Summary
What is in it
Siemens' short user manual for the SIMATIC TI505 7MT Channel Controller (7MTCC), the module that lets a Series 505 CPU control 7MT I/O. It explains inserting the module, connecting it to the 7MT system, powering the 7MT I/O, checking status indicators and configuring it into CPU memory, then programming with control words and control blocks, update times and timing estimates, fatal and non-fatal error codes, and specifications.
Its parts
- Overview
- Installing the 7MTCC
- Operating the 7MTCC
- Scan Times and Error Codes
- Specifications and References
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
A user manual for the SIMATIC TI505 7MT Channel Controller (7MTCC), a module that lets a Series 505 CPU control 7MT I/O. It does not print the 7MT200 designation the site files it under. It covers installing the module, setting up its configuration table and control blocks in V-memory, scan times, LED error codes and specifications.
- Device
- Channel controller module that lets a Series 505 CPU control 7MT I/O p. 4
- Capacity
- Two 7MT I/O bases, 128 7MT I/O channels per controller p. 4
- Mounting
- Any I/O slot in a local or remote Series 505 base; not in a distributed base p. 5
- Interface cable
- 910–36 to the 7MT system p. 5
- Module type
- 4WX/4WY special function module p. 5
- Backplane power
- 4.0 W of +5 V; 0 W of –5 V p. 11
- Control blocks
- Up to 48, in a configuration table of at least 196 words in V-memory p. 8
- Block size
- Up to 512 words for each read and write block p. 6
- Status LEDs
- MOD GOOD (blinks for fatal errors) and COMM (blinks for non-fatal errors) p. 5, 10
- COMM error codes
- 2 blinks: invalid configuration table address in WY5; 3: invalid write block address or size; 4: invalid read block address or size; 5: invalid control block information; 6: overlapping V-memory read/write tables p. 10
- Operating temperature
- 0 to 60°C (32 to 140°F) p. 11
- Storage temperature
- –40 to +70°C (–40 to 158°F) p. 11
- Relative humidity
- 5% to 95% noncondensing p. 11
- Agency approvals
- The manual states UL Listed (UL508 industrial control equipment) and CSA Certified (CSA142 process control equipment) p. 11
What this manual walks you through
- Inserting the module in a Series 505 base p. 5
- Powering the 7MT I/O bases p. 4, 5
- Upgrading from a PM550 controller to a Series 505 CPU p. 5
- Configuring the module in the CPU I/O definition chart p. 5
- Reading the status word and acknowledge bits p. 6
- Setting the configuration table address and command bits p. 7
- Defining control blocks, with a worked example p. 8, 9
- Changing the configuration table p. 8
- Estimating read and write scan times p. 10
- Diagnosing fatal and non-fatal errors from LED blinks p. 10
Good to know
- Turn off power to the base and modules before installing or removing a module, cable or terminal block. p. 5
- The 7MT I/O addressing scheme of the PM550 Programming Manual does not work with this controller. p. 6
- Tables must sit at V-memory addresses below 65,536, or a configuration error occurs. p. 6
- Acknowledge bits do not confirm that a 7MT I/O module actually performed the task. p. 6
- On a fatal error the controller halts and the 7MT I/O hold their last valid state. p. 10
Questions this manual answers
How many 7MT I/O channels can one 7MT Channel Controller handle?
One controller connects to two 7MT I/O bases, for 128 7MT I/O channels. p. 4
What cable connects the 7MT Channel Controller to the 7MT system?
Cable part number 910–36. p. 5
What does 2 blinks of the COMM LED mean?
An invalid configuration table address in WY5. p. 10
When does the COMM LED come on on the 7MT Channel Controller?
It comes on when the module is configured correctly in the I/O table and WY5 holds a non-zero value. p. 5
Can I keep my PM550 power supply when moving to a Series 505 CPU?
Yes. Keep the PM550 power supply connected to the 7MT I/O base with the same cable. p. 5