The text of a manual · part 5 of 18
I/O link master module JW-31LMH Instruction Manual, pages 14 to 16
Pages 14 to 16 of 123: §4 Master module specifications; §5 Name of function of each part
The original document is the PDF (3.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Sharp JW-31LMH
Page 14
§4 Master module specifications
4-1 General specifications
Storage temperature
-20 to +70°C
Ambient operation temperature
0 to +55°C
Ambient humidity
35 to 90% RH (without dew condensation)
Vibration resistance
JIS-C-0911 or equivalent (2 hours for X, Y, and Z axes)
Shock resistance
JIS-C-0912 or equivalent (10G 3 times for X, Y, and Z axes)
Power consumption 300 mA (5 VDC) Weight Approx. 370 g Accessories One instruction manual
[Outside dimensions]
JW-31LMH
250
(Unit: mm)
ne
E:
vita] ig
105 |
¢ As for I/O link slave module ZW-82N/82S, ZW-161N/162N/161S/162S/164S/162M, ZW-164NH/ 162SH/162MH, ZW-324NH/322SH/322MH, and ZW-84NC/162MC, see page 43 to 107. ¢ As for LCD terminal and manifold solenoid valve, see the individual manuals.
Page 15
4-2 Specifications of master module
[1] General specifications
Number of I/O link stations Max. 32 Number of I/O link points Max. 504 (63 bytes) /O relay: 16 points (2 bytes) Data register for special I/O module: 64 bytes For communication monitoring flag : 1 byte
For I/O data link : 63 bytes (However, I/O linked communication begins synchronously with the PC scan cycle.) COMM, MODE 3, ERROR, FAULT, CHECK, HALT Error code, error slave station number Outer wire connection 8 P terminal block (M 3.5 X 7 screws)
Number of I/O occupied points
Synchronous with PC processing
Operation indication
[2] Communication specifications
Data transfer standard EIA RS-485 or equivalent
345.6 k bits/sec, 172.8 k bits/sec. (Changeover by S/H of Transfer speed .
switch SW2) Data format Stari-stop synchronous system Coding method NRZ (Non Return to Zero) Frame check Parity check and double-reverse check Synchronous mode Start-stop system Transfer mode Time sharing cyclic digital system
Party line
Communication line Shielded twisted pair cable
Cable total length: 1 km max.
Page 16
§5 Name of function of each part
@
® ©
@
Indicator lamp
Operation lamp (For detail, see page 29)
(0 Error code or error slave station number indication
COMM............ Communicating
MODES .......... Mode is set to 3
ERROR ......... Error
FAULLT........... Fault
CHECK ......... Checking 7 ey,
HALT ..........-- Stop communication
Rating plate
Setting section cover
Terminal block (connector type terminal block) for communication cable connection.
Module retention screw
Setting switch (see page 18) Switches to select function of the module.
SW1 oe For setting I/O link bytes SW2 wee For mode setting
SWS ........0008 Termination resistance switch SW4 oo. CHECK switch
Terminal block cover
Indicator © a ee _ O e) 2) Rating plate @ Setting section @ cover ] Terminal block @ |
Module retension screw ©
Setting switch ©.
Setting section @ cover vo
] rene ae
Terminal block (7) cover
% As for the CHECK lamp and HALT lamp, see pages 15 (CHECK relay) and 16 (HALT relay)
respectively.
Each position of lamp is located on the setting section cover.