For the Sharp ZW-32IO2 and Sharp ZW-32S2T
Page 151
6-1
Precaution for wiring
Follow the below instructions for wiring:
1) Separate power line and I/O lines of the JW50H/70H/100H from high voltage lines and power lines as far as possible. Do not run power lines and I/O lines in parallel with high voltage or power lines.
2) For the I/O expansion cable and wiring the 5 VDC cable, use supplied accessories for the I/O expansion cable. ,
3) Do not install the I/O expansion signal cables and 5 VDC power cables (Note 1)
4) Don't run the I/O expansion cable and the 5 VDC cable inside a duct.
5) Cables connected to I/O modules should be routed in such a manner that the indicator tights on the modules are not hidden.
6) Use twisted cables of over KIV 1.25 square for connection to the primary power input terminal of the power supply module.
7) Use cables of over KIV 0.5 square for wiring from the relay terminal block of the control panel to the input module.
8) Use wires with KIV 0.75 or larger gauge for the wiring from the cabinet's bulkhead terminal block to the output modules that drive high-power loads such as solenoids. Use wires with KIV 0.5 or large gauge for lighter loads.
9) Use wires of over KIV 1.25 square for wiring from the relay terminal block to input/output equipment.
10) When the whole factory site is grounded for high electricity and not suitable for the grounding of the JW50H/70H/100H, connect the GND terminal of the JW50H/70H/100H with just the board ground.(See the next page.)
11) Use critmp-type terminals for all connections to the PC's terminal blocks. For suitable sizes of crimp-style terminals, see the following table.
: Be pac
JW-series I/O modules 7.3 M3.5X7 self-locking screw 8/16-point 7.7 M3.5X8 self-locking screw
ZW-series |_Modules
VO modules | 32-point 7.5 M3.5X8 self-locking screw modules
Power supply module 7.4 M3.5 X6 self-locking screw
Basic rack pane! 8.5 M3.5X8 self-locking screw
Rack panel 8 M3.5 X8 self-locking screw
Expansion rack panel 8 M3.5X8 self-locking screw
Expansion power supply module 7.3 M3.5X8 self-locking screw
6-1
Page 152
12} Wiring with noise countermeasures Malfunctions are often caused by noise interference. This paragraph describes how to improve the system's immunity to noise interface and to prevent possible malfunctions resulting from them. Malfunctions due to noise could result from more than one cause or from a cause which cannot be analyzed in quantitative terms. Attempt appropriate field actions case-by-case by referring to the following typical countermeasures:
(1) Grounding Grounding has two purposes; to protect operators from electric shock and to prevent malfunction by noise. The grounding for noise prevention is shown here. 1) Don't use a common ground for the JW50H/70H/100H and other device. When the GND cable of the JW50H/70H/100H is also used for grounding for other device, noise might come into the JW50H/70H/100H from other device.
Other
PC device
“Common: grounding Bad example: Don't use the GND line of the JW50H/70H/100H for grounding of a motor or an inverter.
Control panel
Motor (heavy load}
PC Inverter SS ground ground CE = - - - } 9 9 f Ground [Terminal block [ Class-3 grounding
Countermeasure 1: Separate grounding for each of the PC, the motor and the inverter.
Motor (heavy foad)
PC Inverter ground ground 9 9 a} qe erminal block Less than 5m { | =
Note 1: Use a twisted wire of over 2 mm? sectional area and less than 5m long in grounding the PC for the noise prevention purpose.
Note 2: If sharing a single ground wire with an inverter cannot be avoided, use separate ground wires to the grounding points as shown:
PC Inverter ground ground 2 9 d L ITerminal block Less than mf |
6-2
Page 153
Countermeasure 2: When a separate ground point is not available for the PC : Connect the PC's grounding post directly to the cabinat chassis on which the basic rack panel is mounted.
. Motor (heavy load) Ground direct PC Inverter, - - ) to chassis ~\__| | ground ground, - 4 ° aE
* Terminal block Ground
Note 1: When grounding the PC directly to the cabinet chassis, note the following points : ¢ Use the minimum length of wire of necessary to connect the power supply module's grounding post to Power supply module the rack panel mounting screw.The same wiring manner should be used for the expansion rack panel.
Basic rack panel i=)
Ground cabie |_- Ground hI
+O
Drop the grounding cable into the ¢ Install firmly the basic rack panel and the expansion __ fastening screw on the basic rack panel.
rack panel on the chassis of the control panel and make sure of the electric conductivity.
Conducted, ,-77~ 7 Chassis
2 - ~__ Expansion rack panel ap Basic rack panel
¢ Where the control panel itself is grounded, do not wire between the grounding point and the GND terminal of the JW50H/70H/1 00H.
Don't wire here
Ground point of the ground
+O pins
Reference: Note for fitting the JW50H/70H/100H on the control panel door. *Ground from the GND terminal of the JW50H/70H/100H to the door. *Use a twisted wire of over 2 mm? sectional area for grounding cable of the control panei from its door (less than 50 cm.)
| PC
Door Connect the PC ground cable rN with the door.
Connect the door ground cable with the control panel chassis.
is
Control panel - ]|
6-3
Page 154
(2) Countermeasure of noise from power supply line The AC power supply input noise resistance capacity of the JW50H/70H/100H is 1000 Vp-p. When any noise over this limit is possible to come through the power supply line, install an insulation transformer.
Countermeasure: Install an insulation transformer Noise has a high frequency of 100 KHz to 2 MHz, which should be blocked by a transformer.
Insulation transformer PTs PC
Vaan AC power supply | B) ooo | AC input Lo
Note 1: When using an insulation transformer, note the following points: * An insulation transformer with static electricity shield can also prevent noise by static coupling.
* Install and insulation transformer near the power supply input of the control panel in order to block noise at the entrance of the control panel.
Control panel
Insulation transformer
AC power supply, - - - I IE OOOO. ”°
Twisting
Terminal block
¢ Use two twisted wires in the primary and secondary sides of the transformer.
* Choose the insulation transformer of the capacity of more than 20% higher than that of the rated load. When a transformer of the same capacity as that of the rated load is used, a primary input voltage might exceed the transformer rated capacity and become dangerous state such as emitting smoke.
* When a large-capacity transformer with higher voltage in the secondary side is chosen, we recommend to install a intermediate voltage tap.
110V
100V
Primary side 90V OV
¢ With particularly large noise, several transformers can be installed, not only to the power supply input of the JW50H/70H/100H but also to the load and AC input.
Breaker Breaker 56 oO 5 aE For PC power supply AC power supply yO aie For load
5 O- - - Ile For PC input ce)
1e)
oO
6-4
Page 155
(3) Safeguard from lightning Below are countermeasures in case when the factory facilities are located far from residential areas and that effects from induced lightning {induced voltage by lightning strikes) are expected. Note, however, that they are not the measures for direct strikes of lightning. In some cases, the voltage of the induced lightning may go beyond 4000 KV. Therefore, the purpose of these countermeasure is just to minimize the damage on the device.
Ax wohKe
Factory
Countermeasure 1: Install a surge absorber on the receiver panel of commercial electric power as protection from induced lightning. Different models should be chosen according to the facilities load and power supply voltage. For your reference, below is a wiring diagram of the outdoor type cubicle for 1.7 KVA.
Main breaker
Breaker Transformer
5 Loin LN {for voltage reduction) PC Oo: 0 Oo Oo O ; s+ 3I|E100 vac | AC input 250 VAC input v oun oN O Sy For other device
XK Surge absorber
E ad, | Special class-3 grounding (less than 10 ohm)
Class-3 grounding
Note: Note the following when wiring.
* The ground of the surge absorber is the special class-3 ground (less than 10 ohm ground resistance) and should be separated from the ground of the JW50H/70H/100H. (Class-3 grounding.)
« Instail the main breaker before the surge absorber.
* The followings are known surge absorbers in the market. Different types for different power supply voltages.
Varistor voltage: 250V + 10%
Surge resistant volume: 100 VAC ERZ-A20PK251 7 ; COON (8X 20us)
Energy resistant volume: 15 Joule
Matsushita Electric Co.,Ltd.
Varistor voltage: 500V + 10% Surge resistant volume:
1,500A (8 X 20us) Energy resistant volume: 70 Joule
200 VAC ERZ-A20PK501
¢ Use the ground wire of over 3.5mm? section area for the surge absorber.
6-5
Page 156
Countermeasure 2: Underground wiring as a countermeasure of lightning. When communication cables and input cables of the JW50H/70H/100H go out of a building, place them underground. Provide junction for input/output signals using relays. 1. Underground cabling In a lightning weather condition, the atmosphere is electrically charged and a wiring in the air induces a voltage of over 24 VDC. Therefore, place the wiring under the ground.
Outside panel
60 cm or 120 cm below ground level
As for the depth of cable installation, refer to local regulations.
2. Relay connection for the input/output signals using relays. The relay isolates the effects of lightning and minimizes the damage.
PC
Relay EP Input | COM
65 Output K - 9 COM |
(4) Wire of signal cable for expansion When turning ON/OFF of the magnet switch installed near the JW50H/70H/100H and the signa! cable for expansion, high noise and high voltage may occur to give bad effects on the operation of the JW50H/70H/100H. Therefore, for prevention of the noise occurrence, insert a noise killer, such as a varistor, at the contact point of the magnet switch. Do not place the signal cable for expansion and the 5 VDC cable inside the duct, through which input/output signal lines and power lines are running.
Signal cable for expansion
5 VDC cable
Magnet switch
Varistor Wiring duct .
i! Input/output signal lines ~~.
6-6
Page 157
(5) Precautions for input/output signal wiring 1. Relay output module installation if a relay output module is used to switch heavy loads, switching transients can have undesirable affects on the operation of the CPU board, option module, and/or special modules. To avoid this, do not install the relay output module next to these modules.
Example for JW50/70/100, JW50H/70H/100H (ZW-28KB)
Option Do not install module a relay output module next to a option module.
Note : When a relay output module is loaded with inductive loads, use a varistor or C/R filter across each set of relay contacts to absorb transients (see page 73.)
2. DC input module When extending the external line of the DC input module for more than 100 m, use shielding wire. Even in case of less than 100 m extension, shielding wires should be used under certain conditions. Do not forget to connect the shield of the shielding wire with the ground of the JWS50H/70H/I00H.
pep A
Note : The outer shield conductor may be grounded at either or both ends depending on the situation.
3. AC input module Do not use the outputs from a constant voltage transformer and an AC regulator, for the AC power supply to the AC input module. When the constant voltage transformer and the AC regulator are used, the module signal could be turned ON even with an input voltage less than the rate voltage due to a high distortion rate (10 to 50%) of alternative current waves. The power supply to the AC input module should have a distortion rate of less than 5%.
PC
A . Switch AC input “| Constant voltage O° Input transformer Common ~ V
6-7
Page 158
4. Wiring with power line
Do not run the input signal, output signal and communication cables of the JW50H/70H/ 100H near and in parallel with the power line.
¢ When input and output signal cables are extended over 100 m, make separate wiring for the input signal and the output signal of JWSOH/70H/100H.
U
C
Separate wiring
Input
‘
Output When longer than 100m
= Input Output
Make separate wiring for the input signal and the output signal of the JW50H/70H/100H from the power line. Particularly with the power line for the inverter and the servo driver, do not place signal wires inside the same duct or pipe with the power line, even if they are less than 100 m.
in the same duct PC Inverter
| gy
\ PC Inverter |
6-8
Page 159
6-2
Wiring for JW-1PU power supply module
Open the terminal cover and connect the cables to the terminal block as shown :
In case of 100 VAC input Terminal block cover
Pp SHORT A®)))) 2 100 VAC 3 41 INPUT or 200 VAC POON ‘ " 5 Terminal block cover GND 6 3 " ine 8 aT DC relay co
The coil rating must conform to the power supply voltage.
¢ When a DC output module is used, connect an AC relay coil to the halt output terminals and insert the relay contacts into emergency stop circuit.
Note 1: Apply a torque of 1.18Nem or less to the terminal screws.
Note 2: Up to three halt output circuits can be connected in series. For more circuits, use an intermediate relay.
Note 3: For a line voltage of 200 VAC, the metal short on the terminal block must be placed in the 200 VAC position. If 200 VAC power is applied with the line voltage selection ieft at 100 VAC, the power supply module will sustain permanent damage.
In case of 100 VAC input sca SHORT Ya ' 100 VAC ; SSA 5 : “ 6 Halt output internal circuit
6-9
Page 160
6-3 Wiring for JW-2PU power supply module
Open the terminal cover and connect the cables to the terminal block as shown :
Terminal block in case of 24 VDC input ©over
6) / | ; Do not use. ; INPUT U1) ° 24 VDC >Does . 4 “ © 5 Terminal block cover __GND ; = - - _f + : line 3 fat DC relay <p
The coil rating must conform to the power supply voltage.
«Connect a DC relay coil to the halt output terminals and insert the relay contacts into the emergency stop circuit.
Note 1: Apply a torque of 1.18Nem or less to the terminal screws.
Note 2: More than one halt output circuit cannot be connected in series. For serial connections, use relays.
Note 3: Make sure that the input power and halt output are connected with the correct polarity. Cross connection will result in permanent damage to the power supply module.
Halt output internal circuit