SIMATIC DP/DP Coupler Manual: 1 Product Overview

Pages 13 to 16 of 104, from SIMATIC DP/DP Coupler Manual

The original document is the PDF (923 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Siemens 6ES7-158-0AD00-0XA0

Page 13

1

Product Overview

1.1

Field of application and function

Field of application DP/DP Coupler is used to interconnect two PROFIBUS DP networks in order to enable the transfer of data between the master of both networks. The maximum length of transferred data consists of 244 bytes of input data and 244 bytes of output data. PG S7-400

S7-300

DP/DP Coupler ET 200X Figure 1-1

S7-300

ET 200S

ET 200L

Drive

DP/DP coupling of two PROFIBUS DP networks

Configuration You configure the DP/DP Coupler using either STEP 7 or a programming tool that integrates the DP/DP Coupler by means of a GSD file. In STEP 7, you can set up the required length of input and output data. The output data on one side of the DP/DP Coupler form the input data of the other, and vice versa. In STEP 7, define the I/O data areas based on the slot IDs.

DP/DP Coupler A5E00244669-03

1-1

Page 14

Product Overview

Example The example below shows the independence of both networks. That means, you configure a separate PROFIBUS address for each PROFIBUS DP network. In the figure below, that is PROFIBUS address 3 in network 1, and PROFIBUS -address 50 in network 2. DP/DP Coupler Output area PROFIBUS DP Network 1

PROFIBUS DP Network 1

Input area PROFIBUS DP Network 2

16 bytes

16 bytes

1.5 Mbps

Input area PROFIBUS DP Network 1

Output area PROFIBUS DP Network 2

PROFIBUS address 3

8 bytes

8 bytes 8 bytes

Figure 1-2

PROFIBUS DP Network 2

12 Mbps PROFIBUS address 50

Function principle of the DP/DP Coupler (example)

Both networks may operate at different baud rates. The rate at which network 1 writes data to the output buffer is slower than the rate at which network 2 reads these data. Hence, network 2 reads the same data successively. The effect is the reverse when data are transferred from network 2 to network 1. The output buffer will be overwritten several times before network 1 reads the data buffer. This means that only the currently written data are available.

Notice You need to balance the I/O area of both networks.

1-2

DP/DP Coupler A5E00244669-03

Page 15

Product Overview

Appearance The figure below shows the DP/DP Coupler and its operator and display elements: SIEMENS Indicator LEDs

SF1 SF2

DIL switch for network 1 (cf. chapter 4.2) ON: PROFIBUS address by means of STEP 7 on network 1 ON: Data validity indication enabled for network 1

DP1

DP2 64 32 16

BF1 BF2

DIL switch for network 2 (cf. chapter 4.2)

8

ON1

4 2

ON2

ON: PROFIBUS address by means of STEP 7 on network 2 ON: Data validity indication enabled for network 2

1 ADDR DIA PS

ON: DP/DP Coupler is connected to the power supply of network 1

ON

X1 DP1

ON

X2 DP2

PROFIBUS DP connection for network 1 Power supply connection for network 1 Power supply connection for network 2

ON: DP/DP Coupler is connected to the power supply of network 2 PROFIBUS DP connection for network 2

L+ M L+ M

Figure 1-3

Operator and display elements of the DP/DP Coupler

Features Properties of the DP/DP Coupler: • Maximum length of data exchanged consists of 244 bytes input data and 244 bytes of output data, of which up to 128 bytes are consistent • Up to 16 I/O areas for data exchange • If one side fails, the output values of the other are retained • DPV1 is supported with full and uniform diagnostic functions • PROFIBUS address setting either via selector switch on the DP/DP Coupler, or in STEP 7, or by means of another programming tool • Different transmission rates and PROFIBUS addresses on both sides of the DP/DP Coupler • Electrical isolation between the DP networks • Dual power supply

DP/DP Coupler A5E00244669-03

1-3

Page 16

Product Overview

1.2

Compatibility to precursor modules The DP/DP Coupler, order no. 6ES7 158-0AD01-0XA0, is compatible with the DP/DP Coupler, order no. 6ES7 158-0AD00.0XA0. We have enhanced the diagnostic information for SYNC and FREEZE mode on Link 6ES7 158-0AD01-0XA0 compared with DP/DP Coupler 6ES7 158-0AD00-0XA0, and adapted these data in accordance with PROFIBUS standard. The DP/DP Coupler 6ES7 158-0AD01-0XA0 can be used to replace previous module versions. The design is compatible. The DP/DP Coupler is available as spare part under order no. 6ES7 158-0AD00-0XA0.

1-4

DP/DP Coupler A5E00244669-03