Manual · Sharp
I/O link master module JW-31LMH Instruction Manual
Manual123 pagesPDF 3.3 MB
Instruction manual for the Sharp JW-31LMH I/O link master module and its ZW-series I/O link slave modules for W series PCs.
Covers · 1 model
The models it covers
Summary
What is in it
Sharp's instruction manual for the JW-31LMH I/O link master module, which fits an I/O slot of a W series programmable controller and links remote input and output slave modules over a single RS-485 cable. It covers system configuration, master module specifications, installation and wiring, switch settings, monitoring and error handling, transfer time and timing, a program example, and the ZW-series slave modules (ZW-82N/82S, ZW-161N to ZW-162M, ZW-164NH, ZW-324NH, ZW-84NC/162MC) with their own wiring and specifications.
Its parts
- Preface
- Safety precautions
- System configuration
- Master module specifications
- Name of function of each part
- Installation/wiring
- I/O link usage
- Monitor I/O link operation
- Required transfer time and communication timing
- Program examples
- Slave module
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Sharp instruction manual, version 1.0 from March 1998, for the JW-31LMH I/O link master module, which fits a Sharp W series programmable controller and links remote input and output modules over one RS-485 cable. It also covers the I/O link slave modules ZW-82N/82S, ZW-161N/162N/161S/162S/164S/162M, ZW-164NH/162SH/162MH, ZW-324NH/322SH/322MH and ZW-84NC/162MC. It explains installation, wiring, switch settings, status data, error indications and troubleshooting.
- Device type
- I/O link master module that replaces PC I/O wiring to remote inputs and loads with one communication cable p. 8
- Compatible PCs
- JW-50CU, JW-50CUH, JW-70CU, JW-70CUH, JW-100CU, JW-100CUH p. 9
- Capacity
- Up to 32 slave stations; max. 504 I/O link points (63 bytes) p. 15
- Transfer speed
- 345.6 k bits/sec, or 172.8 k bits/sec for older slave modules; set by S/H on switch SW2 p. 8, 15
- Network
- EIA RS-485 or equivalent, shielded twisted pair cable, 1 km total length max. p. 15
- Data exchange time
- About 13.1 ms for 504 I/O link points at 345.6 k bits/sec p. 8
- Power and weight
- 300 mA (5 VDC); approx. 370 g p. 14
- Environment
- Operation 0 to +55°C; storage -20 to +70°C; 35 to 90% RH without condensation p. 14
- PC resources used
- 16 I/O relay points (2 bytes) and a 64-byte data register area p. 15
- Terminal block
- 8 P terminal block (M 3.5 X 7 screws) p. 15
- Indicators
- COMM, MODE 3, ERROR, FAULT, CHECK, HALT lamps; 7-segment display of error code or error slave station p. 15, 16
- Setting switches
- SW1 I/O link bytes, SW2 mode, SW3 termination resistance, SW4 CHECK p. 16
- Communication modes
- Three modes, chosen on SW2; mode 3 confirms recovery manually p. 9, 16
- PC error codes
- 40 installed module check, 42 output data check error, 44 I/O data bus error, 45 I/O signal error, 46 special I/O error; stored at system memory #0160 p. 37
What this manual walks you through
- Installing the master module in the rack panel p. 17
- Wiring the communication cable to the master and slave stations p. 18, 19, 20, 21
- Using the CHECK and HALT relays p. 22, 23
- Data register layout for slave station data p. 23, 24
- Setting the number of I/O link bytes on SW1 p. 25
- Reading the status byte and error information p. 34, 35
- Finding the slave station with an error p. 36
- Module behavior when the PC stops, errs or loses power p. 37, 38
- Troubleshooting with the I/O link check flow p. 115
Good to know
- DIP switches on the master and slave modules are set only with the power off. p. 10
- The master module cannot go in slots already fitted with option cable ZW-2CC, ZW-4CC or ZW-6CC. p. 17
- With any low speed slave module connected, the transfer speed is set to 172.8 k bits/s. p. 13
- Short pulse signals may be missed; safety-related inputs go directly to the PC. p. 10
- Communication errors are detected only from input module data. p. 36
Questions this manual answers
How many slave modules can a JW-31LMH control?
Up to 32 slave modules with at most 504 I/O link points, over a total cable length of up to 1 km. p. 8
What does the FAULT lamp on the JW-31LMH mean?
It shows an error of the master module itself; the manual says to replace the master module. p. 36
How do I see which slave station has an error?
Turn on both the HALT and CHECK relays; the master module displays the error station address, lowest first when there are several. p. 36
Which Sharp PLCs take the JW-31LMH?
The JW-50CU, JW-50CUH, JW-70CU, JW-70CUH, JW-100CU and JW-100CUH. p. 9
Contents
Chapters and sections
Each line opens the PDF at its page.
- Cover1
- Introduction2
- Safety Precautions3
- §1 Preface8
- §2 Safety precautions10
- §3 System configuration11
- §4 Master module specifications14
- §5 Name of function of each part16
- §6 Installation/wiring17
- §7 I/O link usage22
- §8 Monitor I/O link operation34
- §9 Required transfer time and communication timing40
- §10 Program examples47
- §11 Slave module50
- §12 Appendix115
The whole text · 18 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 41-4
- Table of Contents5-7
- Pages 8 to 108-10
- §3 System configuration11-13
- Pages 14 to 1614-16
- §6 Installation/wiring17-21
- §7 I/O link usage22-33
- §8 Monitor I/O link operation34-39
- §9 Required transfer time and communication timing40-46
- §10 Program examples47-49
- §11 Slave module, pages 50 to 5950-59
- §11 Slave module, pages 60 to 6960-69
- §11 Slave module, pages 70 to 7970-79
- §11 Slave module, pages 80 to 8980-89
- §11 Slave module, pages 90 to 9990-99
- §11 Slave module, pages 100 to 109100-109
- §11 Slave module, pages 110 to 114110-114
- Pages 115 to 123115-123
The file