Page 17

2

Installation Overview of contents Section

2.1

Topic

Page

2.1

Installation principles

2-1

2.2

Installing the DP/DP Coupler

2-2

Installation principles

Mounting position The mounting position of the DP/DP Coupler is user–specific. Please note, that the ambient temperature may not exceed 60 when the device is mounted vertically, and for all other mounting positions 40 For further information on operational conditions, refer to chapter A.1.

Open equipment The DP/DP Coupler is an open device. It may only be installed in cubicles, cabinets or electrical control rooms which can only be accessed by means of a key or a tool. Only trained or authorized personnel should have access to the housings, cabinets or electrical control rooms.

Mounting system The DP/DP Coupler may be mounted on a DIN rail (7.5 mm and 15 mm), or on an S7 system profile rail . Ample free space of at least 40 mm above and below the module should be provided for the installation. For more information on installing S7 modules, refer to the S7-300 Programmable Controller, Installation manual.

DP/DP Coupler A5E00244669-03

2-1

Page 18

Installation

2.2

Installing the DP/DP Coupler

Components required • DP/DP Coupler • Profile rail: – DIN rail (7.5 mm or – 15 mm), or – a rail for the S7 mounting system Component order nos. are found in appendix B.

Installing the DP/DP Coupler on a DIN rail Step

Activity

1

When you install the DIN rail, make sure you provide at least 40 mm of free space above and below the modules in order to allow easy installation and the deflection of heat. Note: Always ensure a low–impedance connection between the DIN rail and the grounded sheet metal plate or mounting panel. For the installation on varnished or galvanized sheet metal you should use a suitable contact agent or contact disks, for example.

2-2

2

Hang the DP/DP Coupler onto the DIN rail and then swing it down.

3

Screw–tighten the DP/DP Coupler.

4

Wire the DP/DP Coupler as described in chapter 3.

DP/DP Coupler A5E00244669-03

Page 19

Installation

Installing the DP/DP Coupler on a profile rail for the S7 installation system Step

Activity

1

When you install the S7 profile rail, make sure you provide at least 40 mm of free space above and below the modules in order to allow easy installation and the deflection of heat. Note: Always ensure a low–impedance connection between the DIN rail and the grounded sheet metal plate or mounting panel. For the installation on varnished or galvanized sheet metal you should use a suitable contact agent or contact disks, for example.

2

Remove the slide from the bottom of your DP/DP Coupler with the help of a screwdriver (see fig. 2-1).

3

Hang the DP/DP Coupler onto the S7 profile rail and then swing it down.

4

Screw–tighten the DP/DP Coupler.

5

Wire the modules as described in chapter 3.

Figure 2-1

Remove the slide on the bottom of the module before you install it on the S7 system rail

Removing the DP/DP Coupler You remove the DP/DP Coupler in reverse order. Switch off the 24 V DC power supply to the DP/DP Coupler before you remove it.

DP/DP Coupler A5E00244669-03

2-3

Page 20

Installation

2-4

DP/DP Coupler A5E00244669-03