A four-page Siemens data sheet, dated 08/03/2018, for the SIRIUS 3RV1742-5CD10 circuit breaker in size S3 for system (plant) protection, with a 20 A release and screw terminals. It gives the voltage, current and breaking capacity ratings, ambient limits, mounting, dimensions and conductor sizes, plus a dimension drawing. It also marks the breaker as phased out and names its successor.
- Type
- SIRIUS circuit breaker, size S3, for plant protection, 3 poles, standard switching capacity p. 1, 2
- Releases
- A-release (overload) 20 A; short-circuit release 260 A p. 1
- Approval
- The spec sheet states approval as a circuit breaker to UL 489 and CSA C22.2 No.5-02 p. 1
- Successor
- Phased out; preferred successor 3RV2742-5CD10 (SIRIUS 3RV2) p. 1
- Rated voltage
- 690 V p. 2
- AC-3 at 400 V
- 20 A p. 2
- Breaking capacity Icu
- 100 kA at 240 V and 400 V, 30 kA at 500 V, 12 kA at 690 V; 65 kA at 480Y/277 V AC to UL 489 p. 2
- Release design
- Thermomagnetic; no ground fault or phase failure detection p. 2
- Mounting
- Screw or snap-on onto 35 mm standard rail (DIN EN 50022), any position p. 2
- Dimensions
- 168 mm high, 70 mm wide, 174 mm deep p. 2
- Terminals
- Screw-type with box terminals on the main circuit; screw-type on auxiliary and control circuit p. 3
- Main conductors
- Solid 2x (2.5 to 16 mm²); stranded 2x (10 to 50 mm²) or 1x (10 to 70 mm²) p. 3
- Ambient temperature
- -20 to +60 °C operating; -50 to +80 °C storage and transport p. 2
- Power loss
- 12 W typical p. 1
What this sheet walks you through
- Main circuit ratings p. 2
- Short-circuit breaking capacity by voltage p. 2
- Mounting, dimensions and side-by-side spacing p. 2, 3
- Conductor cross-sections for the main contacts p. 3
- Dimension drawing p. 4
Good to know
- The data sheet marks the breaker as a phased-out product. p. 1
- Maximum installation altitude is 2 000 m. p. 1
- At AC-3 the maximum operating frequency is 15 per hour. p. 2
Questions this sheet answers
What replaces the Siemens 3RV1742-5CD10?
The data sheet names the SIRIUS 3RV2 type 3RV2742-5CD10 as the preferred successor. p. 1
What current is the 3RV1742-5CD10 set to?
Its overload release is 20 A and its short-circuit release 260 A. p. 1
What is the UL 489 breaking capacity of the 3RV1742-5CD10?
65 kA at 480Y/277 V AC according to UL 489. p. 2
How big is the 3RV1742-5CD10?
168 mm high, 70 mm wide and 174 mm deep; it mounts on 35 mm rail. p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Data sheet
3RV1742-5CD10 Circuit breaker size S3 for system protection with approval circuit breaker UL 489, CSA C22.2 No.5-02 A-release 20 A Short-circuit release 260 A Screw terminal Standard switching capacity !!! Phased-out product !!! Successor is SIRIUS 3RV2 Preferred successor type is >>3RV2742-5CD10<<
Product brand nameSIRIUSProduct designationcircuit breakerDesign of the product
for plant protection according to UL 489/CSA C22.2 No.5-02
General technical data Product extension
- Auxiliary switch
Yes
Power loss [W] total typical
12 W
Surge voltage resistance rated value
6 000 V
Protection class IP
- on the front Shock resistance
IP20 25g / 11 ms
Mechanical service life (switching cycles)
- of the main contacts typical Continuous current rated value
50 000 20 A
Ambient conditions Installation altitude at height above sea level
- maximum
3RV1742-5CD10 Page 1/42 000 m08/03/2018
Subject to change without notice © Copyright Siemens
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
Ambient temperature
- during operation
-20 ... +60 °C● during storage-50 ... +80 °C● during transport-50 ... +80 °C
Main circuit Number of poles for main current circuit
3
Adjustable pick-up value current of the currentdependent overload release
20 ... 20 A
Operating voltage
- rated value
690 V
- at AC-3 rated value maximum
690 V
Operating current
- at AC-3, at 400 V rated value
20 A
Operating frequency
- at AC-3 maximum
15 1/h
Auxiliary circuit Number of CO contacts
- for auxiliary contacts
0
Protective and monitoring functions Product function
- Ground fault detection
No
- Phase failure detection
No
Maximum short-circuit current breaking capacity (Icu)
- at AC at 240 V rated value
100 kA
- at AC at 400 V rated value
100 kA
- at AC at 500 V rated value
30 kA
- at AC at 690 V rated value
12 kA
- at 480 AC Y/277 V acc. to UL 489 rated value
65 kA
Short-circuit protection Design of the overcurrent release and short-circuit release
thermomagnetic
Installation/ mounting/ dimensions Mounting position
any
Mounting type
screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Height168 mmWidth70 mmDepth174 mm
Required spacing
- with side-by-side mounting
3RV1742-5CD10 Page 2/4
08/03/2018
Subject to change without notice © Copyright Siemens
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
- Backwards
0 mm, at the side
0 mm
Connections/Terminals Product function
- removable terminal for auxiliary and control circuit
No
Type of electrical connection
- for main current circuit
screw-type terminals with box terminals
- for auxiliary and control current circuit
screw-type terminals
Arrangement of electrical connectors for main current circuit
front side
Type of connectable conductor cross-sections
- for main contacts, solid
2x (2.5 ... 16 mm²), stranded
2x (10 ... 50 mm²), 1x (10 ... 70 mm²), finely stranded with core end processing
2x (2.5 ... 35 mm²), 2.5 ... 50 mm² 2x (10 ... 1), 1x (10 ... 2)
- at AWG conductors for main contacts
Certificates/approvals General Product Approval
Declaration of Conformity
Test Certificates Special Test Certificate
Marine / Shippingother MiscellaneousConfirmation
Further information Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system) https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV1742-5CD10
Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV1742-5CD10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RV1742-5CD10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV1742-5CD10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current https://support.industry.siemens.com/cs/ww/en/ps/3RV1742-5CD10/char
3RV1742-5CD10 Page 3/4
08/03/2018
Subject to change without notice © Copyright Siemens
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
Further characteristics (e.g. electrical endurance, switching frequency) http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV1742-5CD10&objecttype=14&gridview=view1 22,5
22,5 3026∅515516815545129SIEMENS70
- last modified
- 3RV1742-5CD10 Page 4/4
07/25/2018
08/03/2018
Subject to change without notice © Copyright Siemens