Product Information for the ET 200B Distributed I/O System Applicability
This Product Information refers to the ET 200B Distributed I/O Device manual, edition 04 (order no.: 6ES5 998-4ET.1).
General Information on the ET 200B Section 3.6, Pg. 3-28: Wiring the Bus Connection
The supply voltage on the PROFIBUS-DP port is intended for connecting a bus connector, an ET 200 hand-held device (only in the case of digital modules) or an OLP.
Section 5.2, Pg. 5-4: Error Display Analog ET 200B
The display of the “DIA” diagnostic LED has the following additional significance for the analog modules of the ET 200B:
Section 8.4.1, Table 8-3: Compensation Units
The type U compensation unit described on page 8-9 in table 8-3 together with its accessories is no longer supplied.
Section 8.4.5, Pg. 8-39: Resolution
Note on table 8-25 on page 8-39:
If you set ”disable” for the ”Diagnostics Alarm” parameter and ”enable” for the ”Diagnostics Enable CH0” parameter (for channel/channel group) during parameterization, when there is an error on the corresponding channel the “DIA” LED comes on, although disabling the diagnostics alarm prevents a diagnosis from being reported to the CPU.
Hinweis The possible resolutions in table 8-25 do not apply to temperature values. The converted temperature values are the result of a conversion in the analog module.
Section 8.6.1, Pg. 8-78: Rules
Third rule (third point):
The terminals of unused outputs are left open when voltage output (V measurement) is configured.
The terminals of unused outputs must be shorted whencurrent output (I measurement) is configured.
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
1
Page 2
Product Information ET 200B
Section 5.3.8, Pg. 5-21: Measurement Range Underflow
In the event of a wire break, the ET 200B-4AI analog module up to and including release 2 may report a measurement range underflow instead of a wire break. As of release 3, the following values apply in tables 8-50 and 8-54 in the ET 200B Distributed I/O Device manual:
Table 8-50, Pg. 8-69
Tabelle 8-50 Units
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measurement Range: 4 to 20 mA) Digitized Measured Value1
Measured value in mA
4 ... 20 mA 15 14 13 12 11 10 9 8 7 6 5 4 3
1
Table 8-54, Pg. 8-71
Range
2 1 0
2559
19.992
0 1 0 0 1 1 1 1 1 1 1 1 1 0 0 1
2048
16.000
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
512
4.000
0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
511
3.992
0 0 0 0 1 1 1 1 1 1 1 1 1 0 0 0
384
3.000
0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0
383
2.992
0 0 0 0 1 0 1 1 1 1 1 1 1 0 0 0
151
1.185
0 0 0 0 0 1 0 0 1 0 1 1 1 0 0 0
4095
< 1.185
0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
Rated range
Wire break
Same representation in data format twos complement, value and sign and binary representation
Tabelle 8-54
Representation of Digitized Measured Values of the ET 200B-4AI (Measurement Range: 0 to 20 mA and 4 to 20 mA)
Measurement Range from 0 to 20 mA
Measurement Range from 4 to 20 mA
Decimal
Hexadecimal
23.5185
22.815
32767
7FFFH
23.518
22.814
32511
7EFFH
:
:
:
:
Units Range
Overflow
Overrange
20.0007
20.0006
27649
6C01H
20.000
20.000
27648
6C00H
15.000
16.000
20736
5100H
:
:
:
:
0.000
4.000
0
0H
-0.0007
3.9995
–1
FFFFH
:
:
:
:
–4864
ED00H
–32768
8000H
Underflow
–32768
8000H
Wire break
–3.5185
1.1852
2
X X O
Rated range
Underrange
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
Page 3
Product Information ET 200B
Section 8.6.3, Pg. 8-84: Parameters
In table 8-58 on page 8-84 it is also possible to specify that the channel is not activated for output value and range.
Section A.1, Pg. A-3: Analog Modules
Note on table A-2 on page A-3: Hinweis The SIxxxAD.200 and SIxxxTD.200 type files contain the normal identifier format for configuration (see table D-7). The SIxxxBD.200 type files contain the special identifier format (see table B-4). If, while running an analog ET 200B module, reconfiguration is carried out with another type file version (e.g. previously with SIxxxAD.200 and subsequently with SIxxxBD.200, or vice versa), you must carry out a STOP-RUN transition on the analog module.
Section B, Pg. B-1: Normal ID format
The following applies to ET 200B analog modules as of release 3: To permit analog ET 200B modules to be connected to DP masters of other manufacturers, all analog ET 200B modules as of release 3 also support the normal identifier format. The prerequisite for this is that your non-Siemens master must send a control command (”UNCLEAR”) cyclically and be able to process diagnostic frames up to 29 bytes in length. If your non-Siemens master does not fulfill these requirements, you can only run the ET 200B modules by means of a device master file created using COM PROFIBUS on the basis of the SIxxxAD.200 type files. For non-Siemens masters, COM PROFIBUS allows you as of version V3.1 to create a device master file for every analog ET 200B module with address identifiers in the normal identifier format. The type files for COM PROFIBUS and STEP 7 still contain the preset address identifiers in the special identifier format for these analog modules. As of release 3, a DP master can read the normal identifier format from the analog ET 200B modules after each power on as in table D-7 (ET 200B Distributed I/O Device manual). If the special identifier format is used in configuration, the module makes the special identifier format available.
Updating of the Slave Diagnostics
As long as the DP master is in CLEAR mode, the diagnostic information of the ET 200B modules is not updated.
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
3
Page 4
4
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
Page 5
Product Information for the X 4 5 6
TB3-4/DC, 6ES7 193-0CA40-0XA0, as of version
Fig. I
10
1
2 9
3 4 5
6
7
8
Fig. II
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
5
Page 6
Product Information for the TB3-4/DC
Fig. III
Fig. IV 24 V
PROFIBUS-DP
5V 24 V ET 200B-16DO
Logic
5V
8x
8x
Supply Q0: 0...7
TB3-4/DC
X1
Q1: 0...7
L1+ L2+ L3+ M
Interface between electronics block and terminal block Suppr. Logic STOP/RUNswitch
Station number selection PROFIBUS-DP connection
Outp.
L1+ L2+ L3+ M
M Ground PE PE Screw for grounded configuration
6
Digital outputs
24 V supply
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
Page 7
Product Information for the TB3-4/DC
Description
The TB3-4/DC terminal block belongs to the family of the ET 200B distributed I/O station modules. Fig. I: Basic construction: TB3-4/DC terminal block (spring-release terminal) 1 Polarization slide 2 Switch for setting the station number (this number is not accepted by the system until you actuate the STOP/RUN switch (STOP RUN)) 3 PROFIBUS-DP interface 4 Screw for connecting frame to PE 5 M5 screw for connecting PE 6 Terminal block for inputs/outputs 7 Slide for removing the terminal block from the standard mounting rail 8 Terminals for the logic supply and the load power supply 9 STOP/RUN switch for switching the power supply to the logic components in the electronics block on and off. The STOP/RUN switch also switches the ET 200B distributed I/O station on and off. 10 Fuse Fig. II: Dimension drawing: TB3-4/DC terminal block Fig. III: Terminal designations: TB3-4/DC terminal block Fig. IV: Block diagram: TB3-4/DC terminal block and ET 200B-16DO
Characteristics
The TB3-4/DC terminal block (spring-release terminal, 4-tier) offers the same functionality as the TB1-4/DC terminal block (screw terminal, 4-tier). The only difference is that the TB3-4/DC is fitted with a 4-tier spring-release terminal. The ET 200B-16DI, -16DO, -8DI/8DO, -8DI/8DO HWA and -8RO electronics blocks can all be connected to the TB3-4/DC terminal block.
Installation and settings
You can find details of how to install and set the terminal blocks of the ET 200B in the ET 200B Distributed I/O Station manual.
Input/output connections
The assignment of the inputs and outputs on the terminal blocks of the TB3-4/DC depends on the type of electronics block mounted on them. The pin-out of all the plug-in electronics blocks for the TB1-4/DC is described in the ET 200B Distributed I/O Station manual. This pin-out is the same as for the TB3-4/DC.
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
7
Page 8
Product Information for the X 4 5 6
TB4-4/DC, 6ES7 193-0CB40-0XA0, as of version
Fig. I
10
1
2 9 3 4 5
6
7
8
Fig. II
8
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
Page 9
Product Information for the TB4-4/DC
Fig. III
Fig. IV 24 V
PROFIBUS-DP
5V 24 V ET 200B-16DO/2A
Logic
4x
4x
Q0: L1+ M1 0...3
5V
4x
4x
Q1: Q0: Q1: L2+ M2 4...7 L3+ M3 0...3 L4+ M4 4...7
Interface between electronics block and terminal block
X1 Station number selection TB4-4/DC
L5+ M5
Suppr. logic
PROFIBUS-DP Connection M5
PE
Suppr. logic
L1+ M1
L2+ M2
Suppr. logic L3+ M3
Suppr. logic L4+ M4
Suppr. Logic STOP/RUNswitch
L5+ M5
Outp. Supply Ground PE Screw for grounded configuration
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02
Digital outputs
24 V supply
9
Page 10
Product Information for the TB4-4/DC
Description
The TB4-4/DC terminal block belongs to the family of the ET 200B distributed I/O station modules. Fig. I: Basic construction: TB4-4/DC terminal block (spring-release terminal) 1 Polarization slide 2 Switch for setting the station number (this number is not accepted by the system until you actuate the STOP/RUN switch (STOP RUN)) 3 PROFIBUS-DP interface 4 Screw for connecting frame to PE 5 M5 screw for connecting PE 6 Terminal block for inputs/outputs and the load power supply 7 Slide for removing the terminal block from the standard mounting rail 8 Terminals for the logic supply 9 STOP/RUN switch for switching the power supply to the logic components in the electronics block on and off. The STOP/RUN switch also switches the ET 200B distributed I/O station on and off. 10 Fuse Fig. II: Dimension drawing: TB4-4/DC terminal block Fig. III: Terminal designations: TB4-4/DC terminal block Fig. IV: Block diagram: TB4-4/DC terminal block and ET 200B-16DO/2A
Characteristics
The TB4-4/DC terminal block (spring-release terminal, 4-tier) offers the same functionality as the TB2-4/DC terminal block (screw terminal, 4-tier). The only difference is that the TB4-4/DC is fitted with a 4-tier spring-release terminal. The ET 200B-16DO/2A, -32DI, -32DI 0.2ms, -32DO, -16DI/16DO, -24DI/8DO and -24DI/8DO 0.2ms electronics blocks can all be connected to the TB4-4/DC terminal block.
Installation and settings
You can find details of how to install and set the terminal blocks of the ET 200B in the ET 200B Distributed I/O Station manual.
Input/output connections
The assignment of the inputs and outputs on the terminal blocks of the TB4-4/DC depends on the type of electronics block mounted on them. The pin-out of all the plug-in electronics blocks for the TB2-4/DC is described in the ET 200B Distributed I/O Station manual. This pin-out is the same as for the TB4-4/DC.
10
Product Information on the ET 200B Distributed I/O Station EWA 4NEB 780 6731-02