Calculate the value R of the bleeder resistance in the following formula:
Re< vO V: Power supply voltage | I: Minimum action current of the output module
Then, the capacity of R (W) is
Vig Woe XZ.
5) OFF delay time when the DC output module drives the induced load When the DC output module with a built-in cramp diode is used as a surge killer to drive the induced load of direct current such as electro-magnetic valves and solenoid valves, it may be impossible to complete high-speed switching due to the delay of response, since electric current goes to the load through the cramp diode. In such a case, the DC output module with a built-in zener diode, instead of the cramp diode, could speed up the response.
Output module
[ Ooad DC output module with a built-in zener diode ] L P JW-12S5 a JW-32S8 JW-35S ZW-32S52TD
6) Driving a load current of 1A or more (2A max.) from a JW-series DC output module The JW-125S output module uses FETs in its final stage. It can thus drive a load current of up to 2A if two FET outputs are connected in parallel.
Note 1: For parallel driving, be sure to turn both OUT1 and OUT2 on or OFF simultaneously.
rN OUT1 A OUTI oa Output module OUT2
Note 2: Be sure to use a flywheel diode in parallel with the load.
Note 3: The allowable surge current is not doubled by the parallel connection. it remains 4A(100 ms}.
Surge killer le
Note 4: The JW-32S is not capacity of doubling its output capacity by parallel connection (1A max.)
4-61
Page 90
7) External power source . DC and relay output modules require external power sources to supply DC output modules with output transistor's base current, and relay output module's coil driving current. Connecting an external power source also makes any output module's internal flywheel diodes effective. If a DC output module is used with no external power source connected to it, the internal flywheel diode will remain ineffective and the output transistors may sustain damage.
JW-12S JW-32S ZW-3282 ZW-32S5 7W-882 M De output | Zw-32s2T ZW-35S a wi1es2 odule ZW-3285 ZW-32S2TD name ZW-64S82 Relay output | JW-34S module ZW-16S4D ZW-32S4T ZW-16S4
¢ For DC output modules, one power source should, as a rule, be shared for both the external and load power supplies.
[Example for connrction]
Quiput indicator at
®, J. bal
Photo- coupler tnternat-circuit
Fuse blown
5/12/24 VDC.
In case of JW-12S/382S In case of JW-34S
4-62
Page 91
at Power supply(+) Constnat voltage circuit AQ. Load . 4 62 O - F Ae 1 o> AS. ne, Load Load Output indicator Output indicator t - O -O Load ‘a Load ro ae 5A ;* “ey Load ‘Output indicator Load fe $}__> Bis Output indicator LO (4) (-) Load Aig oe, B19 12/24 VDC} Cpmmen 20 = oe {_._ - Constnat voltage circuit Li) B20 - [| 8/12/24 VDC|Common(-} 4 aut
5} Rack panel SS] 24 VDC terminal block
In case of ZW-16S2/8S2 In case of ZW-32S2
Sitz/24 VOG A1|Commoni{+) . Teen aT Constnat voltage circuit A2] tg s Load 0 [eel [> - O - -* 5 pO + A320 1 _| Load B H Load 1 st EO ( 1 oa Common ' Load ol 1017, uw t+ - O se FO : r Load cE Output indicater O Aiijo boad [5 ' fn 4 bo 1 Load Es | Power supply ‘ommon a | - - - for AC or DC load A1al7 4 7 Contact outpul module TS ES 7, ” Rack panel 24V terminal block a 1 Output indicator G3) betray A20) a P - F be rm Boge | Power supply(-)
In case of ZW-16S4 In case of ZW-32S5
_ oOo - _ - ie a ( i o AO Lae \ T Load xf ~ - - Load ‘ kz 7 Output indicator oa Output indicator Bo : pag cormmon- > [Coma : con ae { ® \ " Power ed : mplvd Load Output indicator \, O a pres _) Load KX Lead & | Qutpul indicator Do : | ca: | dhe 5/12/24 VDC a Or ope a |___- - - Constnat vollage circuit Load Common2 Coe i
5/12/24 VDC tpower supply 2(+ ™ - ~ Constnal voltage circuit
In case of ZW-32S2T In case of ZW-32S2TD
Note 1: External 24 VDC power supplied to the 24 VDC terminal block on a rack panel is shared by any of ZW-8S2, ZW-16S2, and ZW-16S4 module installed.
4-63
Page 92
a. When external supply voltage is lower than load supply voltage (see page 4-49 note ) The load may be activated by a load current (lour) passing through the output module's flywheel diode.
When Vi < Ve: Output module Constant voltage circuit QUT Load Dp { \ L External Load | OUT supply __ oad _|- voltage | vane Vi V2 | COM!
b. Power ON/OFF sequence (see page 4-49 note) When powering up the system, first turn the external power source ON, followed by the load power supply. When turning the system power OFF, first turn the load power supply OFF, followed by the external power source. If this power ON/OFF sequence is not followed, the [oad will malfunction.
So O al Load External () supply | Load | | voltage ve] Vi Ve, 4-64
Page 93
c. When using both DC and relay output modules on one rack panel:
Contact output module
Relay driver
(+)
BC output module
Voltage regulator
Contact output module
Relay driver
DC output module
Voltage regulator
4-65
1) When a DC output modules is used to drive 24 VDC toads, connect the 24 VDC load power supply terminals to the pertinent terminals on the basic or expansion rack panel's 24 VDC terminal block.
2) When a DC output modules is used to drive 12 VDC loads, connect an external 24 VDC loads, connect an external 24 VDC power source (which is separate from the 12 VDC load power supply) to the 24 VDC terminal block on the basic or expansion rack panel, and connect the negative terminal of the terminal block to that of the terminal block on the basic or expansion rack panel, and connect the negative terminal of the terminal block o that of the load power supply. The separate 24 VDC power source is needed for driving the relays 1 within the relay output modules.
Page 94
Note: Using the JW-1 2S/JW-32S/ZW-32S2TD output modules with zener diodes as surge suppressors can prevent load malfunction due to loop current. Also, they may be used in the circuit with separate external and load power supplies as shown:
Output module (ZW-32S2TD)
Constant voltage Ty circuit Load Zener diode External C) ? T supply Load i Our | voltage | voltage 1avo0 | ea COM
8) Driving micro loads with relay output modules The relays used in relay output modules are suited for driving relatively high-power loads. For low-power loads rated, for example, at 24 VDC , 10mA, the reliability of the relay contacts will be reduced. For low-power applications, we recommend that you use DC output modules with transistor outputs. If the use of low-power relay contacts is necessary, use external low-power miniature relays with high contact reliability and drive them from either a DC or relay output module as shown:
Control object RY
Control object RY ° T Le Ney,
DC output module
4-66
Page 95
9) Life of relays of the relay output module The relay's life of the module (JW-34S, ZW-16S4, ZW-16S4D, ZW-32S4T), which uses a relay in output circuit, varies depending on the kind of loads (difference of the power rate of the signal on the contact point is AC or DC and its current value). The following shows characteristic curves of the relay contact point.
\ ’ 20 iN Y aN ocHy =T=0 \ YY. \ ACIOV NG COS¢=1 400
70
N N, 7) \ Upper COS¢=1 aN . Y)
‘ \ \ X N
50
30
Switching life (>< 10,000 times)
DCHV T=7 ms \ ‘“ 3 s \ 4 . o 0.4 0.3 05 07 4 2 3. 4~=«5 COS: Power factor Switching current (A) T: Damping time costant
Note 1: The above chart shows standard values. Depending on the environment of usage (ambient temperature and humidity), different life may result.
Note 2: When the signal to the contact point is DC, the life of relays varies according to the load rise characteristics (time constant: T) of the load. The load rise characteristics of the load after the contact point is turned ON are determined by inductance: L and resistance: R
(ot
For the time constant of the load used, see below: In case of resistance load: T< ims In case of small size relay: T=7ms In case of large current L load and magnet: T = 40ms In case of the L load with a diode for surge countermeasure, the life of relays may be similar to the case of T < ims.
Note 3: When magnetic value containing rectification current (diode) is load, full-wave rectification should be used. Half-wave rectification makes the life shorter.
Note 4: Use the relay output module, with the contact switching life of more than 100,000 times and within the current capacity of less than 2A.
4-67
Page 96
10) Fuse blown detction on JW-series output moduies
1e| JW-12S, JW-32S, JW-33S, JW-35S
The JW-12S, JW-325S, JW-33S, and JW-35S DC output modules have an internal fuse failure detection circuit as shown below. Due to the circuit configuration, it can detect fuse failures only if load power is present at the module outputs. If no load power is present, the fuse indicator light on the output module and fuse OFF piug (7363) to the control module will both remain OFF, even when a failure exists.
Output indicator
Extemal load
Photo- coupler
Internal-circuit
Fuse blown detection circuit ween ---------- +t
JW-12S/JW-32S
Output 1 indicator! }® ~ K - >
Pholo-coupler ~ internal-circuit
Fuse blawn detection circuit
HH
JW-33S
4-68
Page 97
[6] Precautions for operating the special I/O module 1) Scan time (ZW-I/Os) ZW-series special I/O modules perform data and command transfer with external devices through i/O relays controlled by an internal microprocessor. For this reason, each scan time must be set longer than the internal processor's execution cycle time. If it is set shorter than the cycle time, a data transfer error will occur. (Unit for processing time : ms)
2 Hate: Sp Me ee Mi : : Modet name }>. -times. = High-speed ZW-1HC5S 2 Pulse catch module ZW-14PC2 ie) counter module
High-speed ZW-1HC6 fe) Pulse output module ZW-1PO02 2 counter module
Analog input module ZW-4AD2 2 Positioner module ZW-112PM 3 Analog output module ZW-2DA2 2 Serial /O module ZW-232SU
Interface module ZW-10DU 6
Note 1: JW-series special I/O modules need no consideration for scan time setting.
a. Checking scan time setting The current scan time setting can be checked by reading the contents of system memory address #0032 and #0033:
#0032 | Lower BCD digit
System memory #0033 | Upper BCD digit b. Setting scan time (constant scan) If the preset scan time is shorter than the special I/O module's execution cycle time, set system memory address #0226 to the appropriate value:
Zero cross 07367| Set in #0226 | PC's scan time OFF Invalid((BCD} | Zero-cross sync.
Zero-cross sync. (minimum scan) Scan time of 01 to 99ms
ON 00(BCD)
ON 01 to 99(BCD)
2) Special I/O module installation Special I/O modules handle high-frequency pulses and/or low currents. Do not install them in slots next to slots where relay output modules (JW-34S/ZW-16S4/ZW-16S4D/ZW-32S4T) are installed.
Relay output module Special I/O module
3) JW-series special I/O modules
(I/O relay) EET 4 For control output i/O operations through JW-series I/O modules access two data memory areas for I/O relays and data registers. For more information, read the programming manual, section 4-1.
(Data register)
For measure data
4-69
Page 98
4-6 Power supply module (JW-1PU: Approved UL/CSA) [1] Name and function of each part
@Retention screws
@)Power indicator if
©Front cover r - |
@)Rating plate
1 ey
®Halt output fuse | @)Terminal block a SHORT Short piece insert position et | | using 200 VAC, ™ a SHORT [| | Short piece insert position - OROAC using 100 VAC
LITT T@ owen _ NEUTRAL. _ RUT terminal | Power supply input MANAG LY, LIVE terminal terminal GND 5 ™ Ground HALT ; _ OUTPUT | 3 7 Halt output terminal MD-2MVAC LJ Note 1: For fuse replacement procedure, see page 11-5. ZO}
Terminal block pin description (1) Retention screws Use these screws to secure the power supply module to the rack panel frame. (2) Power indicator Comes on when +5V power is available. (3) Rating plate @) Terminal block (8 pin) Connect cable wires for power, ground, and the halt output signal to this terminal block. Also used for input voltage selection. 6) Halt output fuse (1A normal class) Use a glass-tubed fuse with 250V, 1A rating for the halt output circuit. ) Front cover Remove this cover to gain access to the fuse.
4-70