Page 79
3) Countermeasure for leakage current on input device In the following device, there is also leakage current at OFF. If the leakage current is higher than the OFF level of the input module, the input module may not turn OFF, or noise margin at OFF state may drop. a. Limit switch with LED Reference
Calculation of leakage current i, Input module | || 4 Rs + Rin -_ | Rin V: Power supply voltage “Leakage iL Ve: Voltage drop in the forward direction of LED current v, Rs: Current limit resistance y com| Rin: Input impedance of input module b. Limit switch with neon lamp (the neon lamp is connected in parallel with the contact point.) Input module :, , i iN Lo [| Rin Leakage iL Current 7
© com[ c. Proximity and photo switches of AC two lines system In the AC two lines system, even at OFF there is leakage current from current consumption of the internal circuit, and this might prevent the input module from falling in the OFF state. This is nominated as “leakage current” in the specifications of photo switches etc. Make sure that this value is less than the OFF level of the input module.
ao Leakage | Current d. Built-in triac, thyristor and contact point output of surge killers Some device has CR device as a surge killer for the purpose of avoiding the check mistakes of triac and thyristor, and the leakage current of this CR may prevent the input module from falling in the OFF state. In such a case, the best remedy is to remove the CR. if this is not possible, use the C value of the CR of less than 0.033 LF for 100 VAC; and that of iess than 0.015 uF, for 200 VAC.
Input module Reference
Calculation of leakage current i, a Rin 7 V FA " 2n fc Lt a4 a V: Power supply voltage f: Power frequency (50/60Hz)
C: Capacitor
4-51
Page 80
Countermeasure : Connection of bleeder resistance As a countermeasure, a bleeder resistance can be inserted in the input side of the input modute as shown below.
resistance |
Input module Input . IN | power supply | Input device with H . leakage current | Bleeder R | Rin
Choose the bleeder resistance value R to meet the following conditions:
. { RinXR iL= ae) <Vin OFF
Composite impedance of the bleeder resistance and the input impedance
Vin o-FX Rin iv: Current leakage of the input device A (eee OFF X05 Vinore: Input of the input module OFF level voltage Margin Rin: Input impedance of the input module
V: Input power supply voltage In this case, the rating electric power W is,
2 W> _ x3. Margin
[Example] In case that the ZW-32NT is used as an input module at the input power supply voitage of 24 V, and that the leakage current of the input device is 5 mA, iL=5mA Vinorr =6V Rin = 2.6 k ohm V=24V 6X26 _ R< “26X5 - 6_ X0.5=1.14k ohm If Ris 1 k ohm, ws, 2* X 3=1.73W 1x<108 7 W will be 2 W.
4-52
Page 81
4) Notes for long-distance wiring and by-pass wiring In the AC input module, when the cables to external device are very long or wiring along with power lines is made, the input module might be turned ON in spite of the OFF command in the input device, due to leakage current and inducement by floating capacity among cables.
Input module IN ] ae a | ' “ comL___.
Power line, etc.
Countermeasure 1: Connect a bleeder resistance and a CR surge killer in parallel with the input module to reduce the composite impedance of the input module. Input module
The smaller the R value, the more effective. However, when R becomes small, power consumption i) increases. Therefore, note the R's watt value.
Input module fal C: 0.033 to 0.33LF te (Pressure resistance of over 250 VAC) R: 47 to 120 ohm
Countermeasure 2: Change the input power supply to DC (use DC input module}. In general, the direct current signals are little affected by floating capacity and inducement.
Countermeasure 3: Close circuit by making use of the b contact. When the b contact is used to make a close circuit at OFF, very little induced voltage ts generated.
Input modute
Note: Do not wire the input signal line near and in parallel with power lines of a motor and an inverter.
4-53
Page 82
5) Surge current of the AC input module
There is surge current in the AC input module, when turning ON the input.
The surge current of the AC input module is determined by constants (R, C) of the input circuit inside the module, power supply voltage at ON input, phase, power supply current capacity and wiring impedance. The surge current stated in the AC input module specifications is the worst value for the case of the ON input at the maximum impressed voltage and at the peak phase.
If, in certain input device, contact points are affected (adhered etc.) by the surge current, the surge current should be reduced by connecting a limit resistance Rs outside the module as shown below.
AC input module
Limit _ _ resistance OFF - >ON Rs R C comme, My ? {| g
Surge current |
The following limit resistances Rs can be connected outside the module: For 100 VAC input module, less than 2 k ohm (over 2 W rate electricity) For 200 VAC input module, less than 4 k ohm (over 2 W rate electricity)
Reference
* When a limit resistance of 2 k ohm (or 4 k ohm) is connected for the 100 VAC (or 200 VAC} input module, the surge current becomes jess than 80 mA at the peak ON.
Note: If a resistance bigger than the above value is connected, the input ON/OFF levels and the response times cannot be guaranteed.
Module name. Surge current specifications JW-11N Max. 480mA (0.2ms or less, 182 VAC peak ON) JW-13N Max. 500mA (0.2ms or less, 264 VAC peak ON) JW-31N Max. 480mA (0.2ms or less, 132 VAC peak ON) ZW-16N1 Max. 365mA (0.4ms or less, 121 VAC peak ON) ZW-16N3 Max. 342mA (0.4ms or less, 242 VAC peak ON) ZW-32N1 Max. 440mA (0.2ms or less, 121 VAC peak ON)
4-54
Page 83
6) Countermeasure in case of connection of induced load to input signal If the induced load is connected to the input signal, in order to absorb the noise, connect a surge killer near the load for the AC circuit; and a diode, for the DC circuit, as shown below. For AC power supply, eo Surge killer: R, C, /\VW\VH FF °° C: 0.033 to 0.33 UF
: (Resistance voltage of over 250 VAC)
- | R: 47 to 120 ohm COML_.._ For DC power supply DC input module Diode: <q 3 Inf | _ . Peak inverse voltage (Vam) should be more than 3 iE ' times bigger than the load voltage, and the average | ~~ | rectification current should be bigger than load CoML current.
4-55
Page 84
[5] Precautions for operating the output module
1) Protection from output short circuit
In case of a short circuit of the load connected to an output terminal, output devices and print board may be burned. Be sure to insert a protection fuse in the output.
Some modules have a built-in fuse per common line for protection of the module from heating and burning due to excessive current. It is not intended, however, for protection of the output devices and load from excessive current; therefore, insert fuse for each line outside the module. This is also advisable from maintenance point of view.
Power supply load
Output module
2) Countermeasure to surge current of lamp load At turning ON an incandescent lamp, there is surge current 10 to 20 times bigger than normal current for several 10ms. For reduction of the surge current, insert either a bleeder resistance or an electric current limit resistance.
a. To insert a bleeder resistance axe
NA oN
Bleeder resistance aS Output module
During the OFF state of the output module, keep supplying dark current so smali as to turn ON the lamp dimly.
b. To insert an electric current limit resistance
Current limit resistance module
4-56
This limits the current within a value determined by the value of the current limit resistance. When the resistance value is high, the voltage on the lamp decreases. Determine the resistance value by the brightness needed when turning ON the lamp.
Page 85
3) Countermeasure to surge voltage at opening/closing induced load
Some load generates surge voltage of several thousands voit when an induced load is opened or closed its circuit. All output module except the relay output module have a circuit to absorb surge within module. However, when the wiring to the load is long, its effectiveness is reduced and a surge countermeasure is required in the load side as well. In case of the relay output module without surge absorption circuit, surge countermeasure outside the module is indispensable in case the load generates high voltage. (This surge voltage countermeasure can extend the life time of the contact points of the relay.)
Surge voltage countermeasure
L load na ’ Surge killer 9 Relay output module ° L load } TO F Diode | Relay contact point output module co] L load ~ OO = Transistor output module, FET output module a on i Triac output module surge killer
(In case of contact ints in series line)
R Cc CR surge killer: }=- - - ->/A\A\/4-- C: 0.033 to 0.33 uF (Pressure resistance of over 250 VAC) R: 47 to 120 ohm
Example of CR surge killer
For 100 VAC 953M2503 10411(0.1 p + 120 ohm) (made by Matsuo Electric Co., Ltd.) For 200 VAC 953M5003 33311(0.033 Wu + 120 ohm) (made by Matsuo Electric Co.,Ltd.)
Diode:, >t - Peak inverse voltage (Vrm) is more than three times of the load voltage. Average rectified current (lo) is more than load current.
in case of AC load, a varistor can be used in place of the CR surge killer for the same effect. (Installation of both of the CR surge killer and the varistor increases the effect.)
For 85 to 132 VAC | TNR12G221K (made by Marcon Co., Lid.), NV220D14 (made by NEC) For 170 to 264 VAC | TNR12G431K (made by Marcon Co., Ltd.), NV430D14 (made by NEC)
4-57
Page 86
Note 1: Avoid the use of a capacitor only as an arc killer, as shown below:
Though a capacitor is very effective for the Though a arc deletion at capacitor is very shut-off. But at the effective for the opening of the
2 arc deletion at r circuit of a contact a shut-off. But B - point, electricity is ® 7 charged current to g accumulated at the & the capacitormay | @ capacitor. melt the contact Therefore, the point at turning ON short circuit current a contact point. of the capacitor may melt the contact point at turning ON the contact.
Note 2: DC output module uses a zener diode as a surge absorber within the module. In case of using an induced load of large load current such as solenoid valves, note the followings:
Output module _ ‘ > W128 4 » r COMO x JW-32S Zener diode JW-35S rower (e ZW-32S2TD
D: Diode for counter surge voltage absorption at OFF
¢ When the load current is an induced load of over 0.3 A(0.8A for JW-12S), use the module with the open/close frequency at less than 30 times/min. (1 sec. ON/1 sec. OFF or so).
JW-125 0.5A
JW-32S
JW-35S 0.3A ZW-32S2TD
¢ When more frequent opening/closing, a surge countermeasure for counter voltage absorption is needed in the load side. When the load current is an induced load of over 0.5 A(0.8A for JW- 12S), a surge countermeasure for counter surge voltage absorption is indispensable in the load side. JW-12S 0.8A JW-32S JW-35S 0.5A ZW-32S2TD
4-58
Page 87
¢ The output transistors of JW-32SC and JW-62SC may turn ON for a moment when the contact point (A) turn OFF to ON under the connection with the load in series, even if the output data from PC is OFF. Therefore, the load which response under 1ms may turn ON for a moment. To protect the abnormal processing, connect 100k ohms resistor between the contact point (A).
JW-32S8C, JW-62SC A) Oo Contact ON | | point (A) 100 kohms [ Load | Current | Output transistor _ 1 4] Approx.1ms DC power supply
4-59
Page 88
4) Load which can be driven by the AC output module The AC output module with SSR as an output device can drive directly the loads of electro-magnetic switches, solenoid valves and lamps. In such cases note the surge current at turning ON (from OFF to ON) and the maintenance current during the maintenance state (ON state). Concretely, use the module within the following range:
100 ms 10 mA 2A (1 point), 4A(8 points comment)
IWiI3S _| 45 to. 264 VAC JW-33S 100 ms 10mA 1A (1 point), 4A(16 points comment) ZW-8S1 100 ms 30 mA 2A (1 point), 5A(4 points comment)
ZW-32S1T 100 ms 10 mA 0.6A (1 point), 2.4A(8 points comment ZW-16S3 15 to 242 VAC 100 ms - 2A (1 point), 5A(8 points comment)
6A ( ) 6A ( ) 8A ( ) ZW-16S1 15 to 121 VAC 8A (100 ms} 30 mA 2A (1 point), 4A(8 points comment) 6A ( ) 8A ( )
The ZW-32S1T has two versions with different minimum operating currents :
OUT PUT AC100V(N): 15A(50 ms) or less
OUT PUT AC100V : 50 mA (former version, not produced after Feb.1988.)
*When the AC output module drives the load, note the surge current at turning ON and the holding current during the maintenance state. Keep the surge current below the repeated allowed surge current at the turning ON; and keep the maintenance current, over the minimum action current and below the maximum rated load current during the maintenance state.
*The repeated allowable surge current is a value in case of the pulse width below 100 ms and repeated switching frequency below 20 times/minute. When, in case of the load of a motor, the pulse width of the surge current is large and that the switching frequency is high, keep the ON time of 1 pulse below 50%.
(When the repeated surge current is below the maximum rated load current, there is no limit in the pulse width or in the switching frequency.)
eWhen many loads with big surge current are driven within a same common line circuit, make the number of points which turn from OFF to ON at the same time minimum. When a strong surge current goes through a built-in fuse in a common unit, the built-in fuse may be damaged or fused. The number of the surge current per common which can be turned from OFF to ON at the same time is determined by a fusing property of the built-in fuse as follows (as a guidance): Below 15A (50ms)
Below 10A (50ms)
The numbers in (__) are pulse widths.
* For a light load of the holding current which is smaller than the minimum action current, some characteristics of load may prevent turning OFF. in such a case, connect a bieeder resistance in parallel with the load to increase the maintenance current up to the minimum action current or more.
Some electro-magnetic switches of the pulse-driven cannot be turned OFF even if the holding current is over the minimum action current. In such a case, also, connect a bleeder resistance in parallel with the load. (Select a value of the bleeder resistance so that it can allow the minimum action current by itself.) Bleeder resistance
R ()
SS Power supply (V) © Load Output module
4-60