Page 161
6-4 Wiring for ZW-100PU1/100PU2 expansion power supply module
Open the terminal cover and connect the cables to the terminal block as shown :
ran WW
Not usable
Seeeeee
S m= GND
Class-3 grounding KIV1.25 or thicker wire
400 or 200 VAC aot
Connect in series with / the power supply module’s halt output f
1
AC line power input
=, Aeje
Oo}
Halt output
= fan Wy a 100 or 200 VAC LSA - “at line power input, J \ @]|| - aro, ~7T L- sal Class-3 grounding SS a fe) aa \ Halt output, ! (S) AC relay q
Terminal block on ZW-1PU power supply module
Note 1: Apply a torque of 1.18Nem or less to the terminal screws.
Note 2: Up to three halt output circuits can be connected in series. For more circuits, use an intermediate relay.
Note 3: For a line voltage of 200 VAC, the supply voltage selector switch on the expansion power supply module must be set to the 200 VAC position (see page 4-83).
Page 162
6-5
Wiring for expansion rack panel
When one or more expansion rack panels are to be used, interconnect them and the basic rack panel as shown below, using the 1/O expansion signal and 5V power cables supplied with each rack panel. When connecting cables, pay special attention to the discrimination between the !N and OUT ports of the I/O expansion connectors.
vo expansion signal cable (45 cm) a a ZW-5082Z B VO expansion signal cable (60 cm) f a ZW-1082 B | ZW-1082B ZW-28KB ZW-46KB
When installing expansion rack panels side-by-side, use the ZW-1KC I/O expansion signal cables. For connection to the ZW-10EU I/O expansion module, see the description in section 4-10-1.
Signat cable for expansion: ZW-1KC (tm)
b 5V cable for I/O expansion ao
Note 1: Use wires with a thickness of KIV 1.25 or more for the I/O expansion 5V power cables.
Page 163
*Connecting the I/O expansion signal cable
Reverse insertion prevention key Side lock
The !/O expansion signal cable plug has a reverse insertion prevention key. After plugging the cable into its socket, lock it with the side locks.
4
1N OUT ee, (qe
Note 1: Do not tie the I/O expansion signal and 5V power cables with the PC's input/output signal cables or power cables, nor install one in the duct or conduit where the other is installed.
Page 164
6-6 Wiring for input and output modules
[1] Terminal block type Use a crimp-style terminal for every connection of external devices, such as limit switches and solenoids, to input/output modules.
‘| 1.25-YS3A 2-YS3A V1.25-YS3A B<7.4 V2-YS3A d2>3.5 105-37
2-53 V1.25-3.7 V2-S3
)-style terminal models.
After typing all wires to the terminal block, pass the wire harness through the slot between the terminal block and the I/O module's terminal block on the left.
The terminal block can be detached from the I/O module with the cable wires connected.
Page 165
[2] Connector type description
(1) (2) (3) (4) Aline O Le
F] 2axg Use a slot screwdriver seals @ @ Address terminal rambog” . . O Pin block: FCN-361J040-Au (Fujitsu) Shell: FON-360C040-B (Fujitsu)
1) Address number assignments are not identical to pin number assignments. Assemble the plug with special attention paid to the address number assignments.
2) Cover every soldered wire end with an insulating sleeve. 3) Use a screwdriver to secure the cable plug to the mating receptacle on the module.
Recommended cable: Fujikura Electrical Wire Co. 18 X 7/0.18 57VV-SB (Multicore vinyl-insulated, vinyl-sheathed cable)
Note 1: If it is expected that a large current returns from an output module through the common line, use a thicker wire.
Page 166
6-7 Wiring for 24 VDC terminal block on rack panel (for ZW- 8S2/16S2/16S4)
When a DC output module (ZW-8S2, etc.) or contact output module (ZW-16S4, etc.) is used to drive DC loads, an external supply of 24 VDC must be supplied to the 24 VDC terminal block on the standard of expansion rack panel on which the module is installed.
[1] Driving a 12 or 24 VDC load from a DC output module
~ 24 V terminal block a e When driving a 12 VDC load from a DC output module, the external power supplied to the 24 VDC terminal block on the rack panel must have a voltage equal to or higher than that of the load power supply.
Expansion rack panel e, Basic rack panel Power supply for load (12 VDC or 24 VDC}
[2] Driving a load from a contact output module
_- 24 ¥ terminal block 74
¢ Use a DC power source separate from the load power supply and connect it to the 24 VDC terminal block on the expansion rack panel.
Expansion rack panel
1 24 VDC power supply
Power supph for load
Basic rack panel
Page 167
[3] Using both DC and contact output modules on the same rack panel
Contact output module
(+)
Relay driver 1 1 @ DC output module Load r wy,
I !
! 4
| |
| I o-
24 VDC |
Voltage regulator
Contact output module
(+)
DIO
(-)
Relay driver am abd
DC output module hy
Load pon)
I | I I | I
Voltage regulator eWhen driving a 24 VDC load from a DC output module, connect the positive and negative terminals of the 24 VDC load power supply to the corresponding terminals of the 24 VDC terminal block on the basic or expansion rack panel.
eWhen driving a 12 VDC load from a DC output module, connect a separate 24 VDC power source to the 24 VDC terminal block on the basic or expansion rack panel, with its negative terminal connected to the appropriate terminal of the load power supply. The 24 VDC power is required to drive the contact output module's relay coils.
Note 1: Apply a torque of 1.18Nem or less to the terminal screws. Note 2: When using an external source separate from the load power supply, observe the precautions given in page 4-64.
Page 168
6-8 Intercabinet cable routing examples
[1] Example for use JW-series I/O modules (1) The system given in this example consists of eight rack panels holding JW-series I/O modules and an I/O bus extension adapter:
Tey pe oreo SAS UnRyrnsseebeesats
I/O expansion cable
CJUW-05E C)
5 VDC cable (supplied with JW-O5EC) | [Cabling auct Birt TTT |
Allow a vertical space of 30 to 50mm between each cabling duct and its
I AC power supply adjacent rack panels. Halt output 219: Cabling duct if Class-3 grounding / I/O expansion cable (JW-1EC)
Note 1: Use the same AC line power source for all rack panels.
Note 2: DC and contact output modules require a 24 VDC power source which is separate from the foad power supply.
Note 3: Do not install expansion signal cables or i/O expansion 5VDC power cables in the same duct or conduct in which the PC's I/O signal cables or power cables are installed.
Note 4: For ZW-series I/O module, do not connect more than three halt output circuits in series. If more than three circuits must be connected in series as expansion power supply module operations are monitored by the control module through the I/O expansion cables. Use only the halt output of the power supply module on the rack panel. (The halt outputs of the ZW-2PU power supply modules cannot be connected in series. Be sure to use intermediate relays.)
6-18
Page 169
[2] Example for use JW-series I/O modules (2)
The system given in this example consists of two rack panels holding JW-series I/O modules and no I/O bus expansion adapter.
i
VO expansion cable
'5 VDC cable B CUW-0BKC/UW-1KC) (supplied with the /0 - [, expansion cable) Cabling duct PN TH Allow a vertical space of 30 to 50mm a o[) HOU EE between each cabling duct and its _ in adjacent rack panels.
AC power supply G =
°
*
SOK) [ks
Halt output a
Cabling duct
- Class-3 grounding
Note 1: An expansion power supply module can be instailed on the expansion rack panel only if the I/O bus expansion adapter (JW-1EA/2EA) is used in the expansion port.
Note 2: Use a JW-05KC or JW-1KC I/O expansion cable to establish bus connection between the rack panels. If a cable length of more than 1 m is needed, you have to use an I/O bus expansion adapter (JW-1EA/2EA).
Note 3: DC and contact output modules require a 24 VDC power source which is separate from the load power supply.
Note 4: Do not install expansion signal cables or I/O expansion 5 VDC power cables in the same duct or conduct in which the PC's 1/O signal cables or power driving lines are installed.
Page 170
[3] Example for use ZW-series i/O modules The system given in this example consists of four rack panels holding ZW-series I/O modules :
/O expansion signal cable ed
Use the cables supplied with the .expansion rack panel
IL 0 cable
5 VDC power
Ft! fi Ht rR |
Cabling duct
24 VDC cable
4
DODOOCODOCEDODODOOOOAREN
|
- ox
DOOOOOOOMOWMOCOAGONQONODE DOD
UE i,
Bu a
Eon o =
‘ee =
SI
Cabling duct
CC) CU) |)
Allow a vertical space of 30 to 50 mm between each cabling duct and its adjacent rack panels.
>,
C AC line power s_.3le
Ma a le
Cabling duct hoo To external 24 VDC power source
(required when DC or contact output modules are used.)
Class-3 grounding
Note 1:
Halt output supplied from the same AC line power source.
Note 2:
module's halt output cannot be connected in series.
Note 3:
which is separate from the load power supply.
Note 4:
The power module and expansion power supply module used in the system should be No more than three halt outputs can be connected in series. The ZW-2PU power supply When DC and/or contact output modules are to be used, prepare a 24 VDC power source
Do not install the I/O expansion signal cables and 5 VDC power cables in the same ducts or conducts where the PC's 1/O signal cables or power cables are installed.
Note 5:
When using the I/O expansion module, see page 4-93.