For the Siemens 3RV2711-0DD10

Page 1

Data sheet

3RV2711-0DD10 Circuit breaker size S00 for system protection with approval circuit breaker UL 489, CSA C22.2 No.5-02 A-release 0.32 A N-release 4.2 A screw terminal Standard switching capacity

Product brand name

SIRIUS

Product designation

Circuit breaker

Design of the product

For system protection according to UL 489/CSA C22.2 No. 5

Product type designation

3RV2

General technical data Size of the circuit-breaker

S00

Product extension ● Auxiliary switch

Yes

Power loss [W] total typical

5W

Insulation voltage with degree of pollution 3 rated value

690 V

Surge voltage resistance rated value

6 kV maximum permissible voltage for safe isolation ● in networks with grounded star point between main and auxiliary circuit

400 V

● in networks with grounded star point between main and auxiliary circuit

400 V

Protection class IP ● on the front

3RV2711-0DD10 Page 1/8

IP20

10/01/2018

Subject to change without notice © Copyright Siemens

Page 2

● of the terminal

IP00

Shock resistance ● acc. to IEC 60068-2-27

25g / 11 ms

Mechanical service life (switching cycles) ● of the main contacts typical

100 000

● of auxiliary contacts typical

100 000

Electrical endurance (switching cycles) ● typical

100 000

Certificate of suitability ATEX

No

Protection against electrical shock finger-safe when touched vertically from front acc. to IEC 60529

Reference code acc. to DIN EN 81346-2

Q

Ambient conditions Installation altitude at height above sea level ● maximum

2 000 m

Ambient temperature ● during operation

-20 ... +60 °C

● during storage

-50 ... +80 °C

● during transport

-50 ... +80 °C

Temperature compensation

-20 ... +60 °C

Relative humidity during operation

10 ... 95 %

Main circuit Number of poles for main current circuit

3

Operating voltage ● rated value

690 V

● at AC-3 rated value maximum

690 V

Operating frequency rated value

50 ... 60 Hz

Operating current rated value

0.32 A

Operating current ● at AC-3, at 400 V rated value

0.32 A

Operating power ● at AC-3, at 230 V rated value

40 W, at 400 V rated value

90 W, at 500 V rated value

120 W, at 690 V rated value

120 W

Operating frequency ● at AC-3 maximum

15 1/h

Auxiliary circuit Number of NC contacts for auxiliary contacts

0

Number of NO contacts for auxiliary contacts

0

3RV2711-0DD10 Page 2/8

10/01/2018

Subject to change without notice © Copyright Siemens

Page 3

Number of CO contacts ● for auxiliary contacts

0

Protective and monitoring functions Product function ● Ground fault detection

No

● Phase failure detection

No

Design of the overload release thermal

Operational short-circuit current breaking capacity (Ics) at AC ● at 240 V rated value

100 kA

● at 400 V rated value

100 kA

● at 500 V rated value

100 kA

● at 690 V rated value

100 kA

Maximum short-circuit current breaking capacity (Icu) ● at AC at 240 V rated value

100 kA

● at AC at 400 V rated value

100 kA

● at AC at 500 V rated value

100 kA

● at AC at 690 V rated value

100 kA

● at 480 AC Y/277 V acc. to UL 489 rated value

65 000 A

Breaking capacity short-circuit current (Icn) ● at 1 current path at DC at 150 V rated value

10 kA

● with 2 current paths in series at DC at 300 V rated value

10 kA

● with 3 current paths in series at DC at 450 V rated value

10 kA

Response value current ● of instantaneous short-circuit trip unit

4.2 A

Short-circuit protection Product function Short circuit protection

Yes

Design of the short-circuit trip magnetic

Installation/ mounting/ dimensions Mounting position any

Mounting type screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715

Height

144 mm

Width

45 mm

Depth

97 mm

Required spacing ● with side-by-side mounting, forwards

0 mm, Backwards

0 mm, upwards

50 mm

3RV2711-0DD10 Page 3/8

10/01/2018

Subject to change without notice © Copyright Siemens

Page 4

- downwards

50 mm, at the side

0 mm

● for grounded parts, forwards

0 mm, Backwards

0 mm, upwards

50 mm, at the side

30 mm, downwards

50 mm

● for live parts, forwards

0 mm, Backwards

0 mm, upwards

50 mm, downwards

50 mm, at the side

30 mm

Connections/Terminals Product function ● removable terminal for auxiliary and control circuit

No

Type of electrical connection ● for main current circuit Arrangement of electrical connectors for main current circuit screw-type terminals Top and bottom

Type of connectable conductor cross-sections ● for main contacts, single or multi-stranded

1 ... 10 mm², max. 2x 10 mm², finely stranded with core end processing

1 ... 16 mm², max. 6 + 16 mm²

● at AWG conductors for main contacts

2x (14 ... 10)

Tightening torque ● for main contacts with screw-type terminals

2.5 ... 3 N·m

Design of screwdriver shaft

Diameter 5 to 6 mm

Size of the screwdriver tip

Pozidriv 2

Design of the thread of the connection screw ● for main contacts

M4

Safety related data B10 value ● with high demand rate acc. to SN 31920

5 000

Proportion of dangerous failures ● with low demand rate acc. to SN 31920

50 %

● with high demand rate acc. to SN 31920

50 %

Failure rate [FIT] ● with low demand rate acc. to SN 31920

3RV2711-0DD10 Page 4/8

50 FIT

10/01/2018

Subject to change without notice © Copyright Siemens

Page 5

T1 value for proof test interval or service life acc. to IEC 61508

10 y

Display version Handle

● for switching status

Certificates/approvals General Product Approval

Declaration of Conformity KC

Test Certificates

Marine / Shipping

Type Test Certificates/Test Report

Special Test Certificate

Marine / Shipping other

Railway

Confirmation

Miscellaneous

Vibration and Shock

Further information Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs

Industry Mall (Online ordering system) https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2711-0DD10

Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2711-0DD10

Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RV2711-0DD10

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2711-0DD10&lang=en

Characteristic: Tripping characteristics, I²t, Let-through current https://support.industry.siemens.com/cs/ww/en/ps/3RV2711-0DD10/char

Further characteristics (e.g. electrical endurance, switching frequency) http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2711-0DD10&objecttype=14&gridview=view1

3RV2711-0DD10 Page 5/8

10/01/2018

Subject to change without notice © Copyright Siemens

Page 6

96.9

144.6

72.8

45

5

3RV2711-0DD10 Page 6/8

10/01/2018

Subject to change without notice © Copyright Siemens

Page 7 read from a scan by OCR; it may hold reading errors

SRV?

3RV2711-0DD10 Subject to change without notice Page 7/8 10/01/2018 © Copyright Siemens

Page 8

1/L1

3/L2

5/L3

I>

I>

I>

4/T2

6/T3

2/T1

-F last modified:

3RV2711-0DD10 Page 8/8

09/21/2018

10/01/2018