For the Siemens 3RT1035-1BB40

Page 1

Data sheet

3RT1035-1BB40 Power contactor, AC-3 40 A, 18.5 kW / 400 V 24 V DC, 3-pole, Size S2, Screw terminal !!! Phased-out product !!! Successor is SIRIUS 3RT2 Preferred successor type is >>3RT2028-1BB40<<

Product brand name

SIRIUS

Product designation power contactor

General technical data Size of contactor

S2

Insulation voltage ● rated value

690 V

Degree of pollution

3

Surge voltage resistance rated value

6 kV maximum permissible voltage for safe isolation ● between coil and main contacts acc. to EN 60947-1

400 V

Protection class IP ● on the front

IP20

● of the terminal

IP00

Shock resistance at rectangular impulse ● at DC

10g / 5 ms, 5g / 10 ms

Shock resistance with sine pulse

3RT1035-1BB40 Page 1/8

07/17/2018

Subject to change without notice © Copyright Siemens

Page 2

● at DC

15g / 5 ms, 8g / 10 ms

Mechanical service life (switching cycles) ● of contactor typical

10 000 000

● of the contactor with added electronicscompatible auxiliary switch block typical

5 000 000

● of the contactor with added auxiliary switch block typical

10 000 000

Reference code acc. to DIN EN 81346-2

Q

Ambient conditions Installation altitude at height above sea level ● maximum

2 000 m

Ambient temperature ● during operation

-25 ... +60 °C

● during storage

-55 ... +80 °C

Main circuit Number of poles for main current circuit

3

Number of NO contacts for main contacts

3

Number of NC contacts for main contacts

0

Operating current ● at AC-1 at 400 V, at ambient temperature 40 °C rated value

60 A

● at AC-1, up to 690 V at ambient temperature 40 °C rated value

60 A, up to 690 V at ambient temperature 60 °C rated value

55 A

● at AC-3, at 400 V rated value

40 A, at 690 V rated value

24 A

● at AC-4 at 400 V rated value

35 A

Connectable conductor cross-section in main circuit at AC-1 ● at 60 °C minimum permissible

16 mm²

● at 40 °C minimum permissible

16 mm²

Operating current for approx. 200000 operating cycles at AC-4 ● at 400 V rated value

18.5 A

● at 690 V rated value

12.6 A

Operating current ● at 1 current path at DC-1, at 24 V rated value

55 A, at 110 V rated value

4.5 A

3RT1035-1BB40 Page 2/8

07/17/2018

Subject to change without notice © Copyright Siemens

Page 3

● with 2 current paths in series at DC-1, at 24 V rated value

55 A, at 110 V rated value

25 A

● with 3 current paths in series at DC-1, at 24 V rated value

55 A, at 110 V rated value

55 A

Operating current ● at 1 current path at DC-3 at DC-5, at 24 V rated value

35 A, at 110 V rated value

2.5 A

● with 2 current paths in series at DC-3 at DC-5, at 24 V rated value

55 A, at 110 V rated value

25 A

● with 3 current paths in series at DC-3 at DC-5, at 24 V rated value

55 A, at 110 V rated value

55 A

Operating power ● at AC-1, at 230 V at 60 °C rated value

22 kW, at 400 V rated value

38 kW, at 690 V rated value

66 kW, at 690 V at 60 °C rated value

66 kW

● at AC-2 at 400 V rated value

18.5 kW

● at AC-3, at 230 V rated value

11 kW, at 400 V rated value

18.5 kW, at 500 V rated value

22 kW, at 690 V rated value

22 kW

Operating power for approx. 200000 operating cycles at AC-4 ● at 400 V rated value

9.5 kW

● at 690 V rated value

11.4 kW

Thermal short-time current limited to 10 s

400 A

Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor

2.6 W

No-load switching frequency ● at DC

1 500 1/h

Operating frequency ● at AC-1 maximum

1 200 1/h

● at AC-2 maximum

600 1/h

● at AC-3 maximum

1 000 1/h

● at AC-4 maximum

300 1/h

3RT1035-1BB40 Page 3/8

07/17/2018

Subject to change without notice © Copyright Siemens

Page 4

Control circuit/ Control Type of voltage of the control supply voltage

DC

Control supply voltage at DC ● rated value

24 V

Operating range factor control supply voltage rated value of magnet coil at DC ● initial value

0.8

● Full-scale value

1.1

Closing power of magnet coil at DC

13.3 W

Holding power of magnet coil at DC

13.3 W

Closing delay ● at DC

60 ... 100 ms

Opening delay ● at DC

20 ... 25 ms

Arcing time

10 ... 15 ms

Auxiliary circuit Number of NC contacts for auxiliary contacts ● instantaneous contact

0

Number of NO contacts for auxiliary contacts ● instantaneous contact Operating current at AC-12 maximum

0 10 A

Operating current at AC-15 ● at 230 V rated value

6A

● at 400 V rated value

3A

Operating current at DC-12 ● at 60 V rated value

6A

● at 110 V rated value

3A

● at 220 V rated value

1A

Operating current at DC-13 ● at 24 V rated value

10 A

● at 60 V rated value

2A

● at 110 V rated value

1A

● at 220 V rated value

0.3 A

Contact reliability of auxiliary contacts

1 faulty switching per 100 million (17 V, 1 mA)

UL/CSA ratings Contact rating of auxiliary contacts according to UL

A600 / Q600

Short-circuit protection Design of the fuse link ● for short-circuit protection of the main circuit, with type of coordination 1 required fuse gL/gG: 125 A, with type of assignment 2 required fuse gL/gG: 63 A

3RT1035-1BB40 Page 4/8

07/17/2018

Subject to change without notice © Copyright Siemens

Page 5

● for short-circuit protection of the auxiliary switch required fuse gL/gG: 10 A

Installation/ mounting/ dimensions Mounting type ● Side-by-side mounting screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 Yes

Height

112 mm

Width

55 mm

Depth

130 mm

Required spacing ● for grounded parts, at the side

6 mm

Connections/Terminals Type of electrical connection ● for main current circuit screw-type terminals

● for auxiliary and control current circuit screw-type terminals

Type of connectable conductor cross-sections ● for main contacts, solid

2x (0.75 ... 16 mm²), stranded

2x (0.75 ... 25 mm²), single or multi-stranded

2x (0,75 ... 16 mm²), finely stranded with core end processing

2x (0.75 ... 16 mm²), finely stranded without core end processing

2x (0.75 ... 16 mm²)

● at AWG conductors for main contacts

2x (18 ... 2)

Type of connectable conductor cross-sections ● for auxiliary contacts, solid

2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²), finely stranded with core end processing

2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

● at AWG conductors for auxiliary contacts

2x (20 ... 16), 2x (18 ... 14), 1x 12

Certificates/approvals

3RT1035-1BB40 Page 5/8

07/17/2018

Subject to change without notice © Copyright Siemens

Page 6

General Product Approval

Functional Safety/Safety of Machinery

Declaration of Conformity

Type Examination Certificate

Test Certificates Type Test Certificates/Test Report

Marine / Shipping Special Test Certificate

Marine / Shipping

Miscellaneous other Confirmation

Miscellaneous

Further information Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs

Industry Mall (Online ordering system) https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT1035-1BB40

Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT1035-1BB40

Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RT1035-1BB40

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT1035-1BB40&lang=en

Characteristic: Tripping characteristics, I²t, Let-through current https://support.industry.siemens.com/cs/ww/en/ps/3RT1035-1BB40/char

Further characteristics (e.g. electrical endurance, switching frequency) http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT1035-1BB40&objecttype=14&gridview=view1

3RT1035-1BB40 Page 6/8

07/17/2018

Subject to change without notice © Copyright Siemens

Page 7

55 35

125

17

5

79 45

95

64

111

5

3RT103__00000107_000_ALL Format / Size: DIN A3

3RT1035-1BB40 Page 7/8

07/17/2018

Massstab / Scale: 1:1

Subject to change without notice © Copyright Siemens

Page 8

-Q last modified:

3RT1035-1BB40 Page 8/8

A1(+)

1 /L1

3 /L2

5 /L3

A2(-)

2 /T1

4 /T2

6 /T3

07/16/2018

07/17/2018

Subject to change without notice © Copyright Siemens