Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of SIMATIC ET 200B Distributed I/O Station Manual

Manual · Siemens

SIMATIC ET 200B Distributed I/O Station Manual

Manual344 pagesPDF 2.8 MB

Manual for the Siemens SIMATIC ET 200B distributed I/O station on PROFIBUS-DP: installation, configuration, diagnostics and module data.

Download the PDF2.8 MB

Covers · 1 model

The models it covers

Summary

What is in it

The user manual for the SIMATIC ET 200B distributed I/O station, made of a terminal block and an electronics block. It explains how to install, wire and start up the station, configure and parameterize it on PROFIBUS-DP, read its LEDs and slave diagnostics, and gives technical specifications for every digital and analog ET 200B electronics block and terminal block, with type files, GSD files, telegram structures and order numbers in the appendices.

Its parts

  1. System Overview
  2. Technical Description
  3. Mechanical and Electrical Installation
  4. Configuration and Parameterization
  5. Status and Error Diagnostics
  6. General Technical Specifications
  7. Digital Modules
  8. Analog Modules

From the manual

Key facts from this manual

Each line names its page in the PDF.

This is the Siemens SIMATIC ET 200B Distributed I/O Station manual, edition 04. It covers the ET 200B block I/O slave for PROFIBUS-DP with its digital and analog electronics blocks and terminal blocks. It explains installation, wiring, configuration and LED diagnostics, and lists technical data and order numbers.

Read for this summary: pages 1, 17 to 22, 43, 46, 52 to 53, 62 to 64, 83 to 90, 182 and 326 to 329 of 344.

Type
PROFIBUS-DP slave made of a terminal block and a plug-on electronics block; IP 20 p. 19
Module range
24 V DC digital, 120/230 V AC digital and analog modules p. 19
Supply voltage
24 V DC; a non-Siemens supply must stay within 20 to 30 V including ripple p. 43
Operating temperature
0 to 60 °C preferred (horizontal on a vertical wall), 0 to 40 °C other positions; storage –40 to 70 °C p. 83
Bus interface
9-pin PROFIBUS-DP: pin 3 RxD/TxD-P (data line B), pin 8 RxD/TxD-N (data line A), pin 4 RTS, pin 5 M5V2, pin 6 P5V2 p. 52
Station numbers
00 to 99 by screwdriver; 3 to 99 with IM 308-B, 1 to 99 with IM 308-C or S7/M7 DP master p. 21
Masters
IM 308-B (COM ET 200 V4.x), IM 308-C (COM ET 200 Windows) or S7/M7 DP master (STEP 7) p. 20
Digital terminal blocks
TB1/DC, TB1-4/DC, TB3/DC (16 channels); TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC (32 channels); TB6/AC (16 channels) p. 89
Analog blocks
ET 200B-4/8AI 6ES7 134-0KH01-0XB0, ET 200B-4AI 6ES7 134-0HF01-0XB0, ET 200B-4AO 6ES7 135-0HF01-0XB0 p. 326
Analog terminal block
TB8, 6ES7 193-0CD40-0XA0, used for all analog electronics blocks p. 182, 327
Bus connectors
Max. 12 Mbaud: 6ES7 972-0BA10-0XA0 without, 6ES7 972-0BB10-0XA0 with programmer socket p. 52
LEDs
RUN, BF (bus fault), DIA (group diagnostics), L1+ to L4+ load voltage, and input/output status p. 22
Mounting
Standard sectional rail or directly on a wall; vertical or horizontal p. 19
Bus isolation
PROFIBUS-DP bus galvanically isolated from the internal electronics p. 22

What this manual walks you through

  • Wiring a grounded configuration p. 43
  • Wiring an ungrounded configuration p. 46
  • Connecting the PROFIBUS-DP bus connector p. 52, 53
  • Fixing a station the bus does not accept after power cycling or a baud rate change p. 62
  • Reading the LEDs on digital modules p. 63
  • Reading the LEDs on analog modules, with remedies p. 64
  • Environmental, EMC and insulation specifications p. 83, 84
  • Order numbers of electronics blocks, terminal blocks and labeling strips p. 326, 327
  • PROFIBUS-DP accessories and the manuals needed for each master p. 328, 329

Good to know

  • Non-stabilized load power supplies need a back-up capacitor. p. 43
  • Equipotential bonding and ground connections need a cross-section of 4 mm2 to 10 mm2. p. 43
  • On digital modules, a wrong configuration cannot be corrected while also changing the baud rate. p. 62
  • Grounded sensors, actuators or machine parts can cancel an ungrounded configuration. p. 46
  • The 120/230 V AC digital modules have no STOP/RUN switch. p. 63

Questions this manual answers

What power supply does the Siemens ET 200B need?

24 V DC. A load supply other than the Siemens 6EV1 series must stay within 20 to 30 V including ripple. p. 43

What does a red BF LED mean on an ET 200B?

The station was not addressed within the response monitoring time, for example after losing its master, or it was not parameterized on startup. p. 63

Which station numbers can an ET 200B use?

3 to 99 with an IM 308-B master interface; 1 to 99 with an IM 308-C or an S7/M7 DP master. p. 21

My ET 200B is not accepted on the PROFIBUS-DP bus after power cycling. What do I do?

Set the STOP/RUN switch to STOP and then back to RUN. p. 62

What is the order number of the ET 200B-16DI?

6ES7 131-0BH00-0XB0, a block with 16 inputs at DC 24 V (3 ms). p. 326

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Title1
  2. Preface3
    1. Figures8
    2. Tables12
  3. 1 System Overview17
    1. 1.1 What is the ET 200 Distributed I/O System?18
    2. 1.2 What is the ET 200B?19
  4. 2 Technical Description23
    1. 2.1 Design of the Terminal Block24
    2. 2.2 Design of the Electronics Block26
  5. 3 Mechanical and Electrical Installation27
    1. 3.1 Installing and Setting the Terminal Block28
    2. 3.2 Installing the Electronics Block38
    3. 3.3 DismantlingtheTerminalBlockandtheElectronicsBlock40
    4. 3.4 Electrical Installation42
    5. 3.5 Wiring the Terminal Block48
    6. 3.6 Wiring the Bus Interface52
  6. 4 Configuration and Parameterization55
    1. 4.1 Configuration Options56
    2. 4.2 Requirements for Configuration57
    3. 4.3 Where to Find the Requisite Information?59
  7. 5 Status and Error Diagnostics61
    1. 5.1 Possible Response on Startup62
    2. 5.2 Status and Error Indication by LEDs63
    3. 5.3 Slave Diagnostics65
  8. 6 General Technical Specifications83
  9. 7 Digital Modules87
    1. 7.1 Digital Modules88
    2. 7.2 Terminal Blocks90
    3. 7.3 Electronics Blocks100
  10. 8 Analog Modules181
    1. 8.1 Analog Modules182
    2. 8.2 Terminal Block TB8 (6ES7 193-0CD40-0XA0)183
    3. 8.3 Terminal Block TB8 and Bus Connector184
    4. 8.4 Electronics Block ET 200B-4/8AI (6ES7 134-0KH01-0XB0)185
    5. 8.5 Electronics Block ET 200B-4AI (6ES7 134-0HF01-0XB0)231
    6. 8.6 Electronics Block ET 200B-4AO (6ES7 135-0HF01-0XB0)256
  11. A Type Files and GSD Files273
    1. A.1 Type Files of the ET 200B Modules274
23 more lines, from page 276 on
  1. A.2 GSD Files of the ET 200B Modules276
  2. B Configuration Telegram283
  3. C Parameterization Telegram287
    1. C.1 Structure of the Parameterization Telegram288
    2. C.2 Standard Part of the Parameterization Telegram289
    3. C.3 Parameters for Status290
    4. C.4 Parameters for Analog Input Modules291
    5. C.5 Parameters for Analog Output Module296
  4. D Configuring with COM ET 200 V4.x301
    1. D.1 Status and Error Indication by LEDs302
    2. D.2 Slave Diagnostics303
    3. D.3 Configuration Options311
    4. D.4 Setting the Operating Mode with COM ET 200 V4.x312
  5. E Analog Modules and Old Type Files315
    1. E.1 Status and Error Indication by LEDs316
    2. E.2 Structure of Device-Related Diagnostics (Analog ET 200B)317
    3. E.3 Configuration Options321
    4. E.4 Parameters for Analog Modules322
  6. F Order Numbers325
    1. F.1 Order Numbers for ET 200B Components326
    2. F.2 Order Numbers for PROFIBUS-DP Accessories328
  7. Glossary331
  8. Index339

From the PDF’s own bookmarks.

The whole text · 41 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 41-4
  2. Contents, pages 5 to 105-10
  3. Contents, pages 11 to 1611-16
  4. 1 System Overview17-22
  5. 2 Technical Description23-26
  6. 3 Mechanical and Electrical Installation, pages 27 to 3627-36
  7. 3 Mechanical and Electrical Installation, pages 37 to 4637-46
  8. 3 Mechanical and Electrical Installation, pages 47 to 5447-54
  9. 4 Configuration and Parameterization55-60
  10. 5 Status and Error Diagnostics, pages 61 to 6861-68
  11. 5 Status and Error Diagnostics, pages 69 to 7669-76
  12. 5 Status and Error Diagnostics, pages 77 to 8277-82
  13. 6 General Technical Specifications83-86
  14. 7 Digital Modules, pages 87 to 9687-96
  15. 7 Digital Modules, pages 97 to 10697-106
  16. 7 Digital Modules, pages 107 to 116107-116
  17. 7 Digital Modules, pages 117 to 126117-126
  18. 7 Digital Modules, pages 127 to 136127-136
  19. 7 Digital Modules, pages 137 to 146137-146
  20. 7 Digital Modules, pages 147 to 156147-156
  21. 7 Digital Modules, pages 157 to 166157-166
  22. 7 Digital Modules, pages 167 to 176167-176
  23. 7 Digital Modules, pages 177 to 180177-180
  24. 8 Analog Modules, pages 181 to 190181-190
  25. 8 Analog Modules, pages 191 to 200191-200
  26. 8 Analog Modules, pages 201 to 210201-210
  27. 8 Analog Modules, pages 211 to 220211-220
  28. 8 Analog Modules, pages 221 to 230221-230
  29. 8 Analog Modules, pages 231 to 240231-240
  30. 8 Analog Modules, pages 241 to 250241-250
  31. 8 Analog Modules, pages 251 to 260251-260
  32. 8 Analog Modules, pages 261 to 270261-270
  33. 8 Analog Modules, pages 271 to 272271-272
  34. A Type Files and GSD Files273-282
  35. B Configuration Telegram283-286
  36. C Parameterization Telegram287-300
  37. D Configuring with COM ET 200 V4.x301-314
  38. E Analog Modules and Old Type Files315-324
  39. F Order Numbers325-330
  40. Glossary331-338
  41. Index339-344

The file

Revision and size

RevisionEWA 4NEB 812 6089-02c, Edition 04, 1995
PublisherSiemens AG
Pages344
PDF2.8 MB
TextText from the PDF itself.

The first pages · 3 of 344

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 344
Page 2
Page 2of 344
Page 3
Page 3of 344

More documents · 1