Manual · Siemens
SIMATIC DP/DP Coupler Manual
Manual104 pagesPDF 923 KB
Manual for the Siemens SIMATIC DP/DP Coupler 6ES7 158-0AD01-0XA0, compatible with the 6ES7 158-0AD00-0XA0, linking two PROFIBUS DP networks.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Siemens SIMATIC manual with the information needed to install, wire, configure and commission the DP/DP Coupler, order no. 6ES7 158-0AD01-0XA0, which couples two PROFIBUS DP networks. It notes compatibility with the earlier 6ES7 158-0AD00-0XA0. Chapters cover the product overview, installation on DIN or S7 rail, wiring the dual 24 V DC supply and PROFIBUS DP, DIL switch settings and STEP 7 configuration, operation and response times, LED and program diagnostics, technical data and Zone 2 use, and order numbers.
Its parts
- Product Overview
- Installation
- Wiring
- Configuring and commissioning
- Operation of the DP/DP Coupler
- Diagnostics
From the manual
Key facts from this manual
Each line names its page in the PDF.
Siemens SIMATIC DP/DP Coupler manual, edition 02/2006, written for the coupler 6ES7 158-0AD01-0XA0; it names the 6ES7 158-0AD00-0XA0 only as the compatible earlier version that the newer unit can replace. It covers installation, wiring, the DIL switch settings, configuration, response times, LED diagnostics, technical data and accessories.
- What it is
- Coupler that links two PROFIBUS DP networks so their masters can exchange data p. 13
- Compatibility
- 6ES7 158-0AD01-0XA0 is compatible with and can replace the 6ES7 158-0AD00-0XA0; it adds enhanced SYNC and FREEZE diagnostic information p. 16
- Data exchange
- Up to 244 bytes input and 244 bytes output data, up to 128 bytes consistent; up to 16 I/O areas p. 15
- Transmission speed
- 6ES7 158-0AD01-0XA0: 9.6; 19.2; 45.45; 93.75; 187.5; 500 kbps and 1.5; 3, 6, 12 Mbps; each network may run at its own rate p. 14, 70
- Supply voltage
- 6ES7 158-0AD01-0XA0: 24 VDC (20.4 V ... 28.8 V), typically 90 mA, typically 2 W; PELV supplies only p. 27, 70
- Dual power supply
- Two separate 24 V DC sources, one per network, used redundantly; with both present it uses network 1; a single supply goes preferably to PS2 p. 27
- PROFIBUS address
- 1 to 125, set for each network on the DIL switches or assigned in STEP 7 p. 33, 34
- LEDs
- SF 1, SF 2 group error and BF 1, BF 2 bus error (red); ON 1, ON 2 24 V power supply (green) p. 46
- Isolation
- Electrical isolation between the DP networks; 24 V supply isolated from PROFIBUS-DP; insulation tested at 500 VDC p. 15, 70
- Dimensions and weight
- 6ES7 158-0AD01-0XA0: W 40, H 127, D 117 mm; approx. 250 g p. 70
- Mounting
- DIN rail (7.5 mm and 15 mm) or S7 system profile rail, with at least 40 mm free above and below p. 17
- Bus accessories
- PROFIBUS DP bus connectors 6ES7 972-0BA12-0XA0, 6ES7 972-0BB12-0XA0, FastConnect 6ES7 972-0BA50-0XA0 and 6ES7 972-0BB50-0XA0; bus cable 6XV1 830-0EH10 p. 95
- Rails
- DIN rail 35 mm 6ES5 710-8MA11 (483 mm) to 6ES5 710-8MA41 (2000 mm); S7 rail 6ES7 390-1AE80-0AA0 (482 mm) to 6ES7 390-1BC00-0AA0 (2000 mm) p. 95
What this manual walks you through
- Configuring the coupler in STEP 7 or with another tool through a GSD file p. 13
- Installing the coupler on a DIN rail or an S7 profile rail p. 18, 19
- Connecting one or two 24 V DC supplies and setting the PS switch p. 27, 28
- Connecting the PROFIBUS DP bus connectors p. 28
- Turning on the data validity indication with the DIA switch p. 32, 33
- Setting the PROFIBUS address on the DIL switches p. 33, 34, 35
- Replacing a faulty coupler p. 43
- Estimating response times and the internal copy cycle p. 44
- Diagnosing faults from the LEDs p. 46, 47
Good to know
- The coupler is an open device and must be installed in a cabinet or room reachable only with a key or tool. p. 17
- Only PELV power supply modules may be used. p. 27
- With DIA on, the first bit of the first configured input byte must not carry normal input data. p. 33
- A changed address takes effect only after the 24 V DC supply is switched off and on. p. 35
- The PS switch must match the connected supplies, or STEP 7 will not evaluate the diagnostic data correctly. p. 28
Questions this manual answers
Can the 6ES7 158-0AD01-0XA0 replace a 6ES7 158-0AD00-0XA0 DP/DP Coupler?
Yes. The manual says the 0AD01 is compatible with the 0AD00, its design is compatible, and it can replace earlier versions. p. 16
How much data can the DP/DP Coupler transfer between two networks?
Up to 244 bytes of input and 244 bytes of output data, of which up to 128 bytes are consistent, in up to 16 I/O areas. p. 15
How do I set the PROFIBUS address on the DP/DP Coupler?
With the 24 V DC off, open the front door, set the switches (the address is the sum of the switches set ON), set ADDR to OFF and switch the supply back on. p. 34
Can the two PROFIBUS networks run at different baud rates?
Yes. Each side has its own transmission rate and PROFIBUS address. p. 14, 15
What does a flashing BF LED on the DP/DP Coupler mean?
There is no data exchange between the DP master and the coupler on that network; check the configuration and the PROFIBUS address. p. 47
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 14 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 81-8
- Contents9-12
- 1 Product Overview13-16
- 2 Installation17-20
- 3 Wiring21-28
- 4 Configuring and commissioning29-42
- Pages 43 to 5043-50
- Pages 51 to 5851-58
- A Technical data, pages 59 to 6759-67
- A Technical data, pages 68 to 7668-76
- A Technical data, pages 77 to 8577-85
- A Technical data, pages 86 to 9486-94
- Pages 95 to 10095-100
- Index101-104
The file