Page 59

A

Technical data Overview of contents This chapter provides general technical data and the technical data of the DP/DP Coupler: Section

A.1

Topic

Page

A.1

General technical data

A-1

A.2

Technical data of the DP/DP coupler (6ES7 158-0AD01-0XA0)

A-12

A.3

Use of the DP/DP Coupler in potentially explosive environments of Zone 2 (in all official EU languages)

A-13

General technical data

What are general technical data? The general technical data consist of: • the standards and test values that the described components must comply with and fulfil. • the test criteria by which the described components were tested. Section

DP/DP Coupler A5E00244669-03

Topic

Page

A.1.1

Standards and approvals

A-2

A.1.2

Electromagnetic compatibility

A-6

A.1.3

Transportation and storage conditions

A-8

A.1.4

Mechanical and climatic ambient conditions for operation

A-9

A.1.5

Data on insulation tests, protection class and degree of protection

A-11

A.1.6

Rated voltage

A-11

A-1

Page 60

Technical data

A.1.1

Standards and approvals

CE certification The described components fulfil the requirements and safety objectives of the following EC Directives and comply with the harmonized European standards (EN) published for programmable logic controllers in the official journals of the EC: • 73/23/EEC Low Voltage Directive (for electrical equipment) • 89/336/EEC Electromagnetic Compatibility Directive (EMC Directive) • Directive 94/9/EC on protective devices and systems for use in potentially explosive areas (explosion protection directive) The EC Declarations of Conformity are available for the relevant authorities at the following address: Siemens Aktiengesellschaft Automation and Drives A&D AS RD ST Type Test PO Box 1963 D-92209 Amberg

A-2

DP/DP Coupler A5E00244669-03

Page 61

Technical data

Approvals Underwriters Laboratories Inc. to

UL 508 (Industrial Control Equipment)

CSA C22.2 No. 142 (Process Control Equipment)

Or Underwriters Laboratories Inc. to

HAZ. LOC.

UL 508 (Industrial Control Equipment)

CSA C22.2 No. 142 (Process Control Equipment)

UL 1604 (Hazardous Location)

CSA-213 (Hazardous Location)

APPROVED for use in Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, AEx nC, Group IIC T4 Note The approvals currently effective are found on the rating plate of each module.

FM approval Factory Mutual Research (FM) in accordance with Approval Standard Class Number 3611, 3600, 3810 APPROVED for use in Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4 to EN 50021 (Electrical apparatus for potentially explosive atmospheres; Type of protection “n”) II 3 G EEx nA II T4

Label for Australia The described components comply with the requirements of the AS/NZS 2064 (Class A) standard.

DP/DP Coupler A5E00244669-03

A-3

Page 62

Technical data

IEC 61131 The described components comply with the requirements and criteria of the IEC 61131-2 standard (programmable logic controllers, Part 2: Equipment requirements and tests).

Marine approval (pending) Classification societies: • ABS (American Bureau of Shipping) • BV (Bureau Veritas) • DNV (Det Norske Veritas) • GL (Germanischer Lloyd) • LRS (Lloyds Register of Shipping) • Class NK (Nippon Kaiji Kyokai)

PROFIBUS standard The components described are based on the standard IEC 61784-1:2002 Ed1 CP 3/1.

Use in industrial environments SIMATIC products are designed for use in industry. Table A-1

Use in industrial environments Area of application

Industry

A-4

Requirements Emitted interference

Noise immunity

EN 61000-6-4:2001

EN 61000-6-2:2001

DP/DP Coupler A5E00244669-03

Page 63

Technical data

Use in residential areas If you use the described components in residential areas, you must ensure that they comply with limit value class B to EN 55011 with respect to radio interference. Measures suitable for achieving the radio interference level required by limit value class B are: • Installation in grounded switch cabinets / cubicles • Use of filters in supply lines

!

Warning There is a risk of injury and damage to property. In areas where there is a risk of explosion, injuries and damage may be caused if you remove connectors during operation. In potentially explosive environments, always switch of the power supply before you disconnect any component connectors.

DP/DP Coupler A5E00244669-03

A-5

Page 64

Technical data

A.1.2

Electromagnetic compatibility

Introduction This chapter contains data on the noise immunity and RF suppression of the described components. The described components meet the requirements of the European EMC legislation for the single market.

Pulse-type interference The table below shows the electromagnetic compatibility of the described components with respect to pulse-type interference. The prerequisite for this is that the system meets and complies with the relevant requirements and guidelines relating to electrical equipment. Table A-2

Pulse-type interference

Pulse-type interference

Tested at

Corresponds to severity of

Electrostatic discharge in accordance with IEC 61000-4-2

8 kV

3 (air discharge)

4 kV

2 (contact discharge)

2 kV (supply line)

3

Burst impulse (rapid transient interference) in accordance with IEC 61000-4-4

2 kV (signal line)

High energy single pulse (surge) in accordance with IEC 61000-4-5 External RC circuit is required (see installation manual entitled Automation System S7-300, Installation, Section “Lightning protection and surge protection”)

• Asymmetric interference

2 kV (supply line) 2 kV (signal line/ data line)

• Symmetric interference

3

1 kV (supply line) 1 kV (signal line/ data line)

A-6

DP/DP Coupler A5E00244669-03

Page 65

Technical data

Sinusoidal interference The table below shows the EMC behavior of the described components with respect to sinusoidal interference. Table A-3

Sinusoidal interference

Sinusoidal interference

RF radiation (electromagnetic fields) in accordance with IEC 61000-4-3

Test values

10 V/m with 80 % amplitude modulation of 1 kHz in the range 80 MHz to 1000 MHz

Corresponds to severity of 3

10 V/m with 50 % pulse modulation at 900 MHz RF interference on cables and cable shields in accordance with IEC 61000-4-6

Test voltage of 10 V with 80 % amplitude modulation of 1 kHz in the range 9 kHz to 80 MHz

3

Emission of radio interference Emitted interference from electromagnetic fields in accordance with EN 55011: limit value class A, group 1 From 30 to 230 MHz

< 30 dB (mV/m)Q

From 230 to 1000 MHz

< 37 dB (mV/m)Q

Measured at 30 m distance

Emitted interference via a.c. supply in accordance with EN 55011: limit value class A, group 1 From 0.15 to 0.5 MHz

< 79 dB (mV)Q < 66 dB (mV)M

From 0.5 to 5 MHz

< 73 dB (mV)Q < 60 dB (mV)M

From 5 to 30 MHz

< 73 dB (mV)Q < 60 dB (mV)M

DP/DP Coupler A5E00244669-03

A-7

Page 66

Technical data

A.1.3

Transportation and storage conditions

Transport and storage of modules The described components exceed the requirements of IEC 61131, Part 2, as regards transportation and storage requirements. The following values apply to modules that are transported or stored in the original packaging. Table A-4

Transportation and storage conditions Permissible range

Type of condition

A-8

Free fall (in transport packaging)

v 0.3 m

Temperature from –40 to + 70

Air pressure

From 1080 to 660 hPa (corresponds to a height of –1000 to 3500 m)

Relative air humidity

From 10 to 95 %, without condensation

Sinusoidal vibrations in accordance with IEC 60068-2-6

5 - 9 Hz:

3.5 mm

9 - 150 Hz:

9.8 m/s2

Shock in accordance with IEC 60068-2-29

250 m/s2, 6 ms, 1000 shocks

DP/DP Coupler A5E00244669-03

Page 67

Technical data

A.1.4

Mechanical and climatic ambient conditions for operation

Operating conditions The described components are designed for use in a fixed, sheltered location. The operating conditions exceed the requirements of IEC 61131 Part 2. The described components meet the operating conditions of Class 3C3 in accordance with DIN EN 60721 Part 2.

Use with additional measures Without additional measures, the described components may not be used: • in locations with a high proportion of ionizing radiation • in locations with operating conditions that are severe on account of the following, for example: – dust – corrosive vapors or gases – strong electrical or magnetic fields • in systems that require special monitoring, such as: – lift systems – electrical systems in especially endangered areas An additional measure could be, for example, the installation in a cabinet or in an enclosure.

Mechanical ambient conditions The mechanical ambient conditions for the described components are specified for sinusoidal vibrations in the following table. Table A-5

Mechanical ambient conditions

Frequency range in Hz

Continuous

Occasional

10 v f v 58

0.0375 mm amplitude

0.075 mm amplitude

58 v f v 150

0.5 g constant acceleration

1 g constant acceleration

Vibration reduction When the described components are subjected to major shocks or vibrations, you must take suitable action to reduce the acceleration or amplitude. We recommend mounting the described components on damping material (e.g. on rubber-metal connections).

DP/DP Coupler A5E00244669-03

A-9