The text of a manual · part 1 of 1
SIMATIC TI505 7MT Channel Controller User Manual, pages 1 to 12
Pages 1 to 12 of 12: Title; 7MT Channel Controller
The original document is the PDF (83 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Texas Instruments 7MT200 and Siemens 7MT200
Page 1
SIMATIC TI505 7MT Channel Controller User Manual
Order Number: PPX:505–8115–2 Assembly Number: 2586546–0075 Second Edition
Page 2
Copyright 1992 by Siemens Industrial Automation, Inc. All Rights Reserved, Printed in USA Reproduction, transmission or use of this document or contents is not permitted without express consent of Siemens Industrial Automation, Inc. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. Since Siemens Industrial Automation, Inc. does not possess full access to data concerning all of the uses and applications of customer’s products, we do not assume responsibility either for customer product design or for any infringements of patents or rights of others which may result from our assistance.
01/21/92
Technical data is subject to change. We check the contents of every manual for accuracy at the time it is approved for printing; however, there may be undetected errors. Any errors found will be corrected in subsequent editions. Any suggestions for improvement are welcomed.
Page 3
7MT Channel Controller 1.1
1.2
1.3
1.4
1.5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2
Installing the 7MTCC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
Inserting Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the 7MTCC to the 7MT System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Providing Power to the 7MT I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checking Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuring the 7MTCC into CPU Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 1-3 1-3 1-3 1-3
Operating the 7MTCC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
Programming Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checking 7MTCC and 7MT Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changing the Configuration Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 1-4 1-5 1-6 1-6
Scan Times and Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
Update Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Timing Estimates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Non-fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Ladder Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8 1-8 1-8 1-8 1-8
Specifications and References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9
7MT Channel Controller
1-1
Page 4
1.1
Overview
This manual describes the SIMATIC TI505 7MT Channel Controller (7MTCC).
in your Series 505 base as the CPU V memory allows. Refer to Figure 1-1 for an example.
The 7MTCC allows a Series 505 CPU to control 7MT I/O. You can connect one 7MTCC to two 7MT I/O bases, for 128 7MT I/O channels per 7MTCC. You can install as many 7MTCCs
References Before using the 7MTCC, you must be familiar with the documentation needed to use this product. Refer to the manuals listed on page 1-9.
PM550 power supply or equivalent ±12/+5 V power supply*
7MT I/O
7MT CH CONTROLLER MOD GOOD
COMM
7MT I/O
7MTCC 7MTCC
7MT BASE
CPU
Power Supply
Series 505 base
PM550 power supply or equivalent V power supply*
7MT I/O 505–7190 *±12 VDC power is not required for Series 505 7MT I/O, but may be required by other manufacturers’ modules.
7MT I/O
Figure 1-1 7MTCC and System Configuration
1-2
7MT Channel Controller
Page 5
1.2
Installing the 7MTCC
!
WARNING
To minimize potential electrical shock, turn off power to the base and modules before installing or removing a module, cable, or terminal block. Failure to do so may result in potential injury to personnel or damage to equipment. Be sure to refer to the safety guidelines in your system manuals before installing equipment.
Inserting Module Insert the 7MTCC into any I/O slot on a local or remote base; the 7MTCC does not operate in a distributed base. Use at least 2.6 inch-pounds (0.3N-m) torque on the bezel screws. The number of 7MTCCs you can install in a base is limited by the size of the CPU V-memory. Connecting the 7MTCC to the 7MT System Use cable part number 910–36 to connect the module to the 7MT system.
!
CAUTION
To help avoid potential damage to equipment, verify that 7MT power and communications are attached and that power is enabled before using the system.
Providing Power to the 7MT I/O Each set of two 7MT bases must have a power supply as shown in Figure 1-1. To upgrade your controller from a PM550 to a Series 505 CPU, retain the PM550 power supply and leave it connected to the 7MT I/O base with the same cable. Most 7MT modules require user power; aside from that, no further power connections are needed. For applications requiring any other type of power supply, call your Siemens Industrial Automation, Inc. distributor for the recommended connection procedure. The procedure requires direction from technical support personnel to help ensure that safety precautions are followed. If you need assistance in contacting your distributor, call (800) 964–4114 to find out the name of your distributor. Checking Status Indicators The MOD GOOD LED comes on about two seconds after power-up. If it does not, power-down the system, remove the 7MTCC, and configure I/O again. Reinstall the 7MTCC using appropriate safety precautions; if the LED still fails to light, return the 7MTCC to Siemens for repair. The COMM LED comes on if the 7MTCC is configured correctly in the I/O table and there is a non-zero value in WY5. If either LED blinks, refer to Table 1-5 and Table 1-6 for a list of fatal and non-fatal errors. Configuring the 7MTCC into CPU Memory The 7MTCC is a 4WX/4WY special function module. Figure 1-2 shows an I/O definition chart with a 7MTCC installed in slot 1 with the first word beginning at WX1. Of course, I/O number can change according to your application program. Refer to your TISOFT manual for detailed instructions on selecting the chart.
SLOT
I/O MODULE DEFINITION FOR: CHANNEL. . . 1 BASE. . . 00 NUMBER OF BIT AND WORD I/O I/O SPECIAL ADDRESS X Y WX WY FUNCTION
1
0001
00
00
04
04
YES
2
0000
00
00
00
00
NO
3
0000
00
00
00
00
NO
4
0000
00
00
00
00
NO
5
0000
00
00
00
00
NO
6
0000
00
00
00
00
NO
7
0000
00
00
00
00
NO
8
0000
00
00
00
00
NO
Figure 1-2 I/O Definition Chart
7MT Channel Controller
1-3
Page 6
1.3
Operating the 7MTCC
Programming Overview
Be sure to limit your tables to V-memory addresses below 65,536. A configuration error occurs when table addresses exceed 65,535.
The 7MTCC uses controller V-memory to transfer information between the CPU and the 7MT I/O system. Figure 1-3 gives an overview of the 7MTCC operation.
Checking 7MTCC and 7MT Status Table 1-1 shows status words WX1–WX4.
NOTE: The 7MT I/O addressing scheme described in the PM550 Programming Manual does not work with the 7MTCC. The programming method used with the 7MTCC involves V-memory addresses for control blocks.
Transfers of information occur in read and write blocks. Each read and write block transfers all data in one scan. The maximum block size is 512 words for both blocks, although timing estimates are calculated based on 480 words total. If your program is limited to reads or writes only, set both the size and address of the other type of block to zero (0).
•
Word WX1 is the 7MTCC status word. A value of 1 in bit 1 means that the MOD GOOD LED is on; a value of 1 in bit 2 means that the COMM LED is on.
•
Words WX2–WX4 contain acknowledge bits from the 7MT tasks as shown in Figure 1-3. A value of 1 means the programmed task has been performed; a value of 0 means the programmed task has not been performed.
•
Acknowledge bits are set when a control block exists and the corresponding command bit (Table 1-2) is set. A 7MT I/O module does not have to be in the 7MT base for these bits to be set. The data is transferred, but there is no feedback from the 7MT I/O to verify that the programmed task was actually performed.
Table 1-1 Status Word and Acknowledge Bits MOD GOOD LED COMM LED WX1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
WX2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
WX3
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
WX4
33 34 MSB
35
36
37
38
39
40
41
42
43
44
45
46
Status Bits
32 Acknowledge Bits 47 48 LSB
Write block - in V-memory Read block - in V-memory 7MTCC status bits - WX1 Acknowledge bits - WX2–WX4
Figure 1-3 7MTCC Operation
1-4
7MT Channel Controller
To 7MT From 7MT
7MT I/O
CPU
Configuration table in V-memory - WY5
7MT Channel Controller
Command bits - WY6–WY8
Page 7
Control Words Word WY5 must contain the integer value of the beginning V-memory address of the configuration table. See Table 1-2. The 7MTCC does not begin operation until WY5 contains a non-zero number. The first four consecutive V-memory locations within the configuration table, beginning with the address defined in WY5, contain the following information in the order listed: •
WRITE BLOCK is the beginning V-memory address.
•
WRITE BLOCK size is the number of V-memory locations required by the I/O.
•
READ BLOCK is the beginning V-memory address.
• loaded with the correct data depending upon the type of 7MT I/O installed. Upon operation, the data in the WRITE BLOCK is transferred to the appropriate 7MT I/O module in the manner defined by the corresponding control block. Words WY6–WY8 contain the 7MTCC command bits. Each command bit corresponds to a control block. For example, setting bit 32 (LSB of WY7) to value of 1 causes the operation defined in the 32nd control block in the configuration table to be performed. The transition from 0 to 1 initiates the operation. Once the 7MTCC is configured, its operation can be controlled through two methods: •
All transfers of data from the PLC to 7MT I/O can be started or stopped simultaneously by changing the value in WY5 ( a value of 0 halts operation and the integer value of the beginning address of the configuration table starts/continues operation).
•
Transfers of data to individual 7MT I/O modules may be controlled by setting the corresponding command bit(s) to the desired value.
READ BLOCK size is the number of V-memory locations required by the I/O.
READ and WRITE BLOCK sizes may exceed the actual required but should be defined as small as the 7MT I/O allows to enable the 7MTCC to operated more efficiently. Once the WRITE BLOCK V-memory boundaries have been defined, the appropriate V-memory locations within the WRITE BLOCK must be
Table 1-2 Control Word and Command Bits
WY5
Configuration Table V-Memory Starting Address
WY6
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
WY7
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
WY8
MSB
Command Bits
48 LSB
7MT Channel Controller
1-5
Page 8
Operating the 7MTCC (continued) Control Blocks The 7MTCC is programmed to communicate with the 7MT I/O through the use of control blocks in the configuration table. Up to 48 control blocks may be defined. Each control block contains four elements of variable information. These are described below: •
TASK is a value of 0–4 that defines which type of data operation to perform. See Valid Task Values in Figure 1-4.
•
7MT ADDRESS is the value of actual AIM address to be accessed. This is determined by the 7MT I/O modules physical location in the 7MT base and word address within the I/O module. Starting boundary address for each module are 000–700 for the first base, and 800–1500 for the second base, with a possible 32 locations at each boundary, depending upon the type of module used.
•
•
1-6
NUMBER OF WORDS refers to the integer value of the number of data words (READ or WRITE) determined by the type of 7MT module installed. V-MEMORY OFFSET refers to the integer value of the V-memory offset from the V-memory READ or WRITE block beginning address. This value determines the actual V-memory location where a given 7MT I/O modules data resides within the READ or WRITE blocks.
7MT Channel Controller
All 7MT modules require at least one control block to operate. Other modules, especially those that are configured through software rather than jumper selection, may require as many as three control blocks. Figure 1-4 shows an example 7MT base and its associated control blocks with the configuration table V-memory beginning address at V2000. Note that for every configuration table defined, the minimum configuration size is 196 words. The configuration table beginning address and the next 195 consecutive addresses must only be used for valid configuration table information. Changing the Configuration Table To change the 7MTCC configuration table, follow these steps: 1.
Write a value of 0 to WY5. Bit 2 of WX1 goes to 0. The 7MTCC operation ceases.
2.
Edit V-memory to change the configuration table.
3.
Perform a Write operation. Bit 2 of WX1 remains 0.
4.
Write the configuration table beginning address value to WY5. Bit 2 of WX1 goes to 1. The module resumes operation.
Page 9
80 Write block size in words
V2002
1101 V-memory read block address
Open slot
V2001 Open slot
1001 V-memory write block address
Open slot
RTD input
V2000
V2003
80 Read block size
Control block 1
V2004 V2005 V2006 V2007
2 000 4 0
Task (continuous WRITE) AIM address Number of words V-memory offset from write block address
Control block 2
V2008 V2009 V2010 V2011
1 100 4 0
Task (continuous READ) AIM address Number of words V-memory offset from read block address
V2012 V2013 V2014 V2015
4 200 32 4
Task (one-time WRITE) AIM address Number of words V-memory offset from write block address
V2016 V2017 V2018 V2019
1 200 32 4
Task (continuous READ) AIM address Number of words V-memory offset from read block address
V2020 V2021 V2022 V2023
1 300 4 36
Task (continuous READ) AIM address Number of words V-memory offset from read block address
V2024 V2025 V2026 V2027
4 304 2 36
Task (one-time WRITE) AIM address Number of words V-memory offset from write block address
V2028 V2029 V2030 V2031
4 310 1 42
Task (one-time WRITE) AIM address Number of words V-memory offset from write block address
V2032 V2033 V2034 V2035
4 400 32 43
Task (one-time WRITE ) AIM address Number of words V-memory offset from write block address
V2036 V2037 V2038 V2039
1 400 32 40
Task (continuous READ) AIM address Number of words V-memory offset from read block address
Control blocks 3/4
Control blocks 5–7
Valid Task Values 0: none 1: continuous read 2: continuous write 3: one-time read 4: one-time write
Contents Description
7MT–1300
Thermocouple 7MT–1504
Pulse input 7MT–1100
Thermocouple 7MT–500
7MT–210
Analog output
Address
Control blocks 8/9
Figure 1-4 Configuration Example
7MT Channel Controller
1-7
Page 10
1.4
Scan Times and Error Codes
Update Times 7MT and PLC update times are different. Be sure to refer to all appropriate user manuals to determine the update times of all components of your system. Timing Estimates The timing estimates in this section are based on a total of 480 words. Although it is possible to increase the total to 512 words per block, this has the effect of adding one scan to each number of scans listed in Table 1-3 and Table 1-4. Fatal Errors Fatal errors are reported by the MOD GOOD LED; it blinks a specific number of times depending on which type of error occurs. Refer to Table 1-5.
Table 1-3 One-time Read/write Request Response
Acknowledge Response
Command
Typical
Max
Typical
Max
Read
2 scans
3 scans
1 scan
1 scan
Write
1 scan
2 scans
1 scan
1 scan
Table 1-4 Continuous Read/write Update Command
Typical
Maximum
Read
1 scan
2 scans
Write
1 scan
2 scans
Table 1-5 Fatal Errors When a fatal error occurs, the 7MTCC halts operation and the 7MT I/O are held in their last valid state. Non-fatal Errors The COMM LED blinks a specific sequence of times depending on which type of error occurs. Refer to Table 1-6.
Blinks 2 3 4 5 6
Type of Error Watchdog time-out RAM ROM SFIC Other
Table 1-6 Non-fatal Errors Blinks
Error Type
2
Invalid configuration table address in WY5
1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0
3
Invalid write block address or size
1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1
4
Invalid read block address or size
1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
5
Invalid control block information
1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1
6
Overlapping V-memory read/write tables
1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0
Using Ladder Logic The 7MTCC can be configured and controlled entirely through the use of ladder logic. Any conventional programming method that reads or writes V, WX, or WY memory locations can
1-8
WX1 Contents
7MT Channel Controller be used. Since V-memory is used for the transfer of data, the actual I/O data is readily available and easily accessed by ladder logic programs.
Page 11
1.5
Specifications and References
Maximum power required from Series 505 backplane
4.0 W of +5 V power; 0 W of –5 V power
Operating temperature
0 to 60°C (32 to 140°F)
Storage temperature
–40 to +70°C (–40 to 158°F)
Relative humidity
5% to 95% noncondensing
Pollution degree
2, IEC 664, 664 A
Vibration
Sinusoidal IEC 68-2-6, Test Fc 0.15 mm peak-to-peak, 10–57 Hz; 1.0 g, 57–150 Hz Random IEC 68-2-34, Test Fdc, equivalent to NAVMAT P–9492 0.04 g2/ Hz, 80–350 Hz
Electrostatic discharge
IEC 801, Part 2, Level 4, (15 kV)
Shock
IEC 68-2-27; Test Ea
Noise immunity, radiated
IEC 801, Part 3, Level 3, MIL STD 461B RS01, and RS02
Corrosion protection
All parts of corrosion-resistant material or plated or painted as corrosion protection
Agency Approvals
UL Listed (UL508 industrial control equipment) CSA Certified (CSA142 process control equipment) FM Approved (Class I, Div. 2, Haz. Location) Verband Deutscher Elektrotechniker (VDE) 0160 Clearance/Creepage for Electrical Equipment (Self-Compliance) Series 505 products have been developed with consideration of the draft standard of the International Electrotechnical Commission Committee proposed standard (IEC–65A/WG6) for programmable controllers.
References
•
Model 7MT–1504 Thermocouple Input Module User Manual (PPX:7MT–8114)
•
Model 7MT–1300 RTD Module Reference Guide (2483770–0005)
•
Model 7MT–100 Analog Input Module User Manual (PPX:7MT–8101)
•
Model 7MT–700 8-Channel High-speed Analog Input Module User Manual (2493770–0007)
•
Model 7MT–1100 Pulse Input Module User Manual (PPX:7MT–8111)
•
Model 7MT–600 High-speed Analog Output Module User Manual (2493770–0009)
•
Series 505 Hardware/Installation Manual (PPX:505–8103)
•
Series 505 Programming Reference Manual (PPX:505–8104)
•
PM550 Programming Manual (PPX:550–8101)
•
User Manual for your TISOFT release
7MT Channel Controller
1-9
Page 12
SIMATIC is a registered trademark of Siemens AG. PM550 (Program Master 550), Series 505 and TISOFT are trademarks of Siemens Industrial Automation, Inc.
Texas Instruments and TI are registered trademarks of Texas Instruments Incorporated. T1505 is a trademark of Texas Instruments Incorporated.
UL is a registered trademark of Underwriters Laboratories, Inc.