Manual · Siemens
SIMATIC ET 200B Distributed I/O Station Manual
Manual344 pagesPDF 2.8 MB
Manual for the Siemens SIMATIC ET 200B distributed I/O station on PROFIBUS-DP: installation, configuration, diagnostics and module data.
Covers · 1 model
The models it covers
Summary
What is in it
The user manual for the SIMATIC ET 200B distributed I/O station, made of a terminal block and an electronics block. It explains how to install, wire and start up the station, configure and parameterize it on PROFIBUS-DP, read its LEDs and slave diagnostics, and gives technical specifications for every digital and analog ET 200B electronics block and terminal block, with type files, GSD files, telegram structures and order numbers in the appendices.
Its parts
- System Overview
- Technical Description
- Mechanical and Electrical Installation
- Configuration and Parameterization
- Status and Error Diagnostics
- General Technical Specifications
- Digital Modules
- Analog Modules
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is the Siemens SIMATIC ET 200B Distributed I/O Station manual, edition 04. It covers the ET 200B block I/O slave for PROFIBUS-DP with its digital and analog electronics blocks and terminal blocks. It explains installation, wiring, configuration and LED diagnostics, and lists technical data and order numbers.
- Type
- PROFIBUS-DP slave made of a terminal block and a plug-on electronics block; IP 20 p. 19
- Module range
- 24 V DC digital, 120/230 V AC digital and analog modules p. 19
- Supply voltage
- 24 V DC; a non-Siemens supply must stay within 20 to 30 V including ripple p. 43
- Operating temperature
- 0 to 60 °C preferred (horizontal on a vertical wall), 0 to 40 °C other positions; storage –40 to 70 °C p. 83
- Bus interface
- 9-pin PROFIBUS-DP: pin 3 RxD/TxD-P (data line B), pin 8 RxD/TxD-N (data line A), pin 4 RTS, pin 5 M5V2, pin 6 P5V2 p. 52
- Station numbers
- 00 to 99 by screwdriver; 3 to 99 with IM 308-B, 1 to 99 with IM 308-C or S7/M7 DP master p. 21
- Masters
- IM 308-B (COM ET 200 V4.x), IM 308-C (COM ET 200 Windows) or S7/M7 DP master (STEP 7) p. 20
- Digital terminal blocks
- TB1/DC, TB1-4/DC, TB3/DC (16 channels); TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC (32 channels); TB6/AC (16 channels) p. 89
- Analog blocks
- ET 200B-4/8AI 6ES7 134-0KH01-0XB0, ET 200B-4AI 6ES7 134-0HF01-0XB0, ET 200B-4AO 6ES7 135-0HF01-0XB0 p. 326
- Analog terminal block
- TB8, 6ES7 193-0CD40-0XA0, used for all analog electronics blocks p. 182, 327
- Bus connectors
- Max. 12 Mbaud: 6ES7 972-0BA10-0XA0 without, 6ES7 972-0BB10-0XA0 with programmer socket p. 52
- LEDs
- RUN, BF (bus fault), DIA (group diagnostics), L1+ to L4+ load voltage, and input/output status p. 22
- Mounting
- Standard sectional rail or directly on a wall; vertical or horizontal p. 19
- Bus isolation
- PROFIBUS-DP bus galvanically isolated from the internal electronics p. 22
What this manual walks you through
- Wiring a grounded configuration p. 43
- Wiring an ungrounded configuration p. 46
- Connecting the PROFIBUS-DP bus connector p. 52, 53
- Fixing a station the bus does not accept after power cycling or a baud rate change p. 62
- Reading the LEDs on digital modules p. 63
- Reading the LEDs on analog modules, with remedies p. 64
- Environmental, EMC and insulation specifications p. 83, 84
- Order numbers of electronics blocks, terminal blocks and labeling strips p. 326, 327
- PROFIBUS-DP accessories and the manuals needed for each master p. 328, 329
Good to know
- Non-stabilized load power supplies need a back-up capacitor. p. 43
- Equipotential bonding and ground connections need a cross-section of 4 mm2 to 10 mm2. p. 43
- On digital modules, a wrong configuration cannot be corrected while also changing the baud rate. p. 62
- Grounded sensors, actuators or machine parts can cancel an ungrounded configuration. p. 46
- The 120/230 V AC digital modules have no STOP/RUN switch. p. 63
Questions this manual answers
What power supply does the Siemens ET 200B need?
24 V DC. A load supply other than the Siemens 6EV1 series must stay within 20 to 30 V including ripple. p. 43
What does a red BF LED mean on an ET 200B?
The station was not addressed within the response monitoring time, for example after losing its master, or it was not parameterized on startup. p. 63
Which station numbers can an ET 200B use?
3 to 99 with an IM 308-B master interface; 1 to 99 with an IM 308-C or an S7/M7 DP master. p. 21
My ET 200B is not accepted on the PROFIBUS-DP bus after power cycling. What do I do?
Set the STOP/RUN switch to STOP and then back to RUN. p. 62
What is the order number of the ET 200B-16DI?
6ES7 131-0BH00-0XB0, a block with 16 inputs at DC 24 V (3 ms). p. 326
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 41 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 41-4
- Contents, pages 5 to 105-10
- Contents, pages 11 to 1611-16
- 1 System Overview17-22
- 2 Technical Description23-26
- 3 Mechanical and Electrical Installation, pages 27 to 3627-36
- 3 Mechanical and Electrical Installation, pages 37 to 4637-46
- 3 Mechanical and Electrical Installation, pages 47 to 5447-54
- 4 Configuration and Parameterization55-60
- 5 Status and Error Diagnostics, pages 61 to 6861-68
- 5 Status and Error Diagnostics, pages 69 to 7669-76
- 5 Status and Error Diagnostics, pages 77 to 8277-82
- 6 General Technical Specifications83-86
- 7 Digital Modules, pages 87 to 9687-96
- 7 Digital Modules, pages 97 to 10697-106
- 7 Digital Modules, pages 107 to 116107-116
- 7 Digital Modules, pages 117 to 126117-126
- 7 Digital Modules, pages 127 to 136127-136
- 7 Digital Modules, pages 137 to 146137-146
- 7 Digital Modules, pages 147 to 156147-156
- 7 Digital Modules, pages 157 to 166157-166
- 7 Digital Modules, pages 167 to 176167-176
- 7 Digital Modules, pages 177 to 180177-180
- 8 Analog Modules, pages 181 to 190181-190
- 8 Analog Modules, pages 191 to 200191-200
- 8 Analog Modules, pages 201 to 210201-210
- 8 Analog Modules, pages 211 to 220211-220
- 8 Analog Modules, pages 221 to 230221-230
- 8 Analog Modules, pages 231 to 240231-240
- 8 Analog Modules, pages 241 to 250241-250
- 8 Analog Modules, pages 251 to 260251-260
- 8 Analog Modules, pages 261 to 270261-270
- 8 Analog Modules, pages 271 to 272271-272
- A Type Files and GSD Files273-282
- B Configuration Telegram283-286
- C Parameterization Telegram287-300
- D Configuring with COM ET 200 V4.x301-314
- E Analog Modules and Old Type Files315-324
- F Order Numbers325-330
- Glossary331-338
- Index339-344