Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 9 of 30

Programmable controller New Satellite JW, JW50H/70H/100H User's Manual/Hardware version: Chapter4. Name and function of each part, pages 59 to 68

Pages 59 to 68 of 254, from Programmable controller New Satellite JW, JW50H/70H/100H User's Manual/Hardware version

The original document is the PDF (8.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sharp ZW-16S2, Sharp ZW-32N2T and Sharp ZW-32S4T

Page 59 read from a scan by OCR; it may hold reading errors

[5] Notes on the usage of rack panels (1) Using JW-series 1/O modules 1. Using the I/O bus expansion adapter (JW-1EA/2EA) in each rack panel allows up to eight rack panels to be connected in a daisy chain configuration. However, the number of usable I/O modules depends on the number of 1/O points controllable by the control module installed in the rack panel. The following table lists the number of usable I/O modules for the various control module types:

JW-100CU

Max. No. of rack panels 8 8 8 ve pore Oe oes 512 points/ 1024 points/ 4096 points/

PP g only S4-p 8 modules 16 modules 64 modules I/O modules VO points and I/O modules F : 3168 poinis/

: . 512 points/ 1024 points/ supported using only 32-point 16 vrodtales 30 modules 99 modules I/O modules *Note 1 I/O points and I/O modules 1584 points/ supported using only 16-point 99 modules I/O modules *Note 1

VO points supported using X 64-point, Y 32-point, and Z 16-point I/O modules

64X+ 32Y+16Z 64X+ 32Y+16Z 64X+ 32Y+16Z 512 points 1024 points 1024 points

Note 1: These numbers are attained using eight JW-13BU rack panels, one control module, and four power supply modules.

2. If two rack panels are used with no power supply module installed in the second rack panel, only an /O expansion cable may be used to connect the two rack panels (no I/O bus expansion adapter required). Use a JW-1KC(1m) or JW-O5KC (50 cm cable}. Do not use a cable 1m or more in length.

/O expansion cable YO module (JW-O5KC/JW-1KC)

Power supply module

/O module

Control module

4-34

Page 60 read from a scan by OCR; it may hold reading errors

(2) Using ZW-series /O modules

1. A basic rack panel combined with expansion rack panels can be hold a total of up to 32 ZW-series I/O modules. However, the number of usable I/O modules depends on the number of I/O points controllable by the contro! module installed in the rack panel. The following table lists the number of usable /O modules for the various control module type:

Max. No. of I/O modules 32 32 32 vo pois ae oan t 512 points/ 1024 points/ 2048 points/ PP g only bP 8 modules 16 modules 32 modules

/O modules

I/O points and VO modules” 512 points/ 1024 points/ 512 points/ supported using only 32-point 32 modules 32 modules 32 modules i/O modules *Note 1

I/O points and I/O modules _ 512 points/ 512 points/ 512 points/ supported using only 16-point 32 modules 32 ules 32 modules

VO modules *Note 1 module *Note 1

/O points supported using X 64-point, Y 32-point, and Z 16-point 1/O modules

64X+ 32Y+16Z 512 points

64X+ 32Y+16Z 1024 points

64X+ 32Y+16Z 2048 points

Note 1: If more than 512 I/O points are required with 8 or 16 point modules, see page 101.

2. Up to three expansion rack panels may be attached to the basic rack panel's I/O expansion connector in a daisy chain.If more than three expansion rack panels are needed, see page

4-84,

3. When two or more expansion rack panels are to be used, use an expansion power supply module(ZW-100PU1/100PU2) in one of them, depending on the total system power requirement and the current capacity of the power supply module used in the rack panel.

Expansion rack panel fo Expansion power supply

Expansion rack panel

Total cable length not more than 4m

Expansion rack panel

[ Power supply module

Basic rack panel

Max. 8 I/O modules module

Max. 8 I/O modules

Max. 8 I/O modules

Max. 8 I/O modules

Note: The I/O expansion cabies should not exceed 4m in total length.

4-32

Page 61 read from a scan by OCR; it may hold reading errors

4. For connection between the basic and expansion rack panels or among more than one expansion rack panels, use the I/O expansion cable and 5 VDC power cable supplied with each expansion rack panel.

5. Install I/O modules in the slots of the basic or expansion rack panels from left to right, leaving no vacant slot will be inoperative. If you need an intermediate vacant slot for future system expansion, install a dummy module (ZW-100DM).

»

Power supply module - i» These I/O modules are inoperative. They become operative if a dummy

Vv t _ acan module is installed in the vacant space.

space

6. After powering up the system, verify that the power indicator on each expansion rack panel comes on. If a light remains OFF, no 5 VDC power is being supplied to the rack panel. Check the power connection. Note, however, that the ZW-508ZB expansion rack panel has no power indicator.

7. For details on module installation and cabling see Chapter 5 {page 5-1), "Installation" and Chapter 6 (page 6-1), "Wiring."

4-33

Page 62 read from a scan by OCR; it may hold reading errors

[6] Outline dimension drawings (1) Rack panel

81k a Gy Rack panel (JW-13BU) _ H0 20 HUT H \ Boo : | Rack panel (JW-8BU) a 242 222 "i g FTI Ul, EC earnerearear at Rack panel (JW-6BU) 5 176 164 ‘A ¥ > r > mat al Rack panel (JW-4BU) 480 __460

4 >? SS + +) = SRA =) 1 yy : | Miss : oe (Oy GO. oy Se Os Be Op On LS] \p #12 Rack panel (ZW-08BU) rr Detail of mounting hole

4-34

Page 63 read from a scan by OCR; it may hold reading errors

(2) Basic rack panel

40 a, + oS ee A LT Basic rack panel (ZW-28KB) om

480

460 ss *T5°* oO Oo 0° O° O°

| fo f

Br 7 a i uU i 2° 2 «6 a 6 SO TST ETT SY iY Basic rack panel (ZW-45KB) 5 242 7 222 at

Cry

776" @9*0°.0 cet aml "Lu...

280 300

Detail of mounting hote

« « [Oe OF Oe Oe LI fn

Basic rack panel (ZW-04KB) 167

$$ it

137 et

6 A !, - pal]

28 U F « [oe Of I {fe ht Basic rack panel (ZW-02KB) %6

4-35

Page 64 read from a scan by OCR; it may hold reading errors

(3) Expansion rack panel

200

250

5 ay FE i te) i 8] Be Jo, o,f, ©, 2, SO, Se o. |?

Expansion rack panel (ZW-108ZB)

310 290 fay 4, - 200 250

Scena is h 6 f- a] o4 oo |” |

Expansion rack panel (ZW-102ZB) 10

' 395 | | 375 ' a or oF ot oF oF 2 “alo : | fe

E |

’ Expansion rack panel (ZW-508ZB})

>

200 250

4-36 peat ie) /

/

“+ 9B

Detail of mounting hole

Page 65 read from a scan by OCR; it may hold reading errors

[7] Specifications for rack panel, basic rack panel, and expansion rack panel

1. Rack panel(for JW-series I/Os)

Power supply module siots 1 1 1 1 Control module slots 1 1 1 1 Option module slots 6 6 4 2 /O modute slots 13 max. - 8 max. 6 max. 4 max.

Screw mounting with four M5 screws (mounting hole; slotted

Mounting method g ; round hole with 7mm diameter)

Outline dimensions (WXHX D)|} 480X250*5 | 3102505 | 2422505 174X250X5 Weight Approx. 1.3 kg | Approx. 0.8 kg | Approx. 0.6 kg | Approx. 0.4 kg

2. Rack panel(for ZW-series |/Os)

Power supply module slots 1

Control module slots 1

Option module slots 0

/O module slots 8

Screw mounting with four M5 screws Mounting method (mounting hole; slotted round hole with 7mm diameter) Outline dimensions (WXHX D) 480X250 X25 Weight Approx. 1.3 kg

3. Basic rack panel (for ZW-series I/Os)

ZW-28KB Power supply module slots 1 1 1 Control module slots 1

Option module slots

O}pfal a peo} o;y - I/O module slots

Screw mounting with four M5 screws {mounting hole; slotted

Mounti thod ourmming me round hole with 7mm diameter)

Outline dimensions (WXHX D}| 4802505 | 480250X25.5 | 24230025 | 157X300*25 Weight Approx. 2.1 kg | Approx. 2.2kg | Approx. 1.3kg | Approx. 1.0 kg

4-37

Page 66 read from a scan by OCR; it may hold reading errors

4. Expansion rack panei (for ZW-series I/Os)

Expansion power supply

1 1 1 - module slots /O module slots 8 4 2 8

. Screw mounting with four M5 screws (mounting hole; slotted

Mounting method round hole with 7mm diameter) Outline dimensions (WXHX D)| 48025010] 31025010 225 X250X10 | 395X250 10 Weight Approx. 1.7 kg! Approx. 1.1 kg Approx. 0.9 kg | Approx. 1.4 kg

4-38

Page 67 read from a scan by OCR; it may hold reading errors

4-5 Input/output modules

[1] Name and function of each part (1) JW-series /O modules

@Retention screw JW-32S

O00 000 Input signa Io 10 o10 indicators O20 020 030 030 040 040 050 050 O60 O60 O70 O70 A BC D ©@)Search module -- - ~ - -- - _©_ © indicator S.U. RUSE OUTPUT 5/12/24 VDC

@Module connector

@Ratings plate

@/O terminal biock

@iFuse alarm

. se NAY. indicat (The diagram is JW-32S) matearor (Display)

(1) Retention screw Use this screw to secure the module to the rack panel frame.

(2) Ratings plate

@) 1/0 terminal block (I/O module with 16 I/O points has a single row terminal block). Use this terminal block to connect I/O cable wires from I/O devices. Since it is detachable from the I/O module housing, you can replace the module without having to disconnect the cable wires from the terminal block.

@) Module connector Plug this connector into the mating receptacle on the rack panel.

(5) /O signal indicators (red LED) These indicator comes on when the input or output signal on the corresponding channel is turned ON. Note 1: At power ON, the input signal indicators on input modules and the FUSE indicator on output modules come on momentarily (approx. 20ms.), but this is not an error.

(6) Search module indicator This indicator comes on if th corresponding module is addressed by a support tool. For more details, see the instruction manual for the relevant JW-series support tool.

@) Fuse alarm indicator

This indicator is provided only on output modules. It comes on if any of the output circuit protection fuses have blown.

4-39

Page 68 read from a scan by OCR; it may hold reading errors

(2) ZW-series I/O modules

Retention screws @)Fuse folders and, fuses

@Guide pins @Retention screws aD DGuide pins,

‘ @ P | == )Card-edge . )Card-edge DIO module connector ia ' cover

@Fuse alarm indicator 7] { connector Rating plate t ou ®Rating plate @Device address bs label

@NVO terminal block ®VWO connector

@®Guide pins

4 is+e - @)Guide pins

@ Retention screws Se : @)Retention screws

(The diagram is ZW-32S2T) (The diagram is ZW-32S2)

4) VO module cover (no cover on ZW-32N1T/32N2T/16S4D/32S1 T/32S2T/32S4T) This cover shields the fuses @) and I/O terminal block (7) to prevent possible shock hazard.

(2) Guide pins (2 pins) These pins guide the !/O module while it is being inserted into a basic or expansion rack panel slot.

(3) Retention screws (2 screws) Use these screws to secure the I/O module to the basic or expansion rack panel frame.

(4) Fuse holders and fuses (no fuses on input modules) These fuses protect the circuits from short-circuit failure.

(5) Card-edge connector Plug this connector into the mating receptacle on the basic or expansion rack panel.

©) Rating plate

@) VO terminal block (ZW-32N2T/32S2T modules have two row terminal blocks.) Use this terminal block to connect I/O cable wires from I/O devices. Since it is detachable from the I/O module housing, you can replace the module without having to disconnect the cable wires from the terminal block.

I/O connector Connect an I/O device cable to this connector.

) Device address label This label is supplied with the control module as an accessory. Affix it according to the slot position of the individual I/O module. The device address represents the 2nd, 3rd, and 4th digits of a relay number.

Fuse alarm indicator

This indicator is provided only on the output modules (ZW-3251T/32S2T)}. It comes on if any of the output circuit protection fuses have blown.

4-40