§4 Master module specifications

4-1 General specifications

Storage temperature

-20 to +70°C

Ambient operation temperature

0 to +55°C

Ambient humidity

35 to 90% RH (without dew condensation)

Vibration resistance

JIS-C-0911 or equivalent (2 hours for X, Y, and Z axes)

Shock resistance

JIS-C-0912 or equivalent (10G 3 times for X, Y, and Z axes)

Power consumption 300 mA (5 VDC) Weight Approx. 370 g Accessories One instruction manual

[Outside dimensions]

JW-31LMH

250

(Unit: mm)

ne

E:

vita] ig

105 |

¢ As for I/O link slave module ZW-82N/82S, ZW-161N/162N/161S/162S/164S/162M, ZW-164NH/ 162SH/162MH, ZW-324NH/322SH/322MH, and ZW-84NC/162MC, see page 43 to 107. ¢ As for LCD terminal and manifold solenoid valve, see the individual manuals.

Page 15 read from a scan by OCR; it may hold reading errors

4-2 Specifications of master module

[1] General specifications

Number of I/O link stations Max. 32 Number of I/O link points Max. 504 (63 bytes) /O relay: 16 points (2 bytes) Data register for special I/O module: 64 bytes For communication monitoring flag : 1 byte

For I/O data link : 63 bytes (However, I/O linked communication begins synchronously with the PC scan cycle.) COMM, MODE 3, ERROR, FAULT, CHECK, HALT Error code, error slave station number Outer wire connection 8 P terminal block (M 3.5 X 7 screws)

Number of I/O occupied points

Synchronous with PC processing

Operation indication

[2] Communication specifications

Data transfer standard EIA RS-485 or equivalent

345.6 k bits/sec, 172.8 k bits/sec. (Changeover by S/H of Transfer speed .

switch SW2) Data format Stari-stop synchronous system Coding method NRZ (Non Return to Zero) Frame check Parity check and double-reverse check Synchronous mode Start-stop system Transfer mode Time sharing cyclic digital system

Party line

Communication line Shielded twisted pair cable

Cable total length: 1 km max.

Page 16 read from a scan by OCR; it may hold reading errors

§5 Name of function of each part

@

® ©

@

Indicator lamp

Operation lamp (For detail, see page 29)

(0 Error code or error slave station number indication

COMM............ Communicating

MODES .......... Mode is set to 3

ERROR ......... Error

FAULLT........... Fault

CHECK ......... Checking 7 ey,

HALT ..........-- Stop communication

Rating plate

Setting section cover

Terminal block (connector type terminal block) for communication cable connection.

Module retention screw

Setting switch (see page 18) Switches to select function of the module.

SW1 oe For setting I/O link bytes SW2 wee For mode setting

SWS ........0008 Termination resistance switch SW4 oo. CHECK switch

Terminal block cover

Indicator © a ee _ O e) 2) Rating plate @ Setting section @ cover ] Terminal block @ |

Module retension screw ©

Setting switch ©.

Setting section @ cover vo

] rene ae

Terminal block (7) cover

% As for the CHECK lamp and HALT lamp, see pages 15 (CHECK relay) and 16 (HALT relay)

respectively.

Each position of lamp is located on the setting section cover.