Page 50
§11 Slave module
The table below lists the Sharp I/O link slave modules which can be connected to the JW-31LMH as slave modules.
Model name No. of points Specification ZW-82N 8 points 12/24 VDC ZW-161N 16 points 100 to 120 VAC Input ZW-162N 16 points 12/24 VDC
ZW-164NH 16 points 24 VDC ZW-324NH 32 points 24 VDC
ZW-84NC 8 points 24 VDC ZW-82S 8 points 12/24 VDC, 0.3 A, transistor output ZW-161S 16 points 100 to 120 VAC, 0.5 A, triac output Output | ZW-162S 16 points 12/24 VDC, 0.3 A, transistor output ZW-164S 16 points 264 VAC/30 VDC, 2 A, relay output (separated common)
ZW-162SH 16 points 24 VDC, 0.3 A, transistor output ZW-322SH 32points 24 VDC, 0.3 A, transistor output 12/24 VDC, 0.3 A, transistor output 8 points, 12/24 VDC input 8
ZW-162M 16 points points
ZW-162MH 46 points 24 VDC, 0.3 A, transistor output 8 points, 24 VDC input 8 0 points
ZW-322MH 32 points oints 0.3 A, transistor output 16 points, 24 VDC input 16
ZW-162MC 16 points ons 0.3 A, transistor output 8 points, 24 VDC input 8
¢ For LCD terminal and manifold solenaid valve, see respective instruction manuals.
~43-
Page 51
11-1 ZW-82N/82S
[1] Name and function of each part
Module retention hole (4 ¢} Uses M3 screw.
Indicator lamp Show operational status.
Terminal block covers Protect the terminal blocks.
Rating plate
Terminal block Terminals for power, a communication, and other lines. Switch cover SA J Protects mode setting switch. NY Switch cover Protects address setting switch. . . Mode setting switch
Address setting switch Sets operational mode. Sets slave station number.
(Set condition at delivery) Output Module Intput Module OFF ON (Set condition at delivery) (Set condition at delivery) a] j-40 12 3 4 ION 123 4 10 IN aie <|OLE SGU, 10 “4 = J | oFF = OFF = |-1 Bg. Bf 3g. ; ints 3580 » ADDRESS beceees Baby E, A4
Page 52
[2] Setting switch
Be sure to turn OFF the power to the PC before setting switches. Setting switches while power is ON could cause a malfunction.
(1) Address setting switch (ST No.)
Set slave station number (ST No.). * Set from "01" in octal notation.
¢ Set which byte of the "I/O link area" in the mastermodule is used.
OFF ON, 40, 20
0, 4 Octal notation, 2 ms |
Hanae
ADDRESS
Example: When using two 16 points slave module and one 8 poinis slave module:
Status
Slave station 01. - - »
16 points module
/- - - _>
Slave station 03,, | - - - - >
16 points module oO
402010 4 2 1 N |! ] | uuUUR
402010 4 2 1 Nitti
Slave station 056) |} - _ - - - _>
8 points module
Sele
OFF ON, - » |EL_]/-40 m_|| - 20 m__]|-10 C_B|-4 mg_|-2 LC H\-1
Duplicate setting of slave station addresses will result in a malfunction.
Duplicate setting
Operation
If two input modules have the same address
Unspecified input data
If an input module and an output module have the same address
Unspecified data and output module condition
If two output modules have the same address
Output of same data
The slave station address of the LCD terminal Z-SM10 shall be set in decimal notation., ~45-
Page 53
{2) Mode setting switch Sets termination resistance, function, and other items.
(Output module) (Input module) CG, _ > ® ~ 228 2 ON= c < ON = m| 12 3 4 w) 12 3 4 oe) oe = = OFX UE OFF - OFFOFF i = , av” i Oo S | © i= !loea (= | { | ! i I ! Sq ! 3 Sa | i 28 a =o. i 258m 2 Ss B8S8q x ea BE o ga EBBES § eses Pas eses =z
@ Termination resistance « When seiting termination resistance switches, those for stations on the ends of I/O link lines should be "ON," and all other stations should be “OFF." « The delivery setting is "ON." « Setting example: In the diagram below, slave station 03,,, and the master station are set to "ON," while the other stations are set to "OFF."
Slave station 03,, Slave station01,, Slave station02, Slave station 04,,, Master station
ON OFF OFF OFF ON
| | | | | | |
@ Function setting switch oN I/O link line
¢ Sets “OFF : I/O link” as communication functions. ¢ The delivery setting is “OFF.” ¢ Module will not operate, if turned “ON.”
@ Output hold switch (on output module only)
* When the I/O link communication is error, set the operation at the slave module side. If there is no communication from the master module for more than 1 second, it is judged that the communication is suspended.
The communication is also suspended when the master module HALT relay is "ON."
Setting value} Function Description
ON Reset | All outputs are "OFF" when communication is suspended. Output before suspension is held when communication is suspended. *When the CPU is error (when the watchdog timer is actuated), all outputs are "OFF."
OFF Hold
@ Output prohibit switch (on output module only) « This is the communication test switch of output module.
Setting value | Function Description ; Lamp of output module and output element are "ON/OFF" ON Permit . . depending on the output signal of PC. OFF Hold Output elements are all "OFF" regardless of PC output signal.
-46-
Page 54
[3] Installation method
(1)
(2)
Installation
Avoid keeping slave module in the following condition.
¢ Direct sunlight.
¢ Ambient temperatures below 0°C and over 55°C.
¢ No condensation due to rapid temperature variation.
* Relative humidity which exceeds 35 to 90%.
¢ Corrosive and flammable gases.
* Dusts, iron, and salty conditions.
¢ Vibration and shock producing and transferring positions. « Slave module should be installed with its top facing up.
Good installation No-good installation
* As module are not dustproof or waterproof, install them in sealed cabinets if at all possible.
« Avoid installation just above high calorie heat generating devices (heaters, transformers, high capacity resistance etc.). Also avoid to install other equipment close to slave module.
¢ Avoid installation in a box in which high voltage device is installed.
* As much as possible keep away from high voltage cables and power cables.
* Install on a good conductivity metal plated panel instead of painted one for easy grounding and better noise tolerance.
e Use zinc plated retention screws of M3 for installing slave module.
Installation dimensions joneeeeee Y (Unit: mm) 1 Wiring duet Z t y 2 4 7 be ergs rt i r poccreby poeeeeey pemreetny Y toi tt | q Z Ys it , ot : fi Y ' 1 4 tt : [a | 4 << - - M3 tapped hole | (Wiring allowance} wring - 1 Wiring du
LL 1 Yrers,
* Secure 50 mm or more space above and below the
Ls module for heat radiation. Keep away for 30 mm or more between moduies for wiring.
* Use 2 M3 x 10 screws for retention.
eh biti
~A7-
Page 55
[4] Wiring method (1) Wiring cautions
Use crimp-style terminals for connecting external devices such as limit switches and solenoid valves with input/output module. Select crimp-style terminals referring the dimensions below.
© M3.0X8 Self lock-up screw
RQ... torque:
10 kg-cm or less
M3.0X8 | 74, Self lock-up screw
(2) Connecting communication cables
Terminal block leletele; rere
Insulation tape
Signal cable
Twisted wire he {30 mm)
150 mm or less
Fisi-cisisisls lelelete)
Use the recommended twisted pair shield cable for wiring to the terminals L,, L,, and SHIELD. When wiring the shield line to the terminal block, it is convenient to relay the twisted cable with 0.5 mm® at the outside of the shield cable.
Note 2} When installing a slave module in a new location or otherwise moving it, be careful that the communication cable is not excessively stressed or bent.
Note 3| Cables from the shield should be kept as short as possible (below 30 mm).
Note 4] Ground the slave module’s FG terminal (frame ground terminal) with a twisted cable of about 0.5 mm? using the SHIELD terminal. From FG terminal, ground to the control panel chassis with a cable not longer than 150 mm., 48
Page 56
(3) Power supply wiring Twist DC power input lines with each other. As DC input power supply uses a insulation type DC/DC converter inside the module, it is also applicable as power for input signal or output signal.
5 ie) fe) oO fe) 24 VDC con power = ° my = : supply ‘ oo] OF sor So wv SJ yO ms DC/DC { C)} =| 4 - - - - converter 4 sue 24D = ‘ u = (For logic circuit) = C) 6 se C) Eis a © - © ov ~«< - - - C 1?) : io) ie)
FG terminal Class-3 grounding
In case of sharing this power with load driving power for DC input/output signal, note wiring and noise prevention method.
FG terminal of slave module is sure to connect with ground through base by cable below 150 mm. It is also used as ground for the DC/DC converter.
When DC power is supplied to a slave module positioned away from it, provide fuse elements for the DC power supply and each module respectively. Be careful for voltage drop due to long distance wiring.
Slave module
Fuse
Fuse
Slave module
() Fuse O 2
Slave module O © power
<Reference> Power voltage and line resistance Line resistance DC power voltage (V,) = 24V + slave module current x line resistance x 2 x wire length (km) | Nominal sectional area 0.3 mm?......61.9 ohm/km ‘ : Module Line resistance 2 AA 0.5 mm~......37.1 ohm/km DBC power V1 Current 24V 0.75 mm’......24.8 ohm/km supply < - _ II, AQg-
Page 57
(4) Wiring input signal cable i DC input (ZW-82N)
DC power supply: 12/24 VDC
SHARP Onn Ono) poo a BI => u-) eI | 59 u 3 - ~0 ire _L_ External supply power a miei - 42/24 VDC {5 -~~9, __ - _ swevolC) | Input tools [E (5) Wiring output signal cable EE Transistor output (ZW-82S) DC power supply: 12/24 VDC Fuse element :125 VAC, 3A (on the market) =" ° External supply power Or Ore 12/24 VDC Oa ene ou, O - - to} gio Oo fo t - - O- - fO!, O - - «0 - - _ - -(" +) sneol CD Output tools | 8 *-é oa) [& LE |
% Be sure to provide a fuse element for the slave module so as not to burn it out.
¢ Ina DC output module, the (-) pole of external power supply and the (-) pole of DC power are conductive, and be sure to connect wiring to COM (-) terminal., 50-
Page 58
[5] Error and treatment
You can see the self-diagnosis results by the indicator lamps.
il Display meaning Lighting condition Reset method RUN In operation Slave station normal operation, * Slave station switch setting error * Set slave station switch again. ERROR Error * Communication error * Check communication cable. * PC stopped * Operate PC. * Slave module defective ¢ Replace slave module . RESET Reset, HOLD Hold ¢ At master station HALT relay "ON.", Input indicator Comes on when the input signal to the _ Oto7 lamp slave module is "ON. Output indicator Lights when output signal from PC is _ lamp "ON". Operation Indicator lamp Reset Priority description In operation | Error Input Output method order RUN ERROR . Changes due to No control input @ signal from PC Reset input e All points “OFE" points “OFF _ a3] . <= | Hold input © @ Output hold Qo 2 ‘ = Reset and 8 hold input ) Reset input is given "ON", priority. Output prohibit e "OFF" by switch "ON" input | All points "OFF" signal Slave module error e Replace slave module. S 1 oO 3 Switch setting e Set address switch @ | efror again. S 7g | Communication . = | suspended ® e . PC operation 2 S Holding state 8 | Communication before abnormality | Check communication error @ ) cable. 3 (output only) Replace slave module.
@: Lighting, @: Blinks The RESET lamp lights ON only when ZW-31LM is used for master module.
The HOLD lamp lights ON when JW-31LM/JW-23LM/JW-23LMH are used for master module as synchronizing to internal relay, and also lights ON with CHECK relay "ON" in the case of mode 3 and mode 6., 5i-
Page 59
[6] Specifications
(1) General specifications
Item Specifications
Storage temperature -20 to +70°C
Ambient operation temperature | 0 to +55°C
Ambient humidity 35 to 90%RH (No condensation)
Vibration resistance Conforming to JIS-C-0911 (2 hours each in X, Y, Z directions)
Shock resistance Conforming to JIS-C-0912
Allowable power voltage 24 VDC + 15% (ripple factor: less than 5%), power source for logic circuit
Power consumption current 100 mA (24 VDC)
Weight Approx. 300 g (ZW-82N, ZW-82S)
(2) Communication specifications tem Specifications Data transfer rate EIA RS485 or equivalent Transfer rate 172.8 k bits/s Transfer format Asynchronous system Coding method NRZ (Non Return to Zero) Frame check Parity check and reverse-double verification Synchronous mode Asynchronous Transfer mode Time sharing cyclic digital system Communication line Party line
Shielded twisted pain cable
Cable total length : 1 km max.
(3) Outside dimensions (same for both input and output module)
2X4.06 (Unit: mm)
/ ra \ _ A | A
Oo SHARP Onun * O1 COUERROR O2 “petaay OneseT Os cone ell cH © 'q ell Ho LO qd 98 OF g|@ J) jy 38 OF “Mm s88 d zg gee
Sx C) 4 u C) | i W C) 6 SG rq C) 7 SHIELD C) rq QO” al _ - v ro Lo
\ Let * | yt. 5
« 50 > < 60 >, 52-