Page 62
Chapter 3
Software Conversions Instructions
SIMATIC S5 - Ladder
RSLogix 5000 - Ladder where timer T5 is defined as data type TIMER in the program tags as follows.
62
Publication LOGIX-AP010B-EN-P - May 2010
Page 63
Software Conversions Instructions
Chapter 3
Counter - UP The following example shows how a COUNTUP function in SIMATIC S5 can be converted into a similar function in RSLogix 5000 for Statement List and Ladder formats. The RSLogix 5000-equivalent bit/word for each bit/word used in the S5 in the following example is shown below. Function Counter Preset Counter Reset Count Up Output
S5 Statement List A L S A R A CU A =
I4.0 DW20 C1 I4.1 C1 I4.2 C1 C1 Q4.0
Publication LOGIX-AP010B-EN-P - May 2010
S5 DW20 I4.1 I4.2 Q2.0
RSLogix 5000 data_word1 data_bit2 data_bit1 out_bit1
RSLogix 5000 Structured Text C1.Pre := data_word1; C1.Reset := data_bit2; C1.CUEnable := data_bit1; CTUD(C1); out_bit1 := C1.DN; where timer C1 is defined as data type FBD_COUNTER in the program tags as follows.
63
Page 64
Chapter 3
Software Conversions Instructions
SIMATIC S5 - Ladder
RSLogix 5000 - Ladder where timer COUNTER is defined as data type COUNTER in the program tags as follows.
64
Publication LOGIX-AP010B-EN-P - May 2010
Page 65
Software Conversions Instructions
Chapter 3
Counter - DOWN The following example shows how a COUNTDOWN function in SIMATIC S5 can be converted into a similar function in RSLogix 5000 for Statement List and Ladder formats. The RSLogix 5000-equivalent bit/word for each bit/word used in the S5 in the following example is shown below. Function Counter Preset Counter Reset Count Down Output S5 Statement List A L S A R A CD A =
I4.0 DW20 C1 I4.1 C1 I4.2 C1 C1 Q2.0
Publication LOGIX-AP010B-EN-P - May 2010
S5 DW20 I4.1 I4.2 Q2.0
RSLogix 5000 data_word1 data_bit2 data_bit1 out_bit1 RSLogix 5000 Structured Text C1.Pre := data_word1; => space before := C1.Reset := data_bit2; C1.CDEnable := data_bit1; CTUD(C1); out_bit1 := C1.DN; where counter C1 is defined as data type FBD_COUNTER is the program tags as follows.
65
Page 66
Chapter 3
Software Conversions Instructions
SIMATIC S5 - Ladder
RSLogix 5000 - Ladder where counter COUNTDOWN is defined as data type COUNTER is the program tags as follows.
66
Publication LOGIX-AP010B-EN-P - May 2010
Page 67
Software Conversions Instructions
Chapter 3
Comparison - Equal In the following comparison function the two operands are compared and if found to be equal then the output is set to 1. The RSLogix 5000-equivalent bit/word for each bit/word used in the S5 in the following example is shown below: Function Operand1 Operand2 Output S5 Statement List L IB19 L IB20 !=F = Q3.0
S5 IB19 IB20 Q3.0
RSLogix 5000 data_word1 data_word2 out_bit1 RSLogix 5000 Structured Text If data_word1 = data_word2 THEN out_bit1 := 1; else out_bit1 := 0; END_IF; SIMATIC S5 - Ladder
RSLogix 5000 - Ladder
Publication LOGIX-AP010B-EN-P - May 2010
67
Page 68
Chapter 3
Software Conversions Instructions
Comparison - Greater Than In the following comparison function the Operand 1 is compared to Operand 2 and if Operand 1 > Operand 2 then the output is set to 1. The RSLogix 5000 equivalent bit/word for each bit/word used in the S5 in the following example is shown below: Function Operand 1 Operand 2 Output S5 Statement List L IB19 L IB20 >F = Q3.0
S5 IB19 IB20 Q3.0
RSLogix 5000 data_word1 data_word2 out_bit1 RSLogix 5000 Structured Text If data_word1 > data_word2 THEN out_bit1 := 1; else out_bit1 := 0; END_IF; SIMATIC S5 - Ladder
RSLogix 5000 - Ladder
68
Publication LOGIX-AP010B-EN-P - May 2010
Page 69
Software Conversions Instructions
Chapter 3
Comparison - Less Than In the following comparison function the Operand 1 is compared to Operand 2 and if Operand 1 < Operand 2 then the output is set to 1. The RSLogix 5000 equivalent bit/word for each bit/word used in the S5 in the following example is shown below: Function Operand 1 Operand 2 Output S5 Statement List L IB19 L IB20 <F = Q3.0
S5 IB19 IB20 Q3.0
RSLogix 5000 data_word1 data_word2 out_bit1 RSLogix 5000 Structured Text If data_word1 < data_word2 THEN out_bit1 := 1; else out_bit1 := 0; END_IF; SIMATIC S5 - Ladder
RSLogix 5000 - Ladder
Publication LOGIX-AP010B-EN-P - May 2010
69
Page 70
Chapter 3
Software Conversions Instructions
Comparison - Not Equal In the following comparison function the two operands are compared and if found to be NOT equal then the output is set to 1. The RSLogix 5000 equivalent bit/word for each bit/word used in the S5 in the following example is shown below: Function Operand1 Operand2 Output S5 Statement List L IB19 L IB20 >< F = Q3.0
S5 IB19 IB20 Q3.0
RSLogix 5000 data_word1 data_word2 out_bit1 RSLogix 5000 Structured Text If data_word1 <> data_word2 THEN out_bit1 := 1; else out_bit1 := 0; END_IF; SIMATIC S5 - Ladder
RSLogix 5000 - Ladder
70
Publication LOGIX-AP010B-EN-P - May 2010