w - _ - - - - - _ - - - - - - - - - STNG, _ MODE 24V' converter orraste? OV ; (ov), r

DC power 24V

In case of sharing this power with load driving power for DC input/output signal, note wiring and noise prevention method.

Be sure that the I/O link slave module’s FG terminal is grounded through the control panel. It is also used us ground for the DC/DC converter.

When DC power is supplied to I/O link slave module positioned away from it, provide fuse elements for the DC power supply and each module respectively. Be careful for voltage drop due to long distance wiring module

Fuse 0 Slave module x Fuse O ()

Fuse

<Reference> Power voltage and line resistance Line resistance DC power voltage (V,) = 24V + slave module current x line resistance x 2 x wire length (km) | Nominal sectional area 0.3 mm’......61.9 ohm/km Line resistance Module AA‘ 0.5 mm?......37.1 ohm/km, - > hv Quirent 2] 0.75 mmé...... 24.8 ohm/km AAG

Reference | Terminal block cover

If it is difficulty to make the connections, you can raise the terminal block cover and bold it on the module indicator lamps.

- After the completion the wiring, secure the terminal block cover in its original position.

- The bending portion of the terminal block cover is designed to be bent dozens of times.

t Securing hole Terminal block cover However, if the terminal block cover breaks at bending point, you can secure the terminal ini ° O58 block cover using the holes shown left., 88 -

Page 96 read from a scan by OCR; it may hold reading errors

[3] Specifications

(1) General specifications ltem

Specifications

Allowable power voltage

24 VDC +10% (Ripple factor: Less than 5%), power for logic circuit

Power consumption/current

100 mA max.

Storage temperature, 20 to +70°C

Ambient operation temperature

0 to +55°C

Ambient humidity

35 to 90%RH (Not to condense dew)

Vibration resistance

Conforming to JIS-C-0911 (2 hours each in X, Y, Z directions)

Shock resistance

Conforming to JIS-C-0912 (10 G, 3 times each in X, Y, Z directions)

Withstand voltage

1000 VAC for one minute (between input/output terminalis, DC power input terminal, and secondary circuit)

Insulation resistance

500 VDC, 10 M-ohm min. (between input/output terminals, DC power input terminal, and secondary circuit)

Insulation method

Photo-coupler

Weight

Approximately 500 g

Accessories

One grounding cable, one user's manual

(2) Communication specifications

Item

Specifications

Data transfer rate

EIA RS485 or equivalent

Transfer rate

345.6 k bits/s, 172.8 k bits/s (changes automatically according to the data transfer speed of master station.

Transfer format

Asynchronous system

Coding method

NRZ (Non Return to Zero)

Frame check

Parity check and reverse-double verification

Communication fine

Synchronous mode Asynchronous Transfer mode Time sharing cyclic digital system Party line

Shielded twisted pain cable

Cable total length : 1 km max.

(3) Outside dimensions

Outline dimensions are common to all models.

© FUN

= 898g

“Io!

SHARP ZW-324NH =

JADDRESS|

3

Oo1r23a 567012

80 87.5

4667 OP 34567012946 B07 voor, oT? ps Te to Lov Jewal 1 Taps iz ts)

Cc S|] SOOOOOO

2

OOS OOOO OO |

Ce Lots |

OoLz[-TeéToTezTiy¢ [i tsPs tert: ts Cs iz]

SHHHOH9OH9SOG, | 2 ey

[ey

190 56

Lf

SS

%* Dimensions when a DIN rail lever is movd., ~89-

Page 97 read from a scan by OCR; it may hold reading errors

(4) Specifications of /O

@ ZW-324NH (24 VDC input module)

item Specifications No. of input point 32 points No. of slave station occupied bytes 4 bytes Rated input voltage 24 VDC Allowable input voltage 20.0 to 26.4 VDC

Ripple factor: Less than 15%

Rated input current

4.6 mA TYP. (at 24 VDC)

Input voltage level

ON level: 18.0 V or less, OFF level: 8.0 V or more

Input current level

ON level: 3 mA or less, OFF level: 1.5 mA or more

Input impedance

5.2 k ohm TYP.

Surge current

Response time (module alone)

OFF, ON: 1.0 ms or less (24 VDC) ON, OFF: 1.5 ms or less (24 VDC)

Commen terminal

1 common per 16 points

Outside connection drawings

Surface view

24 24 vc oo! coc [SY supply OV converter| ov O , z L] {lsolated) |_| FH I] indicator 3@ so iam @lgbI|° Be ( rd @ 2 San | Fal sf : 1 I z ra) \ } 1 Photo-coupler @ 5) . : 3) I a =I =@ oO 2D =, Photo-coupler @ yous OC

29 +f 2b oL4 9Gr ozo

Input indicatoy @ = @

+ jaro 2 [ss Tt {t+ Tips y]e Te [vercol Ao |] o jana] 9 [+ [2 fofs [Tr f @ [To frncolare

Internal circuit

[Aveoa. Ian] HNbZE-MZ

2o5r C240 £ SSr C2140

| Ls

¢"COM.A" is assigned at I/O link master module lower number of the communication area., ~90-

Page 98 read from a scan by OCR; it may hold reading errors

@ ZW-322SH (transistor output module)

Item Specifications No. of output point 32 points No. of slave station occupied bytes | 4 bytes Rated load voltage 24 VDC Allowable load voltage 10.0 to 26.4 VDC

Rated max. output current

0.3 A/point, 2 A/common

Surge ON current

0.2 A (100 ms}

Min. load current

Leakage current

0.1 mA or less

Voltage drop at turning ON

0.5 V or less (0.3 A)

Response time (module alone)

OFF, ON: 1 ms or less

ON, OFF: 1 ms or less (resistance load)

Surge killer

Zener diode

Rated fuse

2 A (unavailable replacement) Meltdown detection function is provided (When melted down or load power is turned OFF, the FUSE lamp lights)

Common terminal

1 common per 16 points

Outside connection drawings Surface view 24 VDC Bay [sv power pe/DC supply ov Converter ov (Isolated) output l indicato} © ri ' | 5 UW WAL _ lamp ; id nf o D| (| § 3 Photo-coupfer | a 5 2 1@ ar :|Leat @ Ale 00 ° g 2 - 3 7 wy D Ouiput 2 rn

Photo-coupler

4

. Internal circuit Lg i

[Reco INSINO] HSzzE-Mz

T 2eo5 r C2 |} O2906¢ FP ORBLE DA t I

* "COMN.A’ is assigned at I/O link master module lower number of the communication area.

* We recommend to install applicable fuse to every output for safety.

-~91-

Page 99 read from a scan by OCR; it may hold reading errors

@ ZW-322MH (transistor output, 24 VDC input module)

Item Specifications No. of slave station occupied bytes 4 bytes

No. of output point 16 points

Rated load voltage 24 VDC

Allowable load voltage 10 to 26.4 VDC

Rated max. output power 0.3 A/point, 2 A/common & | Surge ON current 0.5 A (100 ms) 8 Minimum load current - : G Leakage current (when OFF) 0.1 mA or less 2 | Voltage drop at turning ON 0.5 V or less (0.3 A) 2 Response time (module alone) | OFF, ON: 1 ms or less 5 ON, OFF: 1 ms or less (resistance load) ° Surge killer Zener diode

Rated fuse Built-in 2 A fuse {unable replacement)

Meltdown detection function is provided (When melted down or lead power is turned OFF, the FUSE lamp lights)

Common terminal 1 common per 16 points

No. of input point 16 points

Rated input voltage 24 VDC S | Allowable input voltage 20.0 to 26.4 VDC (Ripple factor: 15% or less) 8 Rated input current 4.6 mA TYP. (at 24 VDC) = | Input voltage level ON level: 18.0 V or less, OFF level: 8.0 V or up a. Input current level ON level: 3 mA or less, OFF level: 1.5 mA or up + | Input impedance 5.2 k ohm (TYP.) £ | Surge current _

Response time (Module alone)

OFF, ON: 1.0 ms or less (24 VDC)

ON -> OFF: 1.5 ms or Jess (24 VDC)

Common terminal

1 common line for 16 points (no polarity), ~ 92 -