Page 202
/O error
Note 3: When the error code is 40, reset the I/O collation of hand-held programmer (be specifying the rack, slot). Then, if the error does not occur, it can be judged that the //O module of rack, slot for which 1/O collation has been reset had caused the error.
Note 4: If you set the live I/O installation/removal, you can replace the I/O moduie while the power supply is kept turned ON. While the live 1/O installation/removal is set, the PC calculation is halted. However, the halt output is kept turned ON (close).
[Hand-held programmer key-in procedure]
. . . . a _ _.[ se] Setting the live I/O installation/removal (6 |
Resetting the live I/O installation/removal
SHE
44
1/O data bus
45
/O signal
Mi When using JW-V/O
Check the setting of system memory #0250 (total number of bytes used by the I/O module) and, if it is improper, set it again.
Note 1: Setting of #0250 is required for the system memory #0252 =105:a) (which specifies self-diagnosis of I/O address). When #0252 is set to 000ca) (which does not specify self-diagnosis of I/O address).execute the following operation step 5 and its subsequent steps.
(2)Monitor the system memory #0046. Then, check whether the 1/O module of the I/O address (byte address} where the error has been securely mounted.
765 432 10 #0046 [2/11 [4] 2/14 [2 /1} \ \
Byte addres (JO000 to ]0037)
@)Replace the /O module mentioned in the above (@).
(@)Replace the rack panel in which the I/O module mentioned in the above () has been installed.
()Check whether all the module and I/O expansion cables have been securely attached.
()When the I/O expansion module (ZW-10EU) is used, check the switch setting and check whether it has been securely mounted.
@Sequentially replace the signal cables for system expansion.
(8)When the VO expansion module (ZW-10EU) is used, replace it.
(9)Replace the control module.
(0)Replace the I/O modules sequentially from that nearest to the control module.
@) Replace the rack panels sequentially from the basic rack panel.
Note 2: If you disconnect the signal cable for system expansion to be connected with the rear-side racks while the power supply module is turned OFF, then turn ON the power supply, you can select only a few possible error causes from among many candidates. (lf the error does not occur while the cable is dis-connected, any of the I/O module, rack panel, power supply module or cable may be defective.)
11-11
Page 203
I/O error
46
Special 1/0 error
(Monitor the system memory #0046 and abtain the I/O rack, slot where the error has been detected.
765 43210 #0046 (ol4i21ital4 [ati |
YS
Rack No. Slot No.
(@)Check whether the special I/O module of the rack, slot monitored in the above (1) has been securely attached.
(3)Check whether the 24 VDC power supply is properly supplied when JW-12DA is employed; check whether the 12 VDC power supply is properly supplied when JW-12PM is employed.
(4)Replace the special /O module in the above (2).
(5)Replace the control module.
49
Output module fuse blown
Monitor the system memory #0046 and obtain the /O rack, slot where the error has been detected.
76543210 #0046 Lol4l2lilsl4]e2]7 | : ne
CY Rack No. Slot No.
(@)Check whether the FUSE lamp on the front of output module of the rack. slot monitored in the above (1) is lighted, replace the fuse of pertinent module.
Replace the output module mentioned in the above @). @)Replace the control module.
Note 1: You can set the system memory #0206 so that the PC operation is halted or continues when the fuse burned out is detected. | PC operatio trol m EES | status RUN Operation Flashing 000 continuation | CIS? (intermittent) | Light OFF 010 Halted Open | Light OFF | Light ON
11-12
Page 204
Expansion power supply error
43
Power failure input voltage drop
(Check whether the power voltage changeover short bar of the power supply module (JW-1PU) mounted in the expansion rack panels (racks 1 through 7) has been properly attached (on the 100 VAC position or 200 VAC position).
@)Check whether the input voltage is properly supplied to the power supply module mounted in the expansion rack panels {racks 1 through 7).
- JW-1PU: 85 to 132 VAC(when 100 VAC is selected.) 170 to 264 VAC(when 200 VAC is selected.) - JW-2PU: 20.4 to 32.0 VDC
@)Replace the power supply whose power lamp is extinguished.
)Replace the control module.
©)Replace the rack panel in which the power supply module whose power lamp is extinguished is mounted.
()Sequentially replace the VO bus expansion adapters (JW-2EA)|
@Replace the (/O bus expansion adapters (JW-1EA),
@®)Sequentially replace the I/O expansion cables.
Option error
52
Optional bus error
@)Check whether the option modules (JW-10CM, JW-20CM, JW-20MN, JW-10SU, JW-50CM, and ZW-30CM) have been securely mounted.
@)Reset the special relay 07366 (normally-OFF contact) (to OFF).
@Check whether the user program turns ON 07366. If it turns ON 07366, modify the program.
@ Initialize all the memories with the hand-held programmer, then load the programs to the program memory and the system programs to the system memory again.
)Sequentially replace the option modules. (6)Replace the memory module.
@ Replace the control module.
(8 Replace the cables for the option modules. ‘9)Reptace the rack panel (rack 0).
53
Option module error
(Monitor the system memory #0050, and obtain the option module slot where the error has been detected. (Any slot whose bit is turned ON is defective.)
76543 210
#0050 | L_ PG, I/F, communication port Not used
Slat 2 for option module Slot 3 for option module Slot 4 for option module Slot 5 for option module Slot 6 for option module Slot 7 for option module
Rack panel (JW-13BU)
|___Slot 7 for option module Slot 6 for option module
Slot 5 for option module Slot 4 for option module Slot 3 for option module Stot 2 for option module
11-13
Page 205
Optional 53 error
Option module error
@®Check whether the option modules (JW-10CM, JW-20CM, JW- 20MN, JW-10SU, JW-50CM, and ZW-30CM) have been securely mounted to the optional slot monitored in the above (1).
(3)Replace the option modules mentioned in the above @).
@)Replace the control module.
(&)Replace the cables for the option modules.
(Replace the rack panel (rack 0).
@)Sequentially replace the option modules.
(8)Check whether the writing works such as wiring of communication cable, etc. of each option module have been properly done. (For details, refer to the user's manual of each option module.)
Note 1: You can set the system memory #0207 so that the PC operation is halted or continues when the option module error is detected.
765 432 1090
#o2z07 LI | | | [ J it | 765432
Slot number for option modules
- operation | Halt 2b output.
Flashing (intermittent)
Operation
. . Close continuation
Light OFF
010 Halted Open Light OFF | Light ON
Battery 22 error
Battery voltage drop
Replace the battery. @)Replace the control module. @)Reptace the memory module.
Other error code
Turn OFF and ON the power supply.
@After having initialized all the memories with the hand-held programmer, load the programs to the program memory, the system memory, the data to the data memory and the files to the file memory again.
[Hand-held programmer key-in operation for initializing all the memories]
_ |_.{proe|__ [set ]__ four |_. faeser|_ fz _.,.{ 15 PS ei-fo }-[8
@)Replace the control module. (4)Replace the memory module. (6)Replace the power supply module.
Note 1: Although the power supply error (error code 13) is written when the power supply is turned ON, it is not a defect.
support too!
When you can not communicate with
Hand-held programmer: "PC KIND?" JW-50SP: “Connection error"
(1) Replace the control module.
Others
@Check whether any unlimited loop or scan time of the ladder pogram does not exceed 320ms. If it does, set the PC in the halt mode and modify the ladder program.
(@)When using the remote I/O for JW-10CM/20CM, if you select the mode 0 (specify halting PC when an error has occured to the slave station), check whether an error (including turning OFF of power supply) has not occurred to the slave station.
11-14
Page 206
Power supply error
Check the setting of 100 VAC/200 VAC changeover short bar or changeover switch on the front of power supply module.
v
If the setting is improper, set it to the proper setting. Note : If 200 VAC is applied when 100 VAC is set, the power supply module may be damaged.
NG
Measure the input voltage with the primary power input terminal on the front of power supply module.
JW-1PU : 85 to 182 VAC (when 100 VAC is set) 170 to 264 VAC (when 200: VAC is set) JW-2PU : 20.4 to 32.0 VDC
ZW-100PU1/2 : 85 to 110 VAC (when 100 VAC is set) 170 to 220 VAC (when 200 VAC is set)
+
If the input voltage is outside the above pertinent range, set it to a proper value.
NG
Check whether the fuse on the front of power supply module is not burned out.
Hf the fuse is burned out, replace it. ZW-100PU1 : 2A/250V, resistant to surge ZW-100PU2 : 3A/250V, resistant to surge
NG
Check whether you don't use the power supply module, exceeding its capacity.
JW-1PU : 7A, ZW-100PU1 : 7A
JW-2PU : 5A, ZW-100PU2 : 12A
+
Reduce the number of mounted modules or add a power supply module.
NG
Replace the power supply module.
NG
Replace the control module.
NG
Replace the rack panel.
11-15
When using JW-2PU
When using
JW-1PU/2PU
Page 207
Halt mode (program mode) |
Set the operation mode (monitor mode, change mode) with the hand-held programmer or the like.
NG
Check whether the PC has been halted from the option module (JW-10CM, JW-20CM, JW-20MN, JW-50CM or ZW-30CM.)
4
If the PC has been halted from the option module, operate it from the option module.
NG
Replace the control module.
The control module cannot be controlled with the support tool.
Does the hand-held programmer show "PC Not display KIND?" or does the JW-50SP show
"Connection error"? /
Display Replace the control module. Check whether the control module and
NG support tool have been securely connected. Sequentially replace the /O Securely attach the connection cables and bus expansion adapters converter (when the JW-50SP is used.)
(JW-1EA/2EA). NG
NG
Replace the connection cable.
Sequentially replace the option and I/O modules.
NG
Replace the rack panel.
NG NG
Replace the support tool (the converter when the JW-50SP is used.)
11-16
Page 208
The halt output operation is improper.
Short-circuit the halt output terminal (HALT OUTPUT) on the front of power supply module while the PC is operating. Note : Since the AC current flows, be careful about the insulated wires, etc.
< Does the halt output load (circuit) \ No (unchanged)
operate ?
Yes
.
Check the external wiring related to halt output.
Check whether the halt output fuses on the front of power supply module are not burned out.
S
{f any fuse is burned out, replace it. JW-1PU: 1A/250 V, ordinary class. JW-2PU: 1A/250 V, ordinary class. ZW-100PU1: 1A/250 V, ordinary class ZW-100PU2: 1A/250 V, ordinary class
NG
Replace the power supply module.
NG
Replace the conirol module.
NG
Replace the rack panel.
11-17
Page 209
This flow shows the checking procedure in the event of error of input signal not detected by the self-diagnosis of the control module.
Example of the error
¢ All inputs of specific input module fail to be turned ON.
* Specific input fails to be turned ON (OFF).
* Among input signals of a same input module, operation of a certain input signal affects other input signal.
Countermeasure: Error input signal
(1)| Measure the voltage between the corresponding input terminal of the input module and the common terminal using a tester.
If supply voltage is applied between terminals: ON
If supply voltage is not applied between terminals: OFF
(@)| Check the state of LED of input module.
(3)| Connect hand-held programmer, and check ON/OFF by monitoring the data memory (input relay) corresponding to the abnormal input.
=
In case of (==) Check the external wiring and power supply.
In case of the others Exchange the I/O module.
[The flow of input signal]
Control module Input module
VF LED circuit
VA
‘Common terminal
Memory input terminal | : 4 | \ lPoner supp]
Hand-held programmer
11-18
Page 210
iow 7) This flow shows the checking procedure in the event of error of output signal not detected by the self-diagnosis of the control module.
Example of the error
¢ All inputs of specific output module fail to be turned ON. (In this case, it is highly possible that the fuse of load power output is melted down.)
¢ Specific output fails to be turned ON (OFF).
¢ Among output signals of a same output module, operation of a certain output signal affects other output signal.
Countermeasure: Error output signal
(| Connect hand-held programmer, and check ON/OFF by monitoring the data memory (output relay) corresponding to the abnormal output.
2)| Check the state of LED of output module.
(3); Measure the voltage between the corresponding output terminal of the output module and the common terminal using a tester. When the inter-terminal voltage is output ON voltage {about 1 V or less): ON When the inter-terminal voltage is load supply voltage: OFF Note: When the load power source is OFF and wiring to the load is disconnected, it is error if the output is normal.
| In case of ()=()=@) - - - | Connecting load is error.
| In case of M=@=@B) - - Check the external wiring (power supply).
In case of the others /- - 4 Exchange the output module. |
[The flow of output signal]
Control module Output module i} WF
| ‘| circuit 2)
' LED Output terminal
| | Memory |: + Load 2 | @
Hand-held programmer
11-19