Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Siemens 3RV1742-5CD10 Spec Sheet

Spec sheet · Siemens

Siemens 3RV1742-5CD10 Spec Sheet

Spec sheet4 pagesPDF 181 KB

All 4 pages are below, each with its text.

Download the PDF181 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

A four-page Siemens data sheet, dated 08/03/2018, for the SIRIUS 3RV1742-5CD10 circuit breaker in size S3 for system (plant) protection, with a 20 A release and screw terminals. It gives the voltage, current and breaking capacity ratings, ambient limits, mounting, dimensions and conductor sizes, plus a dimension drawing. It also marks the breaker as phased out and names its successor.

Type
SIRIUS circuit breaker, size S3, for plant protection, 3 poles, standard switching capacity p. 1, 2
Releases
A-release (overload) 20 A; short-circuit release 260 A p. 1
Approval
The spec sheet states approval as a circuit breaker to UL 489 and CSA C22.2 No.5-02 p. 1
Successor
Phased out; preferred successor 3RV2742-5CD10 (SIRIUS 3RV2) p. 1
Rated voltage
690 V p. 2
AC-3 at 400 V
20 A p. 2
Breaking capacity Icu
100 kA at 240 V and 400 V, 30 kA at 500 V, 12 kA at 690 V; 65 kA at 480Y/277 V AC to UL 489 p. 2
Release design
Thermomagnetic; no ground fault or phase failure detection p. 2
Mounting
Screw or snap-on onto 35 mm standard rail (DIN EN 50022), any position p. 2
Dimensions
168 mm high, 70 mm wide, 174 mm deep p. 2
Terminals
Screw-type with box terminals on the main circuit; screw-type on auxiliary and control circuit p. 3
Main conductors
Solid 2x (2.5 to 16 mm²); stranded 2x (10 to 50 mm²) or 1x (10 to 70 mm²) p. 3
Ambient temperature
-20 to +60 °C operating; -50 to +80 °C storage and transport p. 2
Power loss
12 W typical p. 1

What this sheet walks you through

  • Main circuit ratings p. 2
  • Short-circuit breaking capacity by voltage p. 2
  • Mounting, dimensions and side-by-side spacing p. 2, 3
  • Conductor cross-sections for the main contacts p. 3
  • Dimension drawing p. 4

Good to know

  • The data sheet marks the breaker as a phased-out product. p. 1
  • Maximum installation altitude is 2 000 m. p. 1
  • At AC-3 the maximum operating frequency is 15 per hour. p. 2

Questions this sheet answers

What replaces the Siemens 3RV1742-5CD10?

The data sheet names the SIRIUS 3RV2 type 3RV2742-5CD10 as the preferred successor. p. 1

What current is the 3RV1742-5CD10 set to?

Its overload release is 20 A and its short-circuit release 260 A. p. 1

What is the UL 489 breaking capacity of the 3RV1742-5CD10?

65 kA at 480Y/277 V AC according to UL 489. p. 2

How big is the 3RV1742-5CD10?

168 mm high, 70 mm wide and 174 mm deep; it mounts on 35 mm rail. p. 2

The file

Size and text

Pages4
PDF181 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Siemens 3RV1742-5CD10 Spec Sheet

The text of page 1, from the PDF itself

Data sheet

3RV1742-5CD10 Circuit breaker size S3 for system protection with approval circuit breaker UL 489, CSA C22.2 No.5-02 A-release 20 A Short-circuit release 260 A Screw terminal Standard switching capacity !!! Phased-out product !!! Successor is SIRIUS 3RV2 Preferred successor type is >>3RV2742-5CD10<<

Product brand nameSIRIUSProduct designationcircuit breakerDesign of the product

for plant protection according to UL 489/CSA C22.2 No.5-02

General technical data Product extension

  • Auxiliary switch

Yes

Power loss [W] total typical

12 W

Surge voltage resistance rated value

6 000 V

Protection class IP

  • on the front Shock resistance

IP20 25g / 11 ms

Mechanical service life (switching cycles)

  • of the main contacts typical Continuous current rated value

50 000 20 A

Ambient conditions Installation altitude at height above sea level

  • maximum

3RV1742-5CD10 Page 1/42 000 m08/03/2018

Subject to change without notice © Copyright Siemens

Page 2 of Siemens 3RV1742-5CD10 Spec Sheet

The text of page 2, from the PDF itself

Ambient temperature

  • during operation

-20 ... +60 °C● during storage-50 ... +80 °C● during transport-50 ... +80 °C

Main circuit Number of poles for main current circuit

3

Adjustable pick-up value current of the currentdependent overload release

20 ... 20 A

Operating voltage

  • rated value

690 V

  • at AC-3 rated value maximum

690 V

Operating current

  • at AC-3, at 400 V rated value

20 A

Operating frequency

  • at AC-3 maximum

15 1/h

Auxiliary circuit Number of CO contacts

  • for auxiliary contacts

0

Protective and monitoring functions Product function

  • Ground fault detection

No

  • Phase failure detection

No

Maximum short-circuit current breaking capacity (Icu)

  • at AC at 240 V rated value

100 kA

  • at AC at 400 V rated value

100 kA

  • at AC at 500 V rated value

30 kA

  • at AC at 690 V rated value

12 kA

  • at 480 AC Y/277 V acc. to UL 489 rated value

65 kA

Short-circuit protection Design of the overcurrent release and short-circuit release

thermomagnetic

Installation/ mounting/ dimensions Mounting position

any

Mounting type

screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022

Height168 mmWidth70 mmDepth174 mm

Required spacing

  • with side-by-side mounting

3RV1742-5CD10 Page 2/4

08/03/2018

Subject to change without notice © Copyright Siemens

Page 3 of Siemens 3RV1742-5CD10 Spec Sheet

The text of page 3, from the PDF itself

  • Backwards

0 mm, at the side

0 mm

Connections/Terminals Product function

  • removable terminal for auxiliary and control circuit

No

Type of electrical connection

  • for main current circuit

screw-type terminals with box terminals

  • for auxiliary and control current circuit

screw-type terminals

Arrangement of electrical connectors for main current circuit

front side

Type of connectable conductor cross-sections

  • for main contacts, solid

2x (2.5 ... 16 mm²), stranded

2x (10 ... 50 mm²), 1x (10 ... 70 mm²), finely stranded with core end processing

2x (2.5 ... 35 mm²), 2.5 ... 50 mm² 2x (10 ... 1), 1x (10 ... 2)

  • at AWG conductors for main contacts

Certificates/approvals General Product Approval

Declaration of Conformity

Test Certificates Special Test Certificate

Marine / Shippingother MiscellaneousConfirmation

Further information Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs

Industry Mall (Online ordering system) https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV1742-5CD10

Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV1742-5CD10

Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RV1742-5CD10

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV1742-5CD10&lang=en

Characteristic: Tripping characteristics, I²t, Let-through current https://support.industry.siemens.com/cs/ww/en/ps/3RV1742-5CD10/char

3RV1742-5CD10 Page 3/4

08/03/2018

Subject to change without notice © Copyright Siemens

Page 4 of Siemens 3RV1742-5CD10 Spec Sheet

The text of page 4, from the PDF itself

Further characteristics (e.g. electrical endurance, switching frequency) http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV1742-5CD10&objecttype=14&gridview=view1 22,5

22,5 3026∅515516815545129SIEMENS70

last modified
3RV1742-5CD10 Page 4/4

07/25/2018

08/03/2018

Subject to change without notice © Copyright Siemens