The text of a manual · part 3 of 30

Programmable controller New Satellite JW, Model name JW50H/70H/100H, User's Manual/Hardware version, pages 10 to 12

Pages 10 to 12 of 254: Chapter1. Overview; Chapter2. Safety precautions

The original document is the PDF (8.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sharp ZW-32IO2 and Sharp ZW-32S2T

Page 10 read from a scan by OCR; it may hold reading errors

This manual describes the specifications and operation of the individual functional components of the new satellite series JW50/70/100, JW50H/70H/100H.

As the nucleus of a new generation of flexible automation systems, the PC provides enhanced features and speed in data communications, information processing, and system maintenance.

Features 1. Faster processing speed, increased number of timers and counters and enhanced application instructions

Compared to the JW50/70/100, the JW50H/70H/100H features the following enhanced functions. * 50% increase in processing speed

« Increase from 512 timers and counters to 1024 _

¢ Expansion from 116 application instructions to 157

. Enhanced data processing capability

* Data width has been increased to 8/16/32 bits.

« Data retrieve, replace, insert, delete, ASCII conversion, and other data manipulation instruction have been enhanced.

* In addition to the existing general I/O refresh instruction, another features, these instructions allow increased processing throughput.

. Enhanced communication features

* The enhanced satellite net capabilities have enabled the PC to start up a communication sequence with a dedicated send/receive instruction.

¢ Equipped with a SUMINET (note) interface, an optical local area network.

* The satellite I/O link allows the PC to be connected to scattered factory automation devices through a single twisted-pair cable to each device. This significantly reduces field cabling manpower requirements and installation overhead.

. Enhanced I/O bus

* Data is transferred between the PC and spacial I/O module during the I/O refresh. This eliminates the need for a separate data transfer program.

* There is no restriction on device address allocations to I/O modules, provided they are used in separate cages.

* The I/O bus extension adapter allows an expansion rack panel to be situated up to 50m from the PC rack panel, enabling real-time remote i/O operation. Since a programming terminal can be connected to the expansion rack panel, the program can be monitored in the field, where the expansion rack panel is installed.

* The enhanced diagnostic features include input data parity check, output data check, installed module check, and others.

. Reduced burn-in overhead

« Remote monitoring and processing are allowed across networks with different hierarchical levels.

¢ Extensive debugging features available include: sampling trace, break monitor, step-by-step execution, forced I/O ON/OFF control, and others.

* On an error condition, the system automatically registers the error code, time and data.

* A support tool allows replacement of any I/O module, with the exception of special /O modules, with the system power left turned ON.

¢ I/O indicators allow the I/O modules' device addresses to be checked at a glance.

(Note) SUMINET is a trademark of Sumitomo Electric Industry Co., Ltd.

1-1

Page 11 read from a scan by OCR; it may hold reading errors

When handling or operating the PC, keep th following precautions is mind: @ Installation Avoid keeping the PC in the following conditions: * Direct sunlight or temperature extremes outside the range of 0 to 55 degrees. ¢ Relative humidity which exceeds 35 to 90 %. No condensation due to rapid temperature variation. ¢ Corrosive and flammable gases. ¢ Vibration or hard jolts. M@ Grounding « Prepare a class-3 grounding of the PC separately. Never co-ground with high power equipment grounding lines (see page 6-). H Module Installation ¢ Securely fasten the retaining screws in each module. * Firmly connect cable (I/O expansion cable), connecting to the basic/expansion rack panel. Confirm connectors are fastened prior to supplying power. Looseness may cause malfunction. * Each module has a ventilation hole to allow for cooling. Do not block the holes. M Wiring ¢ Take special care to avoid cross connection of the 5VDC and 24VDC supplies to the basic rack panel to an expansion rack panel or expansion rack panels to each other. Looseness of screws may cause malfunction. ¢ Keep the input/output lines away from high voltage or strong current lines such as power lines. HM Cautions for static electricity ¢ Significant volume of static electricity may build up on the human body in extremely dry conditions. Prior to touching the module, discharge the static electricity by touching grounded metals. M Cleaning ¢ Use the soft cloths for cleaning. Volatile solvents (alcohol, paint thinner, freon etc.) and wet rags may cause deformation or change of color. Wi Storage * Keep the control module in cool and dry conditions as it equipped with a battery for memory backup.High ambient temperature may shorten its battery life. M@ Other precautions « Use separate relay logic for the emergency stop control. The relay logic should include a circuit which will shut off the PC output in an emergency. ¢ Do not apply excessive operating stress to switches and connectors. ¢ The following table lists the maximum number of input/output relay contacts, program memory capacity, and file memory capacity available:

MOGE aD es ogram Memory Capac File MeMmor

JW50, JWS0H §12 7.5K words 416K words

JW70, JW70H 1024

JW100, JW100H | 4096 (using JW-I/O) 63K words max.(note) 448K bytes max.(note) 2048 (using ZW-1/O)

(Note) Optional memory module are available for the JW70/100, JW70H/100H. For more details, see page 4-20.

2-1

Page 12 read from a scan by OCR; it may hold reading errors

¢ Never attempt o install or remove a contro! module, option module, or I/O module with the system - power ON. Permanent damage io on-board memories or other circuit devices may result.

[Note JA support tool placed in the "Live I/O replace" mode allows you to replace an I/O module with the system power left turned ON. For more details, see page 9-3.

« The PC's watchdog timer is set to an interval of 320ms. If the scan time exceeds this interval, the halt output contacts will be opened. (For details on scan time, see the progamming manual 2-7[3](9), "Scan time”).

* The type of I/O modules used must be specified in the control module using the DIP switches (see page 4-2). Either JW- /O or ZW-I/O modules may be used with the control module. Table of switch setting (in case of JW-50CU/70CU/100CU)

Slot screwdriver

ZW-VO JW-1/O All OFF | Output hold | Output hold SW2-1 OFF ON ON SWe-2 OFF OFF ON

JW-I/O: 1/0 module dedicated to JW50H/70H/1 OOH ZW-I/O: I/O module designed for use in conventional W51, W70H, and W100

@ At initial power ON ¢ When first powering up the PC, the contents of the momory module installed in the PC are underfined and the I/O installation configuration is not stored in the system memory. Use a support tool to clear the system memory and progam memory and to perform auto 1/O registration of the relay numbers for the I/O module. Refer to the page following the table of contents for the procedure.

Mi installing the module Do not force and bend the pin when installing the module to the connector at the rack panel.

Rack panel Module ~] e a S ma a fx

HM When AC power is used Connect the INPUT terminal of power supply module JW-1PU pay attention to LIVE terminal (non-grounding) and NEUTRAL terminal

(grounding). _ _ N 4 | - NEUTRAL terminal, _ | Input terminal block MER [ of JW-1PU 100 to 240 VAC | _ 5 | - LIVE L terminal 6}