Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of SICK AG EN3 Spec Sheet

Spec sheet · SICK AG

SICK AG EN3 Spec Sheet

Spec sheet2 pagesPDF 384 KB

Both pages are below, each with its text.

Download the PDF384 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Two SICK SENSICK catalogue pages from 2006 for the EN 3 switching unit, which supplies sensors with 24 V DC and gives each of its two inputs a relay output. They give the technical data, a dimensional drawing, a connection diagram, an output current load curve and the order number.

Device type
Switching unit with 2 inputs, each with a relay output; snap-on housing for DIN 46277 support rail p. 1
Supply voltage
90 ... 130 V AC or 200 ... 264 V AC, set with bridges; 48 ... 62 Hz; delivered for 200 ... 264 V AC p. 2
Sensor supply
24 V DC ± 25 %, 1.4 A in total (see load graph) p. 2
Relay outputs
Terminals 5/6/7 (OUT 1) and 13/14/15 (OUT 2); 250 V AC, 2A max.; 20/s p. 2
Inputs
PNP, NPN and B sensors on terminals 26 (IN 1) and 28 (IN 2); 10 ... 30 V DC; HIGH > 10 V DC, LOW < 6 V DC p. 2
Power consumption
env. 40 VA p. 2
Order number
EN 3, order no. 6 009 692 p. 2
Temperature
Operation – 25 °C ... + 55 °C; storage – 40 °C ... + 70 °C p. 2
Enclosure
IP 20; plastic housing p. 2
Weight
Approx. 970 g p. 2
Fuse
250 V/ 0.25 A p. 1
Indicators
Display IN 1, display IN 2 and an operating display p. 1

What this sheet walks you through

  • Wiring supply, sensor inputs and relay outputs p. 1
  • Mounting dimensions p. 1
  • Sensor output current against ambient temperature p. 2

Good to know

  • The NPN variant needs an external pull-up resistor of 10 kΩ or less. p. 2
  • The unit is delivered set for 200 ... 264 V AC. p. 2

Questions this sheet answers

What supply voltage does the SICK EN 3 need?

90 to 130 V AC or 200 to 264 V AC at 48 to 62 Hz, chosen with bridges; it is delivered set for 200 to 264 V AC. p. 2

What is the order number of the EN 3 switching unit?

6 009 692. p. 2

What are the EN 3 relay contact ratings?

250 V AC and 2A at most, with a switching frequency of 20/s. p. 2

Can the EN 3 work with NPN sensors?

Yes, it takes PNP, NPN and B sensors; the NPN variant needs an external pull-up resistor of 10 kΩ or less. p. 2

The file

Size and text

Pages2
PDF384 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of SICK AG EN3 Spec Sheet

The text of page 1, from the PDF itself

KD01_EN_en.qxd25.07.200614:40 UhrSeite 1512

EN 3 Switching units Features

Dimensional drawing

  • Universal supply voltage
  • 2 inputs, each with a relay output

352190support rail DIN 4627798.8

  • Housing with snap fastening for

3 414054591

Fuse (250 V/ 0.25 A) Display IN 1 Operating display Display IN 2

2 3 4

Connection diagram EN 3 90...130 V AC L1

N1718200...264 V AC X1X2X3X451512SENSICK CATALOGUE259OUT 2IN124 V DC + –IN2262728117OUT 1EN3 24 V DC + –613141505-08-2006

Page 2 of SICK AG EN3 Spec Sheet

The text of page 2, from the PDF itself

KD01_EN_en.qxd25.07.200614:40 UhrSeite 1513EN 3 EN 3

Technical data Supply voltage VS Mains frequency Power consumption Outputs Supply voltage for sensor Output current (total)

90 ... 130 V AC or 200 ... 264 V AC1) (can be reset using bridges) 48 ... 62 Hz env. 40 VA

Min. load Relay output Switching voltage, max. Switching current, max. Switching frequency

24 V DC ± 25 % 1.4 A in total, see load graph, output current 200 mA 5/6/7(OUT 1) and 13/14/15 (OUT 2) 250 V AC 2A 20/s

Inputs for PNP, NPN 2) and B sensor inputs Input voltage HIGH LOW

26 (IN 1), 28 (IN 2) 10 ... 30 V DC > 10 V DC < 6 V DC

VDE protection class 1) Enclosure rating Ambient temperature

V

Shock load Weight Housing material

IP 20 Operation – 25 °C . . . + 55 °C Storage – 40 °C . . . + 70 °C Complying with IEC 68 Approx. 970 g Plastic

1)

2)

Delivery 200 . . . 264 V AC

External pull-up resistor ≤ 10 kΩ required for NPN variant

Order information

Load curve, output current

Type EN 3A 1.4Order no. 6 009 6921 21.0 30.50.2 005-08-2006-200204060SENSICK CATALOGUE1513