For the Sharp ZW-16S2, Sharp ZW-32N2T and Sharp ZW-32S4T

Page 136 read from a scan by OCR; it may hold reading errors

Precautions in installation

The JW50H/70H/100H is not designed for dust and water proof construction. Therefore, install JW50H/70H/100H in an enclosed panel. Avoid keeping the JW50H/70H/100H in the following conditions: 1. Ambient temperature extremes outside the range of 0 to 55 °C The relative humidity exceeding the range of 35 to 90% Sudden temperature changes which may cause condensation. Corrosive and flammable gases. Water, oil and organic solvents dripping positions. Dusts, iron and salty conditions. A box in which high voltage device is installed. 8. Strong vibration and shock may usually occur. Install on a good conductivity metal plated panel instead of painted one for easy grounding and better noise tolerance. Use zinc plated retention screws of M5 for installing JW30H.

NOMA ON

Calculation the average consumption electric power (heating value) of JW30H. Determine the average power consumption of the entire machine in the following formula, and calculate the temperature rise in the panel. 1) Power supply module Wow = _ x (Isv x 5)(W) Isv: Current consumption of 5 VDC circuit of respective module 2) Total consumption electric power of respective module (S VDC) Wov = Isv x 5(W) 3) Average consumption electric power of total 24 VDC power supply of output module (power consumption for simultaneous ON points) Woav = l2av x 24(W) 4) Average power consumption by output port drop voltage of output module (power consumption for simultaneous ON points} Wour = lour x Vdrop x No. of output points x Simultaneous ON rate(W) lour: Output current (current of use){A) Vdrop: Drop voltage of respective output module(V) 5) Input port average power consumption of input module (power consumption for simultaneous ON points) ¢ In case of DC input Win = lin x E x No. of input points x Simultaneous ON rate(W) ¢ In case of AC input Win = 0.1 x lin x E x No. of input points x Simultaneous ON rate(W) lin = Input current (Rms value in the case of AC)(A) E = Input voltage (voltage of use)(V) 6) Consumption electric power of special function module Ws = Isv x 5 + leav x 24 (W)

The total of the power consumptions calculated in each module is the power consumption of the entire machine. From this entire power consumption (W}), calculate the heat generation and temperature rise in the panel.

5-1

Page 137 read from a scan by OCR; it may hold reading errors

5-2. Installation procedures

The JW50/70/100, JW50H/70H/100H programmable controller usually comprises many modules. This section describes the installation procedures, from module unpacking through rack panel mounting in a cabinet.

{ Example of basic system configuration ]

| | Module n ee [stat | Mog 1 | Rack panel JW-4BU/6BU/8BU/13BU | 2 | Power supply module | ZW-1PU/2PU 7” JW-50CU/70CU/100CU Check quantities of 3} Contol module packed items JW-50CUH/70CUH/100CUH 4} Memory module ZW-1MA/2MA/3MA/4MA y JW-1MAH/2MAH/3MAH/4MAH | Unpack modules | 5 | Option cable ZW-2CC/ZW-4CC/ZW-6CC 6 | Option module ZW-10CM/20CM/30CM Install memory module JW-10CM/20CM, etc. in control module. 7 | VO module JW-32N, etc. (Note 1) | Install contro! module on Memory module rack panel. TT f Install rack panels in a HHL cabinet. : _ Control module Install option module. | TG 4 TSE l

‘| Install power supply g module. ‘Option module

[install /O module. |

Power supply module

. /O module -

Install option cable. | | END | (Note 2)

iT:

arate ARP {

\ Cable for option

Note 1: The JW-50CU, JW-50CUH doesn't require memory module installation as it already contains one as a standard feature.

Note 2: Not needed for a stand-alone system.

Note 3: For the details on how to install each module, see the descriptions in later sections.

5-2

Page 138 read from a scan by OCR; it may hold reading errors

5-3 Mounting rack panels inside a cabinet

Pas

AUTHORS EAS il

Ea, p hanuuduliuanue ducted sl e

Wivuueetaue dal

Fr Tris oo} TEEELISLLL LIE LLL rr TEETIT SI CELL ITT IT ie nee UL i~ 150%

SEO boc

ACS |

!

Duct

PeBEE

ALOT in| l ( io) te] sn | b []

SRADLIFIE aL l

50m 50m

Note 1: The example above shows JW-13BU mounted in a cabinet.

Note 2: To secure adequate ventilation and make module mounting/removal and cabling easy, allow vertical spacing of 50 to 150mm between rack panels. A space of less than 50mm may cause an abnormal temperature rise within modules.

Note 3: Allow a space of more than 50mm on the left-hand side of the basic rack panel.

*Do not install the rack panels in the orientations shown below, as this will cause an usual temperature rise within the system :

=] i a

[ l tnstalltion with vertical side Installtion with horizontal side facing upward (no good) facing upward (no good)

5-3

Page 139 read from a scan by OCR; it may hold reading errors

eWhen installing rack panels side-by-side, allow a space of 50 to 100 mm between them.

50~100mm |

AOL PORT TOE TAT TTT ET A UT a l = a o}° i ic) nee (Unit : mm} qd t it Seana | 2 | Jw-4Bu) | 8 | I g ZW-48KB lg at oo ~ at I = TIS Te eo yO ~ yh = mal 4601 1 ZW-46KB mounting hole location g | Jw-eau || 8 f + ii = | Fs ZWARZB | 8 . 222% 4 . ! + - - -a7--, - 4) “18 ! | ZW-102ZB mounting hole location & Jw-8BU |] 8, I | | +- -, = - - ==t B ZW-106Z28 | B = 202 4 g eee re ‘ 1 £90 ei | JW-138U 3 ZW-104ZB mounting hole location 7 i 1 T Qe | | | | 43 a OF | ‘ ' 460+ 4 al | : ZW-08BU | 3 g 2W-5082B it a | | & ZW-08BU mounting hole location i \ Fs © as 2 st W524 a - - ~-- - - - - - - }, u | | z ZW-1082 8 | g i Toes DT SST | + & 48021 . 4 ~ - ee ee, _ 4 g ZW-28KB | | i ses 8 +

M5-16 tapped hole

Rack panel mounting hole location with board-to board spacing set to 100mm.

5-4

Page 140 read from a scan by OCR; it may hold reading errors

5-4 Installation of power supply module

Module attachment screw hole

Phillips screwdriver

CF

Output connector SS

Module attachment screw hole

Phillips screwdriver

Rack panel attachment screw

1) Plug the power supply module's output connector plug into the left end connector on the rack panel. 2) Secure the two rack panel retention screws of power supply module into module retention screw hole of rack panel using a phillips screwdriver.

5-5

Page 141 read from a scan by OCR; it may hold reading errors

5-5

Installation of memory module This is the way to install th memory module on the control module (JW-70CU/100CU, JW-70CUH/

100H).

[1] Installation of memory module (ZW-1MA/ZW-2MA/ZW-3MA)

Put the memory module on the CPU board of control module.

Connect the memory module's connector and the CPU board's connector.

Fix the memory module with 3 screws to the CPU board.

Install EPROM or EEPROM to IC socket when the ROM operation is used. (see page 162).

N

| Set SW1 and SW

| End RAM EEPROM swe ae " SW1 ROM EPROM

Control module.

JW7OCU | JW-100CU |

CPU board

Memory module ZW-1MA j

| ZW-2MA ZW-3MA

IC socket

| f: OEE, lth

Setting

EEPROM

AT28C64B-15PC (made by ATMEL, available for only B version) : AT28C256-15PC (made by ATMEL)

EPROM

27C512(Fuitsu)

SW2: Select ROM/RAM operation

Setting at ROM ROM operation.

Setting at RAM RAM operation.(normal operation).

Note 1: ROM operation is only available when SW2 is set for ROM operation and the ROM chip is installed.

Note 2: Be sure to install the memory back-up battery on the RAM operation, otherwise, all program will be cleared when the power is OFF. Note 3: ZW-1MA/2MA/3MA can be installed on the control module (JW-70CUH/100CUH), but processing speed is same as normal level.(See page 4-20.)

5-6

Page 142 read from a scan by OCR; it may hold reading errors

[2] installation of memory module (ZW-4MA)

Put the memory module on the CPU board of control module.

Connect the memory module's connector and the CPU board's

Control module connector. Wolponu | Fix the memory module with 3 screws CPU board to the CPU board. Memory module (ZW-IMAD FP O i [ Set SW1 to SWA. a | End. | i q ! ] if F ani ++ - Hr ye 4 [| 4 Screws / if iu. SWi~sws (| ipo os Setting of SW1 to SW4 4 2 3 4 5 | SWNo. |, __ Contents | ON OFF ON 1 Switch file #4 and#C_ | #4 #C = a a a = 2 Switch file #5 and#D | #5 #D 3 Switch file #6 and #E #6 #E OFF] OLL LL 4 File #7 is used or not Used Not used 5 Vacant

Note 1 : Be sure to install the memory back-up battery when ZW-4MaA is used. Note 2 : Clear the memory area by using support tools after the installing the memory module. Refer to each manuals of support tools for details.

Note 3 : The ZW-4MA can be installed on the control module (JW-70CUH/100CUH), but processing speed is same as normal level. (See page 4-20.)

Page 143 read from a scan by OCR; it may hold reading errors

[3] Installation of memory module (JW-1MAH/3MAH)

Put the memory module on the CPU board of control module. Cc ontrol module Connect the memory module's connector and the CPU board's Wetec connector.

CPU board

Fix the memory module with 2 screws to the CPU board.

y

Install EPROM or EEPROM to IC socket when the ROM operation is

Memory module

JW-1MAH | JW-3MAH !

used. | Set SW1 to SW2. | End. | soon

SW2 an

IC socket RAM nial EEPROM Swi ' 7 ! sw2, - - - __ SW2 : Sat the type of ROM ROM Setting | ROM model name _ H EPROM AT28C64B-15PC

(made by ATMEL, available for only B version) AT28C256-15PC (made by ATMEL)

27C512(Fuitsu)

EEPROM

(© mark : Setting at delivery) QEPROM

SW1: Select ROM/RAM operation and normal/high speed

‘Setting _ “Contents Swi-t ORAM Setting at RAM operation ROM Setting at ROM operation {Note 1 Swi-2 L. Normal speed OH High speed

Note 1: ROM operation is only available when SW1-1 is set for ROM operation and the ROM chip is installed. Be sure to install the memory back-up battery on the RAM operation, otherwise, all program will be cleared when the power is OFF.

Note 2: Refer to the programming manual “Chapter 3. Description of instructions" to confirm the each processing time. (Normai/high speed).

*Processing time of normal speed operation, Processing time of JW50/70/100. *Processing time of high speed operation > Processing time of JW50H/70H/100H. (When the JW-1MAH/3MAH is installed on the JW-70CU/100CU,

5-8

Page 144 read from a scan by OCR; it may hold reading errors

[4] Instailation of memory module (JW-2MAH)

Put the memory module on the CPU board of control module. Control module 2 Wy

Connect the memory module's - [ YWw7oCuUr UD?

connector and the CPU board's JW100CUH connector. we CPU board 4

Fix the memory module with 3 screws Memory module HL rs to the CPU board. (JW-2MAH)

Ora

Install EPROM or EEPROM to IC socket when the ROM operation is used.

eS OD

} | res Serena ee, ,

S | Set SW2 to SWS. | | y | End. | RAM RAM EEPROM Q Screws / SWw2 1, ‘| a SW3, - - - - - - - SWS : Set the type of ROM ROM - Setting | ROM model name _ H EPROM AT28C64B-15PC {made by ATMEL, EEPROM available for only B version) AT28C256-15PC (© mark : Setting at delivery) (made by ATMEN) g 'Y), |OEPROM 27C512(Fuitsu)

SW2: Select ROM/RAM operation and normal/high speed

Swi-1 ORAM Setting at RAM operation ROM Setting at ROM operation [Note 1 swt-2 L Normal speed OH High speed

Note 1: ROM operation is only available when SW2-1 is set for ROM operation and the ROM chip is installed. Be sure to install the memory back-up battery on the RAM operation, otherwise, all program will be cleared when the power is OFF.

Note 2: Refer to the programming manual "Chapter 3. Description of instructions" to confirm the each processing time. (Normal/high speed).

*Processing time of normal speed operation, Processing time of JW50/70/100. *Processing time of high speed operation + Processing time of JW50H/70H/100H. . (When the JW-2MAH is installed on the JW-70CU/100CU,

Page 145 read from a scan by OCR; it may hold reading errors

[5] Installation of memory module (JW-4MAh)

Put the memory module on the CPU C ontrol module board of control module. Connect the memory module's Beste | connector and the CPU board's 9 connector.

CPU board 0 0

‘ ; : Memory module a | Sg

Fix the memory module with 3 screws COW-AMA LD rete } to the CPU board. H {

| Set SW1 and Swe.

Gkeetteccrenen F

ERC

>

| an}

| End

SW2

SW1: Select the file memory

ORF | Gre Setting __ - _ - Contents OFF |. ON ae Sw! SW1-1_ | File #7 is used or not} Unused Used ON L1_2 SW1-2 | Switch file #6 and #E| #E #6 H SW2: Select normal/high speed ORAM - d SWe2-1 ROM Unuse swe-2 L Normal speed OH High speed

Note 1: Be sure to install the memory back-up when JW-4MAH ts used.

Note 2: Clear the memory area by using support tools after the installing the memory module (JW- 4MARH). Refer to each manuals of support tools for details.

Note 3: Refer to the programming manual “Chapter 3. Description of instructions" to confirm the each processing time. (Normal/high speed). *Processing time of normal speed operation > Processing time of JW50/70/100. *Processing time of high speed operation + Processing time of JW50H/70H/100H. (When the JW-4MAH is installed on the JW-70CU/100CU,

5-10

Page 146 read from a scan by OCR; it may hold reading errors

5-6 Installing the control module

Module attachment screw hole

Installation position for optional cable

Installation procedure for optional cable

Phillips screwdriver (Bend the option cable.

ea

@)Attach the connectors in the optional cabie one after another, starting from the left side.

Option module . Connector details installation slot

1) Plug the control module's connector into the mating socket next to the left end socket on the basic rack panel. 2) Secure the two rack panel retention screws of control module into module retention screw hole of rack panel using a philips screwdriver.

Note 1: When using an option module, install the option cable on the basic rack panel before installing the control module. When installing the option cable, ensure the correct connector orientation.

Note 2: Be sure to install the control module right next to the power supply module.

Note 3: Bend the option ribbon cable toward the basic rack panel.

5-11

Page 147 read from a scan by OCR; it may hold reading errors

5-7 Installation of /O modules

[1] installing JW-series I/O modules The JW-series I/O modules can be installed on any of the following types of rack panels:

JW-13BU | Accommodates up to 13 JW I/O modules. JW-8BU Accommodates up to 8 JW I/O modules. JW-6BU Accommodaies up to 6 JW I/O modules. JW-4BU Accommodates up to 4 JW I/O modules.

Rack panel a

Philips screwdriver

Input module, output module

1) Plug the I/O module's connector into the mating socket on the rack panel. 2) Secure the two rack panel retention screws of I/O module into module retention screw hole of rack panel using a philips screwdriver.

Note 1: Whenever installing or removing an I/O module, be sure to turn off the power supply to the rack panel or enter the “Live VO replace” mode.

Note 2: Do not install a contact output module (JW-34S, etc.) next to an option module as voltage spikes from relay contacts may cause the option module to malfunction.

Note 3: No I/O modules can be installed in positions where the option cable (ZW-2CC/4CC/6CC) is already installed.

5] ° q a a ree lb

Rack panel CJW-13BU)

Cable for option (ZW-4CC)

CO modules cannot be installed in these: > positions.

Page 148 read from a scan by OCR; it may hold reading errors

[2] Installing ZW-series /O modules The ZW-series I/O modules can be installed on any of the following types of rack panels:

Rack panel ZW-08BU | Accommodates up to 8 ZW I/O modules. ZW-28KB | Accommodates up to 8 ZW I/O modules. Basic rack ZW-46KB _ | Accommodates up to 6 ZW I/O modules. panel ZW-04KB | Accommodates up to 4 ZW I/O modules. ZW-02KB | Accommodates up to 2 ZW I/O modules. ZW-108ZB| Accommodates up to 8 ZW I/O modules. Expansion ZW-104ZB} Accommodates up to 4 ZW I/O modules. rack panel ZW-102ZB} Accommodates up to 2 ZW I/O modules. ZW-508ZB| Accommodates up to 8 ZW I/O modules.

Rack panel Guide hole | Module retention screw, VO module retention Guide pin. ; \ Guise pin Guide hole cover screw’ ee > ~

Rack panel

POS a. _ Guide hole. oad Guide pin I/O terminal block Rack panel retention screw

Guide pin\ Guide hole . Terminal block ~~ Module retention screw

1) Remove the front access cover from the I/O moduie to be installed (insert your finger into the cover's top opening and pull the cover forward).

2) Insert the guide pins at the back of the I/O module into the mating guide holes in the rack panel, then push in the module until its connector is firmly plugged into the mating socket.

3) Secure the module to the rack panel with the top and bottom module retention screws.

4) Connect the cable wires from an external 1/O device to the terminal block (ferminal type), or to the /O connector(connector type}.

5) Replace the front access cover, with the cables from the terminal block passing through the bottom opening of the cover (terminal block type).

H you have difficulty removing the front cover, pull while pusing on this area with your thumb.

(Removing the /O module's front cover) {Installing the I/O modute’s front cover)

Note 1: Whenever installing or removing an I/O module, be sure to turn off the power supply to the control module or the expansion rack panel on which the I/O module is installed.

Note 2: Do not install a contact output module (ZW-16S4/16S4D/32S4T, etc.) next to an option module as voltages spikes from relay contacts may cause the option module to malfunction.

5-13

Page 149 read from a scan by OCR; it may hold reading errors

5-8 Installing the side panel on an I/O module

[1] Installing the side panel on a JW-series I/O module

Side panel [

J =

[2] Installing the side panel on a ZW-series I/O module The side panel to be insfalled on the Jeft side of the left end VO module on an expansion rack panel is supplied with the expansion rack panel.

Supplied tapping screws (M3X8) ~~ 4

AACA Ck

LE /, - or Insert these claws the module.

Side panel

* Apply a torque of less than 0.49Nem to the tapping screws.

Page 150 read from a scan by OCR; it may hold reading errors

5-9 Installing the expansion power supply module (for ZW-I/Os)

@)Guide pin hotes

(2)Module retention screw holes (8)Cover retention screw hole

Guide pin holes Guide pin

@ Module retention screws

@Cover retention screw @Power supply module cover

1) Loosen the cover retention screw @) with a Philips screwdriver and remove the cover (3) from the expansion power supply module. 2) Insert the four guide pins at the back of the module into the mating guide pin holes @) in the expansion rack panel (ZW-108ZB, etc.) then push in the module until its connector is firmly plugged into the mating socket.

3) Secure the two rack panel retention screws of expansion power supply module into module retention screw hole of rack panel using a philips screwdriver.

Note 1: The expansion power supply module cannot be installed on the JW-4BU/6BU/8BU/1 3BU rack panels, ZW-28KB/46KB basic rack panels, or ZW-508ZB expansion rack panel.