The text of a manual · part 3 of 18
I/O link master module JW-31LMH Instruction Manual, pages 8 to 10
Pages 8 to 10 of 123: §1 Preface; §2 Safety precautions
The original document is the PDF (3.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Sharp JW-31LMH
Page 8
§1 Preface
1-1 I/O link
I/O link is designed with the aim of minimizing input and output wirings of PCs. It supersedes all wirings from PC I/O slots to input devices and loads with single communication cable. It is applied installing “I/O link master module: JW-31LMH” (hereafter called “master module”) at I/O slot of the PC and “I/O link input module and I/O link output module” (hereafter called “slave module”) at input devices and load sides.
1-2 Features
[1]
[2]
[3]
[4]
[5]
[6]
High data transfer speed
The JW-31LMH transfer speed is 345.6 k bits/sec., which is twice the conventional JW-31LM model. This allows high speed communications with the ZW-324NH/322SH/322MH lOlink slave modules. By setting the switches, the JW-31LMH can also be connected to the following conventional I/O link slave modules: ZW-82N/82S, ZW-161N/162N/161S/162S/164S/162M. In this case, the transfer speed will be 172.8 k bits/sec.
Up to 32 slave modules can be connected to one master module
The I/O link slave modules and LCD terminals can be installed in discrete layout by a maximum of 32 units, in a range of total distance of 1 km, using shielded twisted pair wires.
(However, number of I/O link points is 504 points at maximum.)
Up to 504 points of I/O link point available
Max. 504 points of I/O link is usable per master module. (In cases where 8-point modules are used, max. number of points becomes 256.) Installation of multiple master module in a PC makes another increase of I/O link points.
(Ex. JW-13BU) JW-31LMH
No. of I/O link points
TI @ a @ cy @
Max. 504 points P Control module
Po Io]
(JW-70CUH), - ~
Power supply module
Io]
Capable data exchange approx. 13.1 ms
The JW-31LMH enables data to be exchanged between a master module and all connected slave modules in approximately 13.1 ms (assuming that 504 I/O link points are connected and the data transfer speed is 345.6 k bits/sec.). As for details, see page 31 of this manual.
Error station display function
When abnormality occurs at a slave station, the master module displays number of this siave station with LEDs, which shortens recovery from trouble.
Output function alternation at error communication Output at error communication of each slave station can be set either “reset” or “hold” individually.
Page 9
[7] Shorten wiring work and wiring change work time
As I/O link slave module can be installed nearby input devices and loading equipment, manufacturers of machines to be controlled by our PC can work input and output wiring at their factories. Only communication cable necessary be wired at field.
A ole ele em Mmmm MyM [Wink Oink syeye ye 5 rs A | | input module output module
3 | Switch ! Load |
SER EEE EE EES a, <a sd
RS485
|____ Cable total extension length: 1km y,
[8] 1/O link master module can be used inserting in the PC slots for below W series models.
JW-50CU, JW-50CUH Applicable PC JW-70CU, JW-70CUH JW-100CU, JW-100CUH
[9] Selectable communication mode from 3 types
In accordance with system contents, three types of communication operation are selectable. See page 19 for details.
Mode 1 Stop communication
Confirm recovery automatically Mode 2
Continue communication Mode 3 Confirm recovery manually
Page 10
§2 Safety precautions
Be aware of the following points prior to use and store the master and slave modules.
1)
2)
6)
7)
8)
9)
Avoid keeping the JW-31LMH in the following conditions: ¢ Direct sunlight. ¢ Corrosive and flammable gases.
Excessive static electricity may be generated on the human body in extremely dry conditions. Prior to touching the master module or slave module, discharge static electricity by touching grounded metals.
Be sure to tighten retention screws of the master module or slave module.
Use dry and soft cloths for cleaning. Organic solvents such as alcohol, paint thinner, and wet cloths may cause deformation or color change.
The outside cases of the master module or slave module have ventilation hole so as to prevent the inside temperature from rising. Do not block this hole or prevent ventilation.
When the master module or slave module is out of order or in abnormal condition (overheat, emitting a bad smell or smoking), stop operation and contact our dealer or service center.
Cautions at required transfer time
Input signals for short operating time output and pulse shaped short input signals may not be input or output in some required transfer time. In order to secure safety of equipment, signals to input should be directly input to the PC.
(As for calculation of required transfer time, see page 33 of this manuai.)
Be sure to set dip switches of the master module and slave modules at power “OFF.” When these switches are changed at power “ON,” it may cause malfunction.
The master module is special I/O module for JW series. It cannot, however, shorten data exchange time between slave stations even using application instruction F-81.