Manual12 pagesPDF 83 KB

User manual for the Siemens SIMATIC TI505 7MT Channel Controller (7MTCC), which lets a Series 505 CPU control 7MT I/O.

What this file really is

The old site listed this file as a manual for the Siemens 7MT200 and Texas Instruments 7MT200. Linked as the 7MT200 manual, but it is the user manual for the 7MT Channel Controller (7MTCC) and does not name the 7MT200.

Download the PDF83 KB

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Siemens' short user manual for the SIMATIC TI505 7MT Channel Controller (7MTCC), the module that lets a Series 505 CPU control 7MT I/O. It explains inserting the module, connecting it to the 7MT system, powering the 7MT I/O, checking status indicators and configuring it into CPU memory, then programming with control words and control blocks, update times and timing estimates, fatal and non-fatal error codes, and specifications.

Its parts

  1. Overview
  2. Installing the 7MTCC
  3. Operating the 7MTCC
  4. Scan Times and Error Codes
  5. Specifications and References

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

A user manual for the SIMATIC TI505 7MT Channel Controller (7MTCC), a module that lets a Series 505 CPU control 7MT I/O. It does not print the 7MT200 designation the site files it under. It covers installing the module, setting up its configuration table and control blocks in V-memory, scan times, LED error codes and specifications.

Device
Channel controller module that lets a Series 505 CPU control 7MT I/O p. 4
Capacity
Two 7MT I/O bases, 128 7MT I/O channels per controller p. 4
Mounting
Any I/O slot in a local or remote Series 505 base; not in a distributed base p. 5
Interface cable
910–36 to the 7MT system p. 5
Module type
4WX/4WY special function module p. 5
Backplane power
4.0 W of +5 V; 0 W of –5 V p. 11
Control blocks
Up to 48, in a configuration table of at least 196 words in V-memory p. 8
Block size
Up to 512 words for each read and write block p. 6
Status LEDs
MOD GOOD (blinks for fatal errors) and COMM (blinks for non-fatal errors) p. 5, 10
COMM error codes
2 blinks: invalid configuration table address in WY5; 3: invalid write block address or size; 4: invalid read block address or size; 5: invalid control block information; 6: overlapping V-memory read/write tables p. 10
Operating temperature
0 to 60°C (32 to 140°F) p. 11
Storage temperature
–40 to +70°C (–40 to 158°F) p. 11
Relative humidity
5% to 95% noncondensing p. 11
Agency approvals
The manual states UL Listed (UL508 industrial control equipment) and CSA Certified (CSA142 process control equipment) p. 11

What this manual walks you through

  • Inserting the module in a Series 505 base p. 5
  • Powering the 7MT I/O bases p. 4, 5
  • Upgrading from a PM550 controller to a Series 505 CPU p. 5
  • Configuring the module in the CPU I/O definition chart p. 5
  • Reading the status word and acknowledge bits p. 6
  • Setting the configuration table address and command bits p. 7
  • Defining control blocks, with a worked example p. 8, 9
  • Changing the configuration table p. 8
  • Estimating read and write scan times p. 10
  • Diagnosing fatal and non-fatal errors from LED blinks p. 10

Good to know

  • Turn off power to the base and modules before installing or removing a module, cable or terminal block. p. 5
  • The 7MT I/O addressing scheme of the PM550 Programming Manual does not work with this controller. p. 6
  • Tables must sit at V-memory addresses below 65,536, or a configuration error occurs. p. 6
  • Acknowledge bits do not confirm that a 7MT I/O module actually performed the task. p. 6
  • On a fatal error the controller halts and the 7MT I/O hold their last valid state. p. 10

Questions this manual answers

How many 7MT I/O channels can one 7MT Channel Controller handle?

One controller connects to two 7MT I/O bases, for 128 7MT I/O channels. p. 4

What cable connects the 7MT Channel Controller to the 7MT system?

Cable part number 910–36. p. 5

What does 2 blinks of the COMM LED mean?

An invalid configuration table address in WY5. p. 10

When does the COMM LED come on on the 7MT Channel Controller?

It comes on when the module is configured correctly in the I/O table and WY5 holds a non-zero value. p. 5

Can I keep my PM550 power supply when moving to a Series 505 CPU?

Yes. Keep the PM550 power supply connected to the 7MT I/O base with the same cable. p. 5

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Title1
  2. 7MT Channel Controller3
    1. 1.1 Overview4
    2. 1.2 Installing the 7MTCC5
    3. 1.3 Operating the 7MTCC6
    4. 1.4 Scan Times and Error Codes10
    5. 1.5 Specifications and References11

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 121-12

The file

Revision and size

Part no.PPX:505-8115-2
RevisionSecond Edition, 01/21/92
PublisherSiemens Industrial Automation, Inc.
Pages12
PDF83 KB
TextText from the PDF itself; page 12 is a scan, read by OCR, which may hold reading errors.
PPX:505-8115-2

The first pages · 3 of 12

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 12
Page 2
Page 2of 12
Page 3
Page 3of 12