Programmable controller New Satellite JW, JW50H/70H/100H User's Manual/Hardware version: Chapter4. Name and function of each part, pages 109 to 118

Pages 109 to 118 of 254, from Programmable controller New Satellite JW, JW50H/70H/100H User's Manual/Hardware version

The original document is the PDF (8.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sharp ZW-16S2, Sharp ZW-32N2T and Sharp ZW-32S4T

Page 109 read from a scan by OCR; it may hold reading errors

Power supply voltage selector switch . This switch allows you to select the primary supply voltage to the expansion power supply module as 100 VAC or 200 VAC. The default selection is 100 VAC.

(9) Locking plate retention screw, Switch locking plate These are used to lock the voltage selector switch into the selected position to prevent inadvertent selection of the wrong voltage. (1) Rack panel retention screws

Use these screws to secure the expansion power supply module to the expansion rack panel frame (ZW-108ZB, etc.)

[2] Outline dimension drawings nd DB i t iy

3 1

“

|

1

Hy

| i

65.5 120 | 130

|

(Inciude expansion rack panel)

(Unit: mm}

4-81

Page 110 read from a scan by OCR; it may hold reading errors

[3] Specifications

Applicable rack | 7w_1987B/Zw-104ZB/ZW-102ZB panel 100 VAC+10%(85 to 110 VAC) F -15% Input voltage Primary supply voltage 200 VAC+10%(170 to 220 VAC) -15%

Power drawn | Max. 40 watts (at 7A output current) | Max. 100 watts (at 12A output current) Surge current Max. 20 A, 10 ms(at 220 VAC input, rated load)

Leakage current} Max. 1 mA at 220 VAC input

Output voltage | 5.1 VDC £0.05 VDC

Output current | 0 to 7A 0 to 12A Output rise time | 20 to 200 ms at rated load

Output hold time | Min. 15ms at rated load

Overcurrent protection Voltage-drop, auto-recovery type (7.7 to 8.4A)

Protection Voltage-limitin , t circuits Overvoltage protection germiting, auto-recovery type (6.0 to 6.75A) Normal blow miniature fuse with 2A rating Protection AC power input (front mounting) fuses Normal blow miniature fuse with 1A ratin g Halt output (front mounting) Function Triac output, shut OFF if the contol module stops functioning Halt output Load voltage 85 to 240 VAC Load current 1A Leakage current 3 mA max. insulation. Min. 10M ohms when measured with a 500 VDC megohmmeter Stength | Withstands 1500 VAC for 1 minute.

Terminal biock | For primary input and halt output connections

Outer dimensions] 65.5(W)X250(H) X 130(D) Weight 1.5 kg Accessories Normal blow miniature fuse with 1A and 2A ratings: 1 each

Primary supply voltage is selectable with a front panel switch. Note: The ZW-100PU1/100PU2 power supply module cannot be installed in a basic rack panel or in the ZW-508ZB expansion rack panel.

4-82

Page 111 read from a scan by OCR; it may hold reading errors

[4] Primary supply voltage switching The primary supply voltage to the ZW-100PU1/100PU2 expansion power supply modules is selectable as 100 VAC or 200 VAC using a front panel switch. The default selection is 100 VAC. If you wish to operate the module on 200 VAC, change the voltage selection in the following sequence:

® 100 VAC @ setting condition

BD Power voltage

@

. 200 VAC Lock plate retention screw setting condition ® FA] (100 VAC setting condition) @ Power voltage

1) Remove the locking plate retention screw.

2) Remove the switch locking plate.

3) Set the voltage selector switch to 200 VAC.

4) Replace the switch tocking plate over the switch, this time with its reverse side facing forward so that it locks the switch tab into the 200 VAC position.

5) Secure the plate with the retention screw.

Noie 1: Never supply 200 VAC to the expansion power supply module with the supply voltage selection left at 100 VAC, or the module will sustain permanent damage.

Note 2: The tolerance of primary supply voltage for the expansion power supply module is not identical to that for the ZW-1PU power supply module. Take care to avoid using the expansion power supply module outside the supply voltage tolerance specified.

Note 3: The following schematic shows the ZW-100PU1/100PU2's halt output circuit:

1A

4-83

Page 112 read from a scan by OCR; it may hold reading errors

4-9 JW-1EA/2EA I/O bus expansion adapter [1] Outline and features

The JW-1EA/2EA I/O bus expansion adapter (hereafter called the JW-1EA/2EA) are used for bus interconnection among racks which contain JW-series I/O modules. The JW-1EA is used solely in the rack panel where the control module is installed, whereas the JW-2EA is used in all rack panels other than the first rack panel.

Containing high-speed line drivers and receivers, the JW-1EA/2EA allow reliable transmission over longer distance than that available with a conventional expansion signal cable:

1) The allowable total cable length from the first to the last rack panel in a daisy chain is 50 meters

(160 feet). 1EA 2EA 2EA 2EA 2EA ; Total cabl length: 50m |

2) Remote programming capability allows you to program system operations, change an existing program, or monitor a running program, using a support tool attached to a rack panel which is up to 50m({in cable length) away from the rack panel where the control module is installed.

1EA 2EA 2EA eee Fel jee Support tool

3) /O module installed in the farthest rack have processing speeds equivalent to those in the control rack panel. Communication time delay inherent in conventional remote I/O is eliminated.

4) Power supply modules' halt output signal lines need not be connected in a daisy chain. lf any of the power supply modules fail, the PC automatically stops running and the halt output signal of all the power supply modules are simultaneously activated (contact opened).

Power supply module |_| 1EA Power supply module |_ | 2EA

Halt output tine

5) One control module can control up to eight rack panels including the one where the control module is installed.

1EA 2EA _2EA 2EA 2EA a4 ¥ ¥ | cs

. P eenet een

Up to 8 racks

4-84

Page 113 read from a scan by OCR; it may hold reading errors

{When the I/O bus expansion adapter is used] In the following cases, an I/O bus expansion adapter is necessary

Three or more rack panels | Although the quantity of connected} The length of I/O expansion are connected. rack panels are two,the expansion | cable exceeds 1m.

rack panel another power supply | (In this case, the expansion module.(The total current consum- | rack panel needs another ption of modules exceeds the power supply module.) capacity of the power supply @2EA module, the expansion rack panel

P "| needs power supply module.) 2EA << U N Power supply module 4 <EA <2EA Min. tm_, PIC - P}C | P}C | UU lA UU <lEA UU <tEA

[Some notes on bus extension cabling]

* The total length of the I/O expansion cables used should not exceed 50m.(50m in one direction, 100m tn both direction)

* Do not install 1/O expansion cables in ducts or conduits where cabling to 1/O devices or power cables are installed.

¢ Plug each I/O expansion cable plug firmly into its mating receptacle. Loose connections may cause an I/O error, causing the PC to stop running.

* Be sure to install the termination connector the JW-1EA/2EA at both ends of the 1/O bus. Also keep the connector cover installed on every unused connector.

¢ Do not apply a tensile stress of more than 2kg to the I/O expansion cables.

* When using the I/O expansion cable over a distance greater than 1m, be sure to use an expansion power supply module in the expansion rack panel.

* The JW-1EA is supplied with two termination connector. Take care not to lose them while unpacking.

4-85

Page 114 read from a scan by OCR; it may hold reading errors

{2] Name and function of each part

JW-1EA JW-2EA @®Connector cover @)Module retention screw = as @RUN indicator . RUN indicator]. I/O expansion | @VO expansion ~ connector | | connector a - connector

)Support tool interface |J= - p

4) Rating plate pePh

7

VO expansion

NO expansion| connector connector | ©)Device number selector switch, - - ] inati @)Termination connector @ Termination connector slo @Termination connector slot

@ Module retention screw (two sets) Use these screw to secure the module to the rack panel frame.

Q

°2 RUN indicator

This light remains on while the PC is normally running; it goes O RUN off if an error has occurred or the PC has entered the program

| |

@ VO expansion connectors Use these connectors to establish I/O bus connections among expansion rack panels.

mode.

(4 Rating plate

(6) Support tool interface connector | Connect your support tool (hand-held programmer, etc.) to this connector.

(6) Rack panel number selector switch

Use this switch to set the rack panel number (1 to 7) which the module is connected. Select rack panel No.0 for the rack panel where the control module is installed (default setting is No.1), and allocate ascending numbers to the rest of the rack panels from near to far. Avoid allocation of the number to more than one rack panel.

Rack No.

@) Termination connector Install this connector on the JW-1EA/2EA at both ends of the I/O bus. The JW-1EA comes with two termination connector (for more details, see page 4-89).

4-86

Page 115 read from a scan by OCR; it may hold reading errors

@ Connector cover

Keep this cover installed on every unused I/O connector. The JW-1EA is supplied with two connector covers.

) Termination connector slot

[3] How to use (1) Installation

Install the JW-1EA/2EA in the I/O expansion connector located on the right-hand side of the JW- 4BU/6BU/8BU/13BU rack panel as shown:

/O expansion connector

Rack panel (JW-4BU/6BU/8BU/13BU)

Use the JW-1EA in the rack panel (where the control module is installed); use the JW-2EA in expansion rack panels.

Note: Allow a space of more than 50mm (2 in.) on the right-hand side of the JW-1EA/2EA to enable insertion/removal of the termination connector.

(2) Bus connections

The are two possible ways of bus connection. Choose according to the operating conditions and purpose. Method | Description ne

; Use this format for a single 1EA Jp} 2ea

Using one WO exransion | Aen total bustength | [C] - of max. 50m. j - _29M__j~ j 2EA IW]1EA 2QEA

Using one VO expansion buses with a rolal bus Fength j 4 | nector on the JW-1EA I con of max. 50m each. 20m 50m

1) Method using either I/O expansion connector on the JW-1EA either of the two I/O expansion Connectors (lO-1 and IO-2) on the JW-1EA may be used for I/O bus extension, as shown below:

vO-1 ~ JW-2EA |= JW-2EA | JW-2EA | Termination connector) 10-2(Connector cover installation) Termination connector,” |< Total cable length 50m max. (for up to 8 rack panels} >|

*For the first (JW-1EA) and last (JW-2EA) adapters, install bus termination connector in their termination plug slots and connector covers over the IO-2 connectors.

*Set a range 1 to 7 for a rack panel number. Avoid definition of the same device number for more than one rack panel. Numbers 0, 8, or 9 are usable for device numbers JW-2EA.

Note: No restriction exists regarding whether you use IO-1 or 10-2 connector on each adapter. Use whichever is more convenient.

4-87

Page 116 read from a scan by OCR; it may hold reading errors

2) Method using either I/O expansion connectors on the JW-1EA Both of the I/O expansion connectors (IO-1 and IO-2) on the JW-1EA may be used for I/O bus extension, as shown below:

|. Total cable length 50m max. at VO-1 owica IF UL Li 1] ~ JW-2EA Jw-2EA [5 JW-2EA |'

|»

[

CI YO-2 Termination connector_|

(} Connector covers are installed.

Ca om t=

LI

Total cable length 50m max. |

WARE A L Jw-2ea_ |b _JW-2EA ;

C7)

Termination connector |

“The maximum total cable length allowable for each I/O expansion bus is 50m.

*Install a bus termination plug and connector cover on the last adaptor on each bus.

*The maximum total number of rack panels are attached to JW-1EA module's !O-1 connector, up to 3 rack panels may be attached to its 10-2 connector.

*Set a range 1 io 7 for a rack panel number. Avoid definition of the same device number for more than one rack panel. Numbers 0, 8, or 9 are usable for device numbers JW-2EA.

3) I/O expansion cables The following I/O expansion cables are optionally available for the JW-1EA/2EA:

. ae Specifications _ ees |, JW-O5EC 50 cm long (50 conductor) | JW-1EC 1m long (50 conductor) JW-3EC 3 m long (50 conductor) JW-10EC 10 m long (50 conductor) JW-30EC 30 m long (50 conductor) JW-50EC 50 m long (50 conductor) 35mm(minimum) i & y JW-1EA JUW-2EA nn ; ?15mn ft Lg y Shield connector leads

VO expansion cable

Secure the shield conductor leads to the rack panel frame using the module retention screws. ‘

Note: Clamp the 1/O expansion cable to relieve tensile stress on their connections.

4-88

Page 117 read from a scan by OCR; it may hold reading errors

(3) Setting the rack panel number selector switch The JW-2EA has a rotary-type rack panel number selector switch. Set a unique rack panel number for each rack panel using this switch:

Screwdriver oN S. ert <5 a)

Setting switch

@

1to7 RACK NO.

Applicable screwdriver

Note : Set a unique rack panel number for each rack panel. Numbers 0, 8, or 9 are not usable for rack panel numbers with the JW-2EA.

(4) Installing a termination connector The I/O bus extended with the JW-1EA and JW-2EA must be terminated with a termination connector at each end.

1) For a single I/O expansion connector JW-1EA | [ JW-2EA | JW-2EA |

Termination connecton\ Termination a

2) For double !/O expansion connector

JW-1EA Ul JW-2EA |' JW-2EA |

Termination connector ce aaa

UJ

JW-2EA [> JW-2EA |

Termination connector

(Reference) Reason needing for termination connector 1. Termination connector must be used at both ends of the 1/O bus to prevent signal reflection pulse from the ends of the bus. Otherwise reflection pulse will interfere with the forward signal and cause data errors. Installing a termination connector terminates the end of the bus though a resistor.

2. If a termination connector is installed on an intermediate rack, the resulting reflection and/or attenuation will cause data errors.

4-89

Page 118 read from a scan by OCR; it may hold reading errors

The termination connector is installed in the slot provided in the lower section of the JW-1EA/2EA module, as shown below.

J Note: The termination connector will only fit oriented one way. Do not forcibly insert it with the wrong orientation, as this will damage the connector and/or receptacle.

(5) Connecting a support tool The JW-2EA has a support tool interface connector. When attached to this connector, a support tool can be used in much the same ways as if it was attached to the control module.

{Connectable support tools]

| Hand-held programmer (JW-10PG/11PG/12PG/13PG/14PG)

+ Programmer (ZW-101PG1) Note 1

Multi-purpose progammer (JW-30PG, JW-32PG, JW-40PG, JW-50PG) | Ladder processor Il (Z-100LP2, Z-100LP2F) Note 1 .

Note 1: Each support tool can be used within the range of its capabilities.

Note 2: Only one support tool can be used with a-system at one time. If a support tool is already attached to the control module or any other JW-2EA module in a system, do not attach another to the same system. (Refer to page 11-3.)

4-90