§6 Installation/wiring

6-1 Installation method

1) Insert the master module connector of the I/O module into module connector of the basic rack panel.

2) Tighten 2 pcs. of rack panel retention screw of the master module onto the rack panel using philips screwdriver.

or

Philips screwdriver

~~ JW-31LMH

Side panel

When detaching or attaching the rack panel in the master module, be sure to turn OFF the power source of the rack panel. Detaching or attaching operation cannot be done in I/O live line.

When you install the master module at the left end of the rack panel: JW-13BU or JW-6BU, be sure to install a side plate to the rack panel which is supplied as an accessory.

The master modules cannot be installed onto slots already equipped optional cable: ZW-2CC, ZW-4CC, or ZW-6CC.

Seen TTT

Cable for option module: ZW-4CC

L_ Unable to install master module on these slots.

-~10- - -

Page 18 read from a scan by OCR; it may hold reading errors

6-2 Wiring method

[1] Terminal block number

Termination resistance switch

COMM Y/”

_ Sending

LEE o

SHILD @ (Open)

FG O - --4,__ signal

Receiving

Ss signal

Error Fault

* FAULT

ERROR 7” 7

L190, _ L26 + SG ¢ Li] | L2 7] | se {|_| SHILD>| _| FG -

[2] Wiring of communication cable

(1) Recommended cable

Use our recommended cable, twisted shield pair cables, for wiring.

2-wire system

* HITACHI CABLE LTD.

¢ FUJIKURA LTD.

S-IREV-SW2 “0.5

S-IREV-SB2 * 0.5

RG-22B/U

Don't use wiring communication cables in a place exposed to severe stress or bending due to moving of the master module or slave module.

~W-

Page 19 read from a scan by OCR; it may hold reading errors

(2) Wiring of the master module Wire in 2-wire system communication cable of the master module as follows:

Terminal block

Insulation tape | -S] g

Signal cable \

Li, 2 Twisted cable

30 mm SHIELD

Class-3 grounding

> SHIELD terminal and FG terminal are shorted using a shorting tab.

Note 1 Use our recommended twisted pair shield cable for wiring to the terminals L,, L,, and SHIELD. When wiring the shield line to the terminal block, it is conventent to relay 0.5 mm? twisted cable at the outside of the shield cable.

Note 2| Cables connected with the shield cable should be kept as short as possible (below 30 mm).

Note 3] In 1/O link function, do not connect the signal cable except for the terminals of L,, L,, SG and SHIELD.

Note 4| Use the crimp-style terminals for wiring to terminal block. Select crimp-style terminals with referring the illustration as below.

7.7mm M3.5 X 6mm Self lock-up screw, ~12~

Page 20 read from a scan by OCR; it may hold reading errors

(3) Wiring method with slave station

Wiring in 2 wire system.

Master station Slave station Slave station Slave station JW-31LMH 01(8) 02(8) 37(8) Li (\ - _-A_\ “4 lar aan Ly Qo EEE Li Le Le L2 Lt) / \ S\ Le SHIELD SHIELD “ISHIELD SHIELD Twisted pair | FG shield wires a ob = Class-3 Class-3 Class-3 Class-3 grounding grounding grounding grounding

Note 1 Connect the shield line of the communication cable with SHIELD terminal.

Note 2 | Be sure to short circuit between the SHIELD terminal and the FG terminal of the master module externally. In case of slave module, connect class-3 grounding with its SHIELD terminal. Otherwise, it may easily pick up electrical noise and cause malfunction.

Note 3 | Be sure to execute class-3 grounding for the FG terminal. Avoid co-grounding with other modules. If not grounded, modules easily pick up electric noise, which causes a malfunction.

Note 4 | Each SHIELD terminal of master and slave module are open terminals. According to the noise condition, it is a good idea to execute one point grounding for the shield line of the communication cable.

Note 5 | Cable should be lined from one master module to one slave module and next slave module one by one. Do not execute multiple wiring from one source point.

OQ} anno

Good No good : \ 7 J Junction terminal Junction using a connector

Note 6 | Keep the communication cable as far away as possible from the high voltage and power lines, so as not to close in parallel.

Note 7 | Use our recommended cable for communication cable and keep its total length within 1 km.

Note 8] Do not mis-set or double set slave module numbers and not to use larger slave module numbers than total number of set master module., ~13-

Page 21 read from a scan by OCR; it may hold reading errors

Not necessary to set the modules in order, one by one, nor setting the master module as termination station. The following example is available.

Slave Slave Slave Master Slave Slave Slave Slave station 4 station6 station 1 station station2 station3 station 7 station 5

Switch ON termination resistance ff switch on both termination station

Note 10] Do not wire load driving cables and power supply in the same duct of communication cable. (For the cable supplying power to a slave module exclusively and not for load driving, wiring in the same duct is available.)

Communication cable

Slave module Master im module Wiring for DC power supply ] i Power cable pipe DC power 7 “ ] supply, ~14-