I/O link master module JW-31LMH Instruction Manual: §11 Slave module, pages 60 to 69
Pages 60 to 69 of 123, from I/O link master module JW-31LMH Instruction Manual
The original document is the PDF (3.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Sharp JW-31LMH
Page 60
(4) Specification of each module
@ ZW-82N (12/24 VDC input module)
Item Specifications . No. of input points 8 points No. of slave station occupied bytes 1 byte Rated input voltage 12/24VDC xX Max. input voltage 26.4 VDC
Rated input current
10.5 mA (at TYP. 24 VDC), 5.5 mA (at TYP. 12 VDC)
Input voltage level
ON level : 10 V or less (at ripple lower limit voltage) OFF level: 6 V or up (at ripple upper limit voltage)
Input current level
ON level : 3.5 mA or less, OFF level: 1.5 mA or up
Input impedance
2.3 k ohm (TYP.)
Response time
OFF ~+ ON: 30 ms or less (12/24 VDC) ON, OFF: 30 ms or less (12/24 VDC)
DC power consumption with current (24 VDC)
Max. 100 mA (power for logic circuit)
Operation indication
Light at ON (8 pcs. of LED)
Connection terminal
Terminal block 8P x 2 pcs.
Applicable wire
1.25 mm? or less
Ambient temperature, humidity
0 to 55°C, 35 to 90%RH
Dielectric strength
250 VAC, 1 minute (between input terminal, power input terminal and secondary circuit)
Insulation resistance terminal
500 VDC, 10 M ohm or up {between input terminal, power input and secondary circuit)
Insulation system
By photo-coupler
Common terminal
1 common per 8 points
Outside connection drawings Surface view DC power a VDC | pc/pc > Logic supply converter circuit fo\ 24 VDC -) (Isolated) md Oo SHARP On 2 Once External supply | Oo couch power OP | ©] 12/24 VDC fe} @ [Ol 2 rt) Common (+) Input indicator lamp TO | OTe ry uw aw rei fC] +o oO 0 WA 4 re) 7 SHIELD) re) Input indicator lamp 3: [FE aw o = i ® NY, | A__}7 AW 4 x Full wave rectified DC power without smoothing cannot be used. Ripple factor should be less than 5% in 12 VDC and less than 15% in 24 VDC.
~53-
Page 61
@ ZW-82S (12/24 VDC output module)
Item Specifications No. of output points 8 points No. of slave station occupied bytes 1 byte Rated output voltage 12/24 VDC Allowable output voltage 10 to 30 VDC Rated max. output current 0.3A
Surge ON current
Output element capacity: 1 A (PULSE PW = 20 ms, DUTY = 1/2)
Leakage current
0.1 mA or less
ON voltage
0.5 V or less (0.3 A)
Response time
OFF, ON: 1 ms or less, ON ~ OFF: 1msorless >
DC power consumption with current (24 VDC)
Max. 100 mA (power for logic circuit)
External supply power (10 to 30 VDC)
Max. 5 mA/point
Operation indication
Light at ON (8 pes. of LED)
Connection terminal
Terminal block 8P x 2 pes.
Applicable wire
1.25 mm? or less
Ambient temperature, humidity
0 to 55°C, 35 to 90%RH
Dielectric strength
250 VAC, 1 minute (between output terminal, power input terminal, and secondary circuit) Insulation resistance 500 VDC, 10 M-ohm or up (between output terminal, power input terminal, and secondary circuit)
Insulation system
By photo-coupler
Common terminal
1 common per 8 points
Outside connection drawings Surface view 24 VDC DC power DC/DCG, > Logic supply T (+) converter |, circuit 24 VDC - (Isolated) fo Oc SHARP Onun Output indicator lamp g) Ourer ANA ww Os con _o - 2 Py > 4 ‘ ) re) Load ae , £9) Pen [QD | 4 ul CD] he ' CI = Output indicator lamp i “(O a 7 sain! (| greed idl O7, s 3A , \}ol/ External COM (+) supply = _L power T | COM (-) 12/24 VDC > When induction load is applied, the switching time from "ON" to "OFF" may delay 1 second or more by inductance of load.
~54-
Page 62
11-2 ZW-161N/162N/161S/162S/164S/162M
[1] Name and function of each part
@ Indicator lamp @ Module retention
@®Rating plate pole Display each operation condition. (See as @ Station number _-~% below)
(STNo.) @ Terminal block cover (integral with case) Protective cover for termina! block Detachable by cutting off fixing portion.
@ Switch cover
® Indicator lamp Protective cover of station number (ST No.) setting switch @ and mode setting switch ©
@) Station number (ST No.) setting switch Set the station number of slave module. &) Terminal block
Connect power source wire, signal wire and other cables.
Mode switch
Switch to set operation mode of slave module. Module retention hole (40)
Mounting holes of M3 screws
Rating plate
DIN rail lever
For detaching from and attaching to DIN lever.
\ / RUN lamp
©Mode setting switch
@ Switch cover
J © Terminal block /
DIN rail lever
©® © ®
[indicator lamp] ERROR lamp tI AY Li J Orrun SHARP [O| SOOO ERROR ZW-164S
24 VDC power lamp - { - >0, 5 6 ° ; 00 0 0 000 3 ; ome) ot I/O lamp
[Cit enna Te ear oa wear ec Touro ee eo ee
QOOOSGOGHO SO OOOOOOO9 fo] h SOOOGHOSOOEOOOGH HO HOO way Wy
(Indicator lamps are common to all models.)
Lamp name Color Operation
Run lamp Green | Lighting during normal operation
Red Lights up when slave station is error or when impossible to communicate with the master station.
24 VDC power lamp | Green | Light when the DC input power source is turned "ON."
Input, output lamps | Red Light when input and output are "ON."
Error lamp
The 24 VDC power lamp does not light when the fuse of DC input power supply is blown the polarity of power source is wrong.
-55-
Page 63
[2] Setting switch Before setting the switch, turn OFF the power supply to the PC. Switch setting without turing OFF the power supply may cause malfunction.
(1) Address switch (ST No.)
Set slave station number (ST No.). Setting at delivery * Set from “01” in octal notation. 4020104 2 1 * Set which byte of the "I/O link area” in the master module is used. { Lt
ST No
Example: When using two 16 points slave module and one 8 points slave module:
402010 4 2 1 ON! Tritt Status nn uy : : Slave station O15) |______._» 1 16 points module |- - - » 402010 4 2 1 Slave station 03,, © [>| 16 points module » ON . 3 ooints modu OFF ON ae Slave station 05, - - - - + | 8 points module = |-40 mm 1\-20 7 E10 P0104 2 | i CH|-4 Slave station 06,,, t+ | 32 points module a9 ' Sit > | QUU6BL 402010 4 2 1 Slave station 12, t+ > | 32 points module > 1a I uF a i
Duplicate setting of slave station addresses will result in a malfunction.
Duplicate setting Operation If two input modules have the same address Unspecified input data lf an input module and an output module have the same address |Unspecified data and output module condition If two output modules have the same address Output of same data
The slave station address of the LCD terminal Z-SM10 shall be set in decimal notation., 56-
Page 64
(2) Mode setting switch Sets termination resistance, function, and other items.
Set condition at delivery Set condition at delivery as an output module as an input module
MODE MODE [i |- Termination resisitance [Bi | - Termination resisitance B__] | - Function setting H__| | - Function setting H_] | - Hold output | T Invalid [CJ | - Prohibit output CH, ON (prohibit-allowed), ON
@ Termination resistance
* When setting termination resistance switches, those for stations on the ends of I/O link lines should be “ON,” and all other stations should be “OFF.”
¢ The delivery setting is “ON.”
¢ Setting example:
In the diagram below, slave station 03, and the master station are set to “ON,” while the other stations are set to “OFF.”
Master station
Slave station 03,, Slave station 01,,, Slave station 02,, Slave station 04,,,
ON OFF OFF OFF ON oN /O link line @ Function setting switch e Sets “OFF: I/O link” as communication function. ¢ The delivery setting is “OFF.” * Module will not operate if turned “ON.”
@ Output hold setting switch (on output module only)
* When the I/O link communication is error, set the operation at the slave module side. If there is no communication from the master module for more than 1 second, it is judged that the communication is suspended.
The communication is also suspended when the master module HALT relay is “ON.”
Set value | Function Description ON Reset All outputs are “OFF” when communication is suspended. Output before suspension is held when communication is OFF Hold P > SUSP reanont suspended. *X
> When the CPU is error (when the watchdog timer is actuated), all outputs are “OFF.”
@) Output prohibit setting switch (on output module only) * This is the communication test switch of output module.
Set value | Function Description
ON Permit Lamp of output module and output element are “ON/OFF” depending on the output signal of PC.
Output elements are ali “OFF” regardless of PC output signal.
OFF Hold
-57-
Page 65
[3] installation method
(1) Installation
Avoid keeping slave module in the following condition.
* Direct sunlight.
¢ Ambient temperatures below 0°C and over 55°C.
« No condensation due to rapid temperature variation.
Relative humidity which exceeds 35 to 90%.
Corrosive and flammable gases.
Dusts, iron, and salty conditions.
Vibration and shock producing and transferring positions. Peripheral space needed in 5 directions for ventilation and wiring.
50 50 aN
<r ul] > CSC / 7 7
Wiring duct bo Wiring duct eS
50
N
SOAS
SS
.0oee.
50
§ a ie 100 Wiring duct ey
3X Slave module should be placed at least 100 mm apart for adequate cooling.
06 20 500008.
SAN
* Install in one of the following 4 directions, which afford good cooling.
| Horizontal mounting | Vertical mounting
COCOLD F po soeacc0s xabarat, 4
GoosooGs oagoooun oO
¢ Being not designed for dust and water proof construction, install in an enclosed panel.
¢ Avoid installation just above high calorie heat generating devices (heaters, transformers, high capacity resistance etc.) Also avoid to install other equipment close to slave module.
¢ Avoid installation in a box in which high voltage device is installed.
* As much as possible keep away from high voltage cables and power cables.
* install on a good conductivity metal plated panel instead of painted one for easy grounding and better noise tolerance.
¢ Use zinc plated retention screws of M3 for installing slave module., ~58-
Page 66
(2) When using fixing screws ¢ Use 2 galvanized screws of M3-10. * Tighten securely to a torque of 5 kgfecm or less.
Hf installation procedure
2-M3 ta \ @ Drill M3 tap holes in the control panel for installation 7 as shown at left. | 2 mB iL @) Tighten fixing screws (M3-10, 2 pieces) with a phillips screwdriver, and fix I/O link slave module.
180
(3) When using DIN rail
* The slave module can be attached to or detached from the 35 mm wide DIN rail instantly. ¢ Not applicable to DIN rail with the width exceeding or less than 35 mm.
(Unit: mm), _ - A | P | 4
=<, =< - - rT w - - re 5 oO a DIN rail lever
I/O link slave module (The back side)
* Using DIN rail lever, fix securely to DIN rail.
-59-
Page 67
Bf Installation procedure
@ Match the claw of the back side of the I/O link Claw slave module with DIN rail.
@) Push the lower side of the I/O link slave / ¥ = module to DIN rail.
= (C=)
DIN rail lever
When installing in the vertical direction, use a bracket to prevent from dropping off due to vibration.
Bracket
@ Dismounting procedure
@ Lower the groove of DIN rail lever at the back side of I/O link slave module with siot screwdriver, and lift the entire I/O link slave module, then it is detached from the DIN rail., ~60
Page 68
[4] Wiring method
(1) Wiring cautions * Use crimp-style terminals for connections to the limit switch, solenoid valve, and other external devices. Tightening tirque: 10 kgfecm max.
@)
M3.5X7 - 72 L Self lock-up screw
M3.5 x7 Self lockup screw
(2) Connecting communication cables
2-wire type
Control panel chassis
For wiring to L,, L,, and SHIELD terminals, use our recommended twisted pair wire with shield. For shielding of the shield wire, relay with a twisted air of about 0.5 mm? outside, and then wiring to the terminal block will be easier.
Keep the wire coming out of the shield as short as possible (30 mm or less), and connect to SHIELD terminal.
To not connect signal cables to terminals other than the L,, L,, or SHIELD terminals. Ground the I/O link slave module’s FG terminal (frame ground terminal) with a twisted cable of about 0.5 mm? using the SHIELD terminal. Attach a ground wire no longer than 300 mm between the FG terminal and the control panel chassis., ~61-
Page 69
(3) Power supply wiring ¢ Twist DC power input lines with each other. As DC input power supply uses an insulation type DC/DC converter inside the module, it is also applicable as power for input signal or output signal. CY (Control panel chassis) Tv a” 5 Class-3 grounding SQoeo on ZW-162N [| 24V a5V | ( = = DC power > Sika WOOF, a DC/DC torte 4 i E} 1 $ 7 z 1 i i 3 i 6 T 7 a Tr 4 3 I 5 I z I 1 A 3 I EA r 7 converter oo 8 6000 0 ee oo0o0Uum0ddlUcUOUcOlUcOlUG 24 Vv | = 0 V 5600005550500550566 (0 V) fol GOOGOOOGHGSGGGOSSSS | =) DC power ‘|F
24V =
Note 1| Incase of sharing this power with load driving power for DC input/output signal, note wirin g and noise prevention method.
Be sure that the I/O link slave module's FG terminal is grounded through the control panel. It is also used as ground for the DC/DC converter.
When DC power is supplied to I/O link slave module positioned away from it, provide fuse elements for the DC power supply and each module respectively. Be careful for voltage drop due to long distance wiring. Slave O O
Fuse *) O
Fuse O
<Reference> Power voltage and line resistance Line resistance
DC power voltage (V,) = 24V + slave module current x line resistance x 2 x wire length (km) | Nominal sectional area 0.3 mm‘.....61.9 ohmv/km
Line resistance Module AA 0.5 mm?.......37.1 ohm/km, _ - - Iv Current 2a] 0.75 mm?...... 24.8 ohm/km IMA, 62-