MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: Appendices, pages 297 to 304

Pages 297 to 304 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 297

Issue 10/06

E.4

Removing fan

Removing fan. Frame Size F

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

297

Page 298

Removing fan

E.5

Issue 10/06

Removing fan. Frame Size F with filter

MICROMASTER 440

298

Operating Instructions 6SE6400-5AW00-0BP0

Page 299

Issue 10/06

E.6

Removing fan

Removing fan. Frame Sizes FX and GX When replacing the fans for sizes FX and GX. refer to the documentation CD ROM. directory - "Spares".

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

299

Page 300

Short circuit current rating (SCCR)

F

Issue 10/06

Short circuit current rating (SCCR)

Frame Sizes A to C The equipment has a "standard SCCR" value of 10 kA, which complies with the requirements of UL508C. In addition to the "standard SCCR" a "high SCCR" is available which can be used for industrial control panel installations in line with the National Electrical Code (NEC) article 409 (edition 2005) and Underwriters Laboratories UL508A (effective April 2006). The uL certification of MICROMASTER 440 allows the drives to adopt a high SCCR equal to the interupt current rating of the branch-circuit protection (BCP) device protecting the drive. Hence by selection of the correct uL listed BCP device with appropriate interrupt rating for the application, any high SCCR rating can be achieved for MICROMASTER 440, including SCCR values above 10 kA. The above statements are valid for the respective maximum voltage of the drive when protected by a UL recognised/listed H, J or K type fuse, a circuit breaker or self-protected combination motor controller.

Frame Sizes D to GX The equipment has a "standard SCCR" value of 42 kA, which complies with the requirements of UL508C. A "high SCCR", which can be used for industrial control panel installations in line with the National Electrical Code (NEC) article 409 (edition 2005) and Underwriters Laboratories UL508A (effective April 2006), can be achieved with the use of current limiting fuses or circuit breakers with an appropriate interrupt rating and derived let through current. For compliance with NEC article 409 and UL508A the calculation, selection and marking of the current limiting device must be carried out by an qualified engineer. The above statements are valid for the respective maximum voltage of the drive when protected by a UL recognised/listed H, J or K type fuse, a circuit breaker or self-protected combination motor controller

MICROMASTER 440

300

Operating Instructions 6SE6400-5AW00-0BP0

Page 301

Issue 10/06

G

Standards

Standards European Low Voltage Directive The MICROMASTER product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards: EN 61800-5-1 Adjustable speed electrical power drive systems, Part 5-1: Safety requirements – Electrical, thermal and energy EN 60204-1 Safety of machinery - Electrical equipment of machines European Machinery Directive The MICROMASTER inverter series does not fall under the scope of the Machinery Directive. However. the products have been fully evaluated for compliance with the essential Health & Safety requirements of the directive when used in a typical machine application. A Declaration of Incorporation is available on request. European EMC Directive When installed according to the recommendations described in this manual. the MICROMASTER fulfils all requirements of the EMC Directive as defined by the EMC Product Standard for Power Drive Systems EN61800-3. Underwriters Laboratories UL and CUL LISTED POWER CONVERSION EQUIPMENT ISO 9001 Siemens plc operates a quality management system. which complies with the requirements of ISO 9001.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

301

Page 302

List of Abbreviations

H

Issue 10/06

List of Abbreviations AC AD ADC ADR AFM AG AIN AOP AOUT ASP ASVM BCC BCD BI BICO BO BOP C CB CCW CDS CI CFM CM CMD CMM CO CO/BO COM COM-Link CT CT CUT CW DA DAC DC DDS DIN DIP DOUT

Alternating current Analog digital converter Analog digital converter Address Additional frequency modification Automation unit Analog input Advanced operator panel Analog output Analog setpoint Asymmetric space vector modulation Block check character Binary-coded decimal code Binector input Binector / connector Binector output Basic operator panel Commissioning Communication board Counter-clockwise Command data set Connector input Cubicfeet per minute (1 l/s ≅ 2,1 CFM) Configuration management Commando Combimaster Connector output Connector output / Binector output Common (terminal that is connected to NO or NC) Communication link Commissioning. ready to run Constant torque Commissioning. run. ready to run Clockwise Digital analog converter Digital analog converter Direct current Drive data set Digital input DIP switch Digital output

MICROMASTER 440

302

Operating Instructions 6SE6400-5AW00-0BP0

Page 303

Issue 10/06

List of Abbreviations

DS EEC EEPROM ELCB EMC EMF EMI ESB FAQ FB FCC FCL FF FFB FOC FSA GSG GUI ID HIW HSW HTL I/O IBN IGBT IND JOG KIB LCD LED LGE MHB MM4 MOP NC NO OPI PDS PID PKE PKW PLC PLI PPO PTC

Drive state European Economic Community Electrical erasable programmable read-only memory Earth leakage circuit breaker Electro-magnetic compatibility Electromotive force Electro-magnetic interference Equivalent circuit Frequently asked questions Function block Flux current control Fast current limit Fixed frequency Free function block Field orientated control Frame size A Getting started guide Global unique identifier Main actual value Main setpoint High-threshold logic Input and output Commissioning Insulated gate bipolar transistor Sub-index Jog Kinetic buffering Liquid crystal display Light emitting diode Length Motor holding brake MICROMASTER 4th. Generation Motor potentiometer Normally closed Normally open Operating instructions Power drive system PID controller (proportional. integral. derivative) Parameter ID Parameter ID value Programmable logic controller Parameter list Parameter process data object Positive temperature coefficient

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

303

Page 304

List of Abbreviations

PWE PWM PX PZD QC RAM RCCB RCD RFG RFI RPM SCL SDP SLVC STW STX SVM TTL USS VC VT ZSW ZUSW

Issue 10/06

Parameter value Pulse-width modulation Power extension Process data Quick commissioning Random-access memory Residual current circuit breaker Residual current device Ramp function generator Radio-frequency interference Revolutions per minute Scaling Status display panel Sensorless vector control Control word Start of text Space vector modulation Transistor-transistor logic Universal serial interface Vector control Variable torque Status word Additional setpoint

MICROMASTER 440

304

Operating Instructions 6SE6400-5AW00-0BP0