11-1 Periodic check
[1] Check items The following lists daily and periodic check items required to maintain the programmable controller in its best condition :
(1) General check
Check OWK/NG judgment | Remarks Rts Dee Criteria. ot ee Ambient temperature Check that all of these parameters 0 to +55 degrees Ambient humidity fall in the ranges of specifications. 35 to 90% RH Where the PC is installed in a Atmosphere . _ No corrosive gas Check for cabinet, the temperature within the condensation Vibration cabinet should be within the allowable None impact range.) None
(2) Control module
Ssese eae ee SU Cntera. Fault indicator Visually check FAULT indicator Off Battery Does battery require replacement? Within the replacement | For RAM operation interval? only is module firmly secured to rack
No loose module panel?
Module installation Are terminal screws firmly tigntened? | No loose screw
Are all I/O expansion cable plugs firmly clamped? Firmly clamped
(3) Program
Check JOKING judgment rite: criteria eee Must be labeled at M Is the memory module model being an easy-to-read Needed for CPU emory capacity used labeled? location inside the board replacement. cabinet. Does the program diskette require No loose module 1 disk rewriting? No loose screw lo is rey Does the data diskette require : Not needed if data rewriting? Firmly clamped memory contents g: need not be stored.
Note : For easier program maintenance, we recommend that you store your programs on floppy disks.
Page 193
(4) /O modules
JW-11N 85 to 132 VAC JW-31N DC input modules : Wao 10 to 26.4 VDC ‘WW _34N 200 VAC input modules: . 170 to 264 VAC JW-13N DC output modules : JW-12S 4.75 to 30 VAC JW-328 DC output modules : _ 10 to 30 VAC JW-35S 200 VAC output modules :|} JW-13S 15 to 264 VAC JW-33S8 Conatct output modules : AC: 264 VAC or less JW-34S DC: 30 VDC or less Verify that input ; ; and output module's ote as Hive modules: ZW-16N1 I/O signal voltages fall 700 VAC inout modul within the specified INpUL Moduies: ZW-32N1T ranges. 80 to 121 VAC DC input modules: Note 1: 10 to 30 VDC ZW-16N2 Input or output Turn-ON voltages are D . . ZW-32N2 es P ata input modules: It specified for input ZW-32N2T voltages ae hiles, 10 to 26.4 VDC ZW-64N2 200 VAC input modules: Note 2: 160 to 242 VAC ZW-16N3 For the ZW-8S2 and 100 VAC output modules: | ZW-8S1 ZW-16S2 output modules, } 15 to 121 VAC ZW-16S1 also note the external ; power sources’ voltages. et ae Van modules: | 7yw_32S1T DC output modules: aWneS? 10 to 30 VAC (Note 2) JW-6482 Data output modules: WV aoeoT 200 VAC output modules: - 15 to 242 VAC ZW-16S3 Conatct output modules: 7 AC: 240 VAC or less ZW-32S5 DC: 30 VDC or less Source-type data output modules: 4.75 to 30 VDC. | 4V-82!02 Pulse catch modules: 12/24 VDC or 10.8 to 26.4 | ZW-14PC2 VDC Pulse output modules: 12/24 VDC ZW-1PO2 Verify that all modules are firmly secured to the No loose module Installation rack panels.
Verify that all terminal screws are firmly tightened.
No loose screw
Page 194
(5) Power supply module and expansion power supply module
Verify that the primary input voltage Primary input voltage | measured at the power receiving -15% to +10% of the 1 terminal block is within the range ratings specified for each module.
Verify that the module ts firmly
No loose module secured to the rack panel.
Installation
Verify that all terminal screws are
No loose screw firmly tightened.
Note 1: The rated primary input voltage for the JW-1PU power supply module is 85 to 132 VAC or 170 to 264 VAC. That for the JW-2PU power supply module is 20.4 to 32.0 VDC.
[Reference] Notes on the support tool connector
* Mode changes for the JW70/100 and JW70H/100H can be performed via the support tool connector or the communication port (see page 4-103).
* If write operations are ineffective through the support tool connector on the JW70/100, it is possible that the write mode of the PC has been changed through the communication port. If this is the case, set the mode again. The write mode switches upon receiving an instruction from the port for which the mode was set. The programmer's mode display does not change, even if the mode is changed through the communication port.
«When write operations are ineffective, monitor memory location #0100 in system memory.
PG
Support tool PC connection connector . 76543210 Write #0010 | [ | 1 | Communication Write disable 0 0 Run j Write enable 1 1 Stop
Page 195
11-2 Battery replacement
When the programmable controller is run in the RAM operation mode, its internal backup battery requires periodical replacement before it is fully discharged. Battery replacement should be done with the power supply to the control module left active.
1) Power supply module name DUNT-5784NCZZ
2) Replacement procedure
Prepare a replacement battery pack.
Remove the battery compartment lid from the control module.
Disconnect the used battery's harness plug from the CPU board's connector, then plug the replacement battery's harness plug onto it within five minutes.
Battery cover
Reptace the battery compariment label.
96 ¥
©
Note 1: Be sure to replace the battery replacement label. Take care not to lose the battery compartment lid.
Note 2: To prevent rupture or electrolyte leakage, never short the battery terminals, nor recharge, disassemble, or heat the battery, not throw it into a fire.
Page 196
11-3 Replacing a fuse
1) Replacing a fuse (halt output fuse) in the power supply module (1) Objective fuse
JW-1PU Glass-tubed minuture fuse (normal blow), 250V, 1A(5.2% x 20), approved UL/CSA
JW-2PU Glass-tubed minuture fuse (normal blow), 250V, 1A(5.2% x 20)
(2) Replacement procedure (halt output fuse)
Track down the cause of fuse failure and repair. cE
250V, 1A (normal class)
4 | Prepare a replacement fuse.
|
Turn OFF the halt output circuit power supply.
!
Remove the front cover from the power supply module.
Remove the fuse holder with a slot screwdriver.
Fuse holder
| Front cover
| Replace the fuse.
Remount the fuse holder into “| the module.
Slot screwdriver
¥
Turn ON the halt output circuit power supply.
External device operating normally?
|!
End Check the circuits connected to the halt output.
Fuse
No (fuse blown out again.)
Fuse holder
Note 1: Before replacing any fuse, be sure to track down the cause of the fuse failure. If you replace one without identifying the cause, damage to module's internal circuitry may result.
Note 2: If the power supply module's internal AC line fuse is burnt out, call your local Sharp service office in Japan. Do not attempt to replace this fuse as its failure results from a problem in the power supply module's internal circuit.
11-5
Page 197
2) Replacing a fuse in an I/O module (1) Replacement fuses Exchange a fuse since you have found a solution of the cause (external wiring, output module failure), when the fuse blown.
Glass-tubed miniature fuse with 125V rating(Class-B normal blow)
SA
Module name
ZW-32102 ZW-14PC2
ZW-1HC5
ZW-14PC2
ZW-32102 ZW-1HC5
ZW-851 ZW-8S2 ZW-16S1 ZW-16S2 ZW-3282 ZW-32S5
(2) Replacement procedure
Fuse
Prepare a replacement fuse. | a
Turn OFF the external power supply to the I/O module.
Turn the PC power OFF.
Track down the cause of the fuse failure.
Remove the front cover from the I/O module.
Remove the burnt out fuse from its holder.
i install the replacement fuse in the holder.
|
Turn ON the external power supply to the I/O module.
[Turn ON the PC power.
Check if modulé is turned ON or OFF(from programmer).
| On (normal)
¥
Pull cover while pushing here with your thumb.
END
Check external device's circuit.
Glass-tubed miniature fuse with 250V rating
(Slow blow)
te
5A
ZW-16S4
| 5A
Alarm fuse
Reted current | 3.24 3.2A Module | ZW-32S1T | ZW-32S2T Fusetype = | HP-32__| HP-50 Alarm fuse 5.0A ZW-32S2TD MP-50 Glass-tubed miniature fuse (Class-A normal biow) 8A 4A JW-12S JW-13S JW-32S JW-33S JW-35S SO(A)-8A | SO(A)-4A 125A 250A
Note 1: Only the ZW-32S1T AC output module and ZW-32S2T data output module contain alarm fuses. If any alarm fuse is burnt out, the fuse light on the corresponding module will come on.
Note 2: Before replacing any fuse, be sure to track down the cause of the fuse failure. If you replace the fuse without identifying the cause, damage to the module's internal circuitry may result.
11-6
Page 198
3) Replacing a fuse in an expansion power supply module (1) Replacement fuses Glass-tubed miniature fuse with 250V rating
ZW-100PU1
Module ZW-100PU2 ZW-100PU1 ZW-100PU2 Application Halt output circuit Power line Power line
(2) Replacement procedure
Track down the cause of fuse failure.
Prepare a replacement fuse.
Turn OFF all the external circuits that connect to the module's halt output.
| Cover retention screw <->,
Turn OFF all the external circuits that connect to the module's halt output.
i
Remove the cover from the Power supply module cover module.
Install the replacement fuse in the holder.
|
Turn ON the external power supply to the I/O module.
Halt output circuit fuse (1A)
Power line fuse
Remove the burnt out fuse from its holder.
|
Install the replacement fuse in the holder,
{
Turn OFF all the external circuits that use the halt output.
t
[Turn ON the PC power. |
Fuse burnt out again?
Yes
¥
Remount the front cover on If the halt output circuit fuse is burnt out, the module. check the circuits that connect to the halt i output. End |
Note 1: Before replacing any fuse, be sure to track down the cause of the fuse failure. If you replace a fuse without identifying the cause, damage to the module's internal circuitry may result.
Note 2: If the expansion power supply module's internal AC line fuse is burnt out, call your local Sharp service office in Japan.
Page 199
11-4 Check at error
[1] Precondition of check flow This troubleshooting describes the countermeasure method (replacement of defective module and subsequent restoring method) in the event the system running normally so far suddenly breaks down. Therefore, the following cases are excluded. 1. Trouble due to error in initial setting when starting up the system (system memory, parameter, setting switch, etc.) 2. Momentary failure due to transient error due to noise or other effect (irreproducible trouble). 3. Trouble due to effect of ladder program (customer's application). See each instruction manual for troubleshooting of special /O module and option module with this manual.
[2] Prepare for causing trouble 1. Be sure to keep backup for program memory and system memory When the control module is abnormal, the current program memory and the like may not be saved by the support tool, or the saved data may be incorrect. Therefore, store the latest program memory and backup of system memory always in the floppy disk (FD). In the case of ROM operation, store the backup in the FD, too.
2. Prepare for support tool at hand Prepare the support tool (JW-50SP, JW-100SP, eic.} that can load/save of hand-held programmer of program(JW-14PG, etc.).
3. Prepare for spare parts Prepare always a spare of each module to be ready for error.
4. Prepare for setting table of each module For prompt troubleshooting, prepare the "switch setting table and I/O relay allocation table of each module. Prepare also the parameter setting table in the module which requires setting of parameter aside from switches, such as special I/O module and option module.
[3] State of LED In the event of error, check the LED(RUN, FAULT) of the power supply module and control module, and remedy according to the check flow depending on the state.
RUN | Contents _ OFFO Disable detection error ON@ | ON®@ | by self-diagnosis Check How 1 11-9 Blink© | OFFO OFFO | OFFO | Power supply error Check flow 2 11-15 Blink© | OFFO | Halt mode Check flow 3 11-16
Support tool error; Check flow 4 11-16 Detectable error for} Halt output error | Check flow 5 11-17
ON @ | OFF F ;
0 self-diagnosis Input relation Check flow 6 11-18
Output relation Check flow 7 11-19
Page 200
[4] Check flow
| Monitor system memory #0160 using a hand-held programmer. |
(Operation in hand-held programmer) fgyy)__fsasn Es cin || sys | _ _ | MNTR : 5 Se , - the-ope
Memory 24 Parity check @Load the programs to the program memory error again. (2)Replace the memory module. ()Replace the control module. (Reference) You can check the parity with the hand-held programmer and obtain the program address ofparity error. [Hand-heid programmer key-in procedure] Set the program mode. (Omit the steps when the program mode has been set.) Continuous check {= =e Hee 23 System @)Load the system programs to the system memory again. setting y @Replace the memory module. check (Replace the control module. Command (Load the programs to the program memory again. 24 code check ‘2/Replace the memory module.
@ Replace the control module.
(Reference)
You can monitor the system memory #0052 to #0054, and obtain the defective program address.
#0054 #0053 #0052
(File Nol {Tt ttt JEP Tr
| HI Low. I I j 6th digit 5thdigit 4th digit 3rd digit 2nd digit 1st digit Program Check the setting of RAM/ROM changeover switch of memory 25 ROM check module and set the switch (to the ROM position). @®Check the setting of EPROM/EEPROM changeover switch of memory module and, if it is improper, set the switch again. @Check the setting of system memory #0255 (which selects the ROM operation) and 0256 (which selects the ROM type)and, if 26 Data it is improper, set the switch again.
ROM check @Check whether the ROM program capacity (setting of system memory #0204 in ROM) is not larger than the program capacity of memory module, and if it exceeds, set the program ROM size again.
Pro (@)Replace the ROM(in which programs have been written).
gram 27 ©)Replace the memory module.
ROM size check @Replace the controf module.
VO (Re-execute the 1/O module registration. Then, set the system
28 registration memory to #0247=03.
table check | (@ Replace the memory module.
vO @)Replace the contro! module. 29 table parity check
Page 201
CPU error 32 RAM check | (Replace the memory module. (RW) (2)Replace the control module. 33 Parity check | (Replace the control module. Hardware 35 check Mounted j - /O error 40 module check Mi When using JW-/0 (Monitor the system memory #0247. If any value other than 03 Input data is set, select the halt mode and write 03, at #0247, then start a parity check operation. , Output dat Note 1: if you turn OFF and ON the power supply with the 42 hi rk ata automatic I/O module registration set, the error detec-enec tion status may change. Therefore, be sure to check it before turning OFF the power supply. 44 | VO data bus | @ Monitor the system memory #0046 and obtain the I/O rack, slot where the error has been detected. 45 V/O signal 765 432 10
#0046 Lol4alalitela att \ Rack No. Slot No.
(@)Check whether the I/O module of the rack, slot monitored in the above (2) has been securely mounted.
@)Check whether the I/O bus expansion adapters (1EA/2EA) of the rack monitored in the above @) has been securely mounted.
(Check whether the setting of the switch of 2EA is proper. (Check the setting of switch No. 0,8 and 9 and check for dupli-cate set values.)
(©)Check wheter the I/O expansion cables of the rack monitored in the above 2) has been securely connected.
(Check whether all the termination plug slot has been properly attached. (8)Check whether ail the modules and I/O expansion cables have been securely mounted and attached. (9)Replace the I/O module checked in the above @). (Replace the 1EA/2EA checked in the above @). (Replace the 1/O expansion cables checked in the above 6). 42)Replace 1EA. (Sequentially replace all the JW-2EAs. (4Sequentially replace all the I/O expansion cables. (5)Replace the rack panel of the rack monitored in the above @). 46)Replace the control module. @?)Replace all the I/O modules sequentially from the one nearest to the control module. (8)Replace all the rack panels sequentially from the rack 0. Note 2: If the slot selected at #0048 is the slot of the top module mounted in the rack panel, EA or I/O expansion cable may defective with high possibility.