SIMATIC DP/DP Coupler Manual: 3 Wiring

Pages 21 to 28 of 104, from SIMATIC DP/DP Coupler Manual

The original document is the PDF (923 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Siemens 6ES7-158-0AD00-0XA0

Page 21

3

Wiring Overview of contents

This chapter informs you of general requirements for wiring the DP/DP Coupler and of the connections you need. Section

3.1

Topic

Page

3.1

Electrical isolation and grounding

3-1

3.2

Connections

3-6

3.3

Connecting the power supply

3-7

3.4

Connecting PROFIBUS DP

3-8

Electrical isolation and grounding

Overview of contents Section

Topic

Page

3.1.1

General rules and regulations for operation

3-2

3.1.2

Operation with a grounded supply

3-5

Dual 24 V DC power supply You may connect the DP/DP Coupler to two separate 24 V DC power supply modules.

Properties of the DP/DP Coupler • both PROFIBUS DP networks are galvanically isolated • both PROFIBUS DP networks are galvanically isolated from the 24 V DC power supply • both 24 V DC power supplies are galvanically isolated • PROFIBUS DP (network 1) and the logic components of the DP/DP Coupler are galvanically interconnected

DP/DP Coupler A5E00244669-03

3-1

Page 22

Wiring

Ungrounded power supply Note The DP/DP Coupler must be operated on a grounded 24 V DC power supply. It can not be operated on an ungrounded 24 V DC power supply!

3.1.1

General rules and regulations for operation

Introduction When the described modules are used in a system, certain rules and regulations must be followed that depend on the area of application. This section provides an overview of the most important rules that must be observed for safe integration in a system.

Specific applications Please comply with the safety and accident prevention regulations (e.g. machine protection guidelines) that are valid for specific applications.

EMERGENCY–OFF equipment EMERGENCY-OFF equipment to IEC 6204 (corresponds with DIN VDE 113) must retain an operational state in all operating modes of then system or plant.

3-2

DP/DP Coupler A5E00244669-03

Page 23

Wiring

Start-up of the system following specific events The following table shows what you have to look out for when the system starts up after certain events. In the case of ...

...

The system starts up after a voltage dip or power failure dangerous operating states may not develop. If necessary, force an ”EMERGENCY–OFF”!

Start-up of the system after interruption of bus communication, Startup after the ”EMERGENCY–OFF” system is released an uncontrolled or undefined state must be prevented.

Startup of the system without the DP master addressing the slaves,

24V DC power supply The following table shows what you have to look out for in the case of the 24V supply. In the case of ...

You must remember ...

Buildings

External lightning protection

Lightning protection measures (e.g. lightning conductors)

24 V DC power supply cables, signal cables

Internal lightning protection

24 V DC supply

Safety extra-low voltage with safe electrical isolation (SELV)

Note For information on lightning protection, refer to the S7–300 PLC; Installation installation manual.

Protection from external electrical interference The following table shows what you have to look out for to ensure protection against electrical influences or faults. In the case of ...

You must ensure that ...

All systems in which the modules are integrated

... The system is connected to the protective conductor so that electromagnetic interference can be discharged.

Connecting, signal and bus lines

... The cable has been routed and installed correctly.

Signal and bus lines

... Cable or conductor breaks do not lead to undefined system states.

DP/DP Coupler A5E00244669-03

3-3

Page 24

Wiring

Shielding braid of the PROFIBUS cable The shielding braid of the PROFIBUS cable must be terminated on a grounded shielding busbar. • Connect the shielding braid with the help of metal cable clamps. • Terminate the shielding to a shielding busbar which is mounted directly downstream of the cable inlet of the cabinet. • The clamp should provide good contact to a large area of the shielding.

Switch cabinet Figure 3-1

Termination of the PROFIBUS cable shielding on the grounded shielding busbar

3-4

DP/DP Coupler A5E00244669-03

Page 25

Wiring

3.1.2

Operation on a grounded power supply

Definition: Grounded power supply The neutral conductor of grounded supplies is bonded to earth. An earth fault between a voltage-carrying conductor or grounded part of the system trips the connected protective devices.

Components and protective measures Various components and protective measures are prescribed for the system installation. The type of components used and degree of protection for your system configuration is specified in accordance with DIN VDE directives. • Main switch (see Figure 3-2, DIN VDE 0100 Part 460 • Isolator (see Figure 3-2, DIN VDE 0113 Part 1

Operation on grounded power supply Figure 3-2 shows the position of the modules in a configuration connected to a TN-S power supply network. In installations with grounded reference potential, interference currents are discharged via the protective conductor. Note: The arrangement of the power connections shown does not correspond to the actual arrangement on the modules; it was selected in the interest of clarity. L1 L2 L3 N PE

Low-voltage distribution, e. g. TN-S system (3 x 400 V) Cabinet Rail

DP/DP Coupler AC DC

AC DC

L+ M

Logic

L+ M

Equipotential busbar in the switch cabinet

Figure 3-2

DP/DP Coupler A5E00244669-03

Configuration with a grounded supply

3-5

Page 26

Wiring

3.2

Connections

Connections of the DP/DP Coupler The figure below shows all interconnections of the DP/DP Coupler:

PROFIBUS DP network 2 24 V DC from network 1 Figure 3-3

3-6

24 V DC from network 2

PROFIBUS DP network 1

Connections of the DP/DP Coupler

DP/DP Coupler A5E00244669-03

Page 27

Wiring

3.3

Connecting the power supply

Required tool To connect the power supply, you require a 3 mm screwdriver.

Power supply unit You may only use power supply modules of the type PELV with electrically isolated operational extra–low voltage (v 60 V DC).

Dual power supply You can use two separate power supply sources for the DP/DP Coupler: • This power supply is redundant, i.e. in case of a module failure, the DP/DP Coupler automatically switches over the other source module. • If both connections are under load (network 1 / network 2), the DP/DP Coupler automatically uses the network 1 power source. • When using only a single power supply for the DP/DP Coupler, you should preferably connect this to PS2.

Note The diagnostic system shows you whether the DP/DP Coupler is connected to the 24 V DC power supply or not. Always set the “PS” switch on the DP/DP Coupler to the correct position! For further information on the DIL switch settings, refer to chapter 4.2.

Power supply connector The 4-pin 24 V DC power supply connector is located on the front panel of the DP/DP Coupler. The connections have the following functions:

Figure 3-4

DP/DP Coupler A5E00244669-03

L+

+24 V DC from network 1

M

Chassis ground fro network 1

L+

+24 V DC from network 2

M

Chassis ground from network 2

Power supply für den DP/DP Coupler

3-7

Page 28

Wiring The maximum conductor cross-section is 2.5 mm2. A cable strain relief is not provided. Step

Activity

1

Strip the wires to a length of 10 mm.

2

Connect the wires to the 2–pin screw terminals of the connector. This connector is plugged into the power supply socket on the supplied unit. When a dual power supply is available for the DP/DP Coupler, you should connect both. If you only have one, you should preferably connect it to PS2.

3

Plug the wired 2–pin connector into the power supply socket of your DP/DP Coupler.

4

Set the “PS” selector switch on the DP/DP Coupler:

• L+/M (PS1) connected to 24 V DC: Selector switch PS (DP1) to “ON” • L+/M (PS2) connected to 24 V DC: Selector switch PS (DP2) to “ON” The selector switch “PS” must be set properly in order to allow the correct evaluation of diagnostic data in STEP 7!

3.4

Connecting PROFIBUS DP

Required tool You need a screwdriver with a blade width of 3 mm to install the bus connector to the DP/DP Coupler.

Bus cable and connector Always use the accessories specified in appendix B for PROFIBUS DP. For information on handling bus cables and connectors, refer to the Distributed I/O System ET 200 manual.

Procedure To connect PROFIBUS DP: 1. Insert the bus connector into the PROFIBUS socket. 2. Tighten the mounting screws on the bus connector.