Spec sheet · Siemens
Product Information for the ET 200B Distributed I/O System
Spec sheet10 pagesPDF 227 KB
Siemens product information sheet for the ET 200B distributed I/O system: manual corrections and the TB3-4/DC and TB4-4/DC terminal blocks.
What this file really is
The old site listed this file as a spec sheet for the Siemens ET 200B. Linked as a spec sheet, but it is a product information addendum with corrections to the ET 200B manual and notes on the TB3-4/DC and TB4-4/DC terminal blocks.
Filed under · 1 model
Filed under these models in the old catalog
Summary
What is in it
Siemens product information that updates the ET 200B Distributed I/O Device manual, edition 04. It adds notes on PROFIBUS-DP bus wiring, the DIA diagnostic LED for analog modules, resolution and output rules, revised measured value tables for the ET 200B-4AI analog module from release 3, normal identifier format support for non-Siemens DP masters, and describes the TB3-4/DC and TB4-4/DC spring-release terminal blocks and which electronics blocks fit them.
Its parts
- General Information on the ET 200B
- Product Information for the TB3-4/DC
- Product Information for the TB4-4/DC
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
This is a Siemens product information sheet that updates the ET 200B Distributed I/O Device manual, edition 04. It corrects details on analog module diagnostics, measured value tables and identifier formats, and describes the TB3-4/DC and TB4-4/DC spring-release terminal blocks. It helps a technician wire and configure ET 200B stations and match terminal blocks to electronics blocks.
- Document
- Update to the ET 200B Distributed I/O Device manual, edition 04 (6ES5 998-4ET.1) p. 1
- Bus
- PROFIBUS-DP p. 1
- TB3-4/DC terminal block
- 6ES7 193-0CA40-0XA0; spring-release, 4-tier; same function as the screw-terminal TB1-4/DC p. 5, 7
- TB3-4/DC fits
- ET 200B-16DI, -16DO, -8DI/8DO, -8DI/8DO HWA and -8RO electronics blocks p. 7
- TB4-4/DC terminal block
- 6ES7 193-0CB40-0XA0; spring-release, 4-tier; same function as the screw-terminal TB2-4/DC p. 8, 10
- TB4-4/DC fits
- ET 200B-16DO/2A, -32DI, -32DI 0.2ms, -32DO, -16DI/16DO, -24DI/8DO and -24DI/8DO 0.2ms p. 10
- Analog input module
- ET 200B-4AI, 6ES7 134-0HF01-0XB0 (4 to 20 mA range) p. 2
- Station number
- Set by a switch on the terminal block; taken over when the STOP/RUN switch is operated p. 7
- Type files
- SIxxxAD.200 and SIxxxTD.200: normal identifier format; SIxxxBD.200: special identifier format p. 3
- Other DP masters
- Analog modules from release 3 support the normal identifier format; master must handle diagnostic frames up to 29 bytes p. 3
- Device master file
- COM PROFIBUS V3.1 or later creates one for each analog ET 200B module p. 3
What this sheet walks you through
- What the PROFIBUS-DP port supply may power p. 1
- Reading the DIA diagnostic LED on analog modules p. 1
- Wiring unused analog outputs p. 1
- Digitized measured values of the ET 200B-4AI from release 3 p. 2
- Connecting analog modules to non-Siemens DP masters p. 3
- Changing the type file version on a running analog module p. 3
- Parts, dimensions and terminals of the TB3-4/DC p. 5, 6, 7
- Parts, dimensions and terminals of the TB4-4/DC p. 8, 9, 10
Good to know
- The type U compensation unit and its accessories are no longer supplied. p. 1
- An ET 200B-4AI up to release 2 may report a range underflow instead of a wire break. p. 2
- Unused analog output terminals must be shorted when current output is set. p. 1
- Slave diagnostics are not updated while the DP master is in CLEAR mode. p. 3
- The resolutions in table 8-25 do not apply to temperature values. p. 1
Questions this sheet answers
Which terminal block fits the ET 200B-16DI?
The spring-release TB3-4/DC, which works the same as the screw-terminal TB1-4/DC. p. 7
What is the order number of the ET 200B TB4-4/DC terminal block?
6ES7 193-0CB40-0XA0. p. 8
Can ET 200B analog modules work with a non-Siemens PROFIBUS master?
From release 3, yes, if the master sends UNCLEAR cyclically and handles diagnostic frames up to 29 bytes; otherwise use a device master file from COM PROFIBUS. p. 3
Why does my ET 200B-4AI show underflow instead of wire break?
Modules up to and including release 2 may report a measurement range underflow on a wire break. p. 2
When does a new ET 200B station number take effect?
Only after the STOP/RUN switch is operated from STOP to RUN. p. 7
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file