Page 23
2
Technical Description
In this Chapter
This chapter contains information on: In Section
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c you will find on Page
2.1
Design of the Terminal Block
2-2
2.2
Design of the Electronics Block
2-4
2-1
Page 24
Technical Description
2.1
Design of the Terminal Block
Design Principle of the Digital TBs
All digital terminal blocks are built on the same design principle explained below using the TB1/DC terminal block as a typical example:
2
1
2 10 3 9
8 Figure 2-1
7
6
5
4
The TB1/DC
1 Coding slide switch 2 Fuse 3 STOP/RUN switch (not TB6/AC). The power supply for logic circuits in the electronics block can be switched on or off with the STOP/RUN switch. It can also be used to switch the ET 200B distributed I/O station on and off. 4 Terminals for power supplies 5 Terminals for inputs/outputs 6 Slide for removing the terminal block from the standard sectional rail 7 M4 screw (connects chassis to PE) 8 M5 screw for connecting PE 9 PROFIBUS-DP interface 10 Switch for setting the station number (the station number is valid only after operation of the STOP/RUN switch (STOP –> RUN)).
2-2
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 25
Technical Description
Design Principle of the TB8 Analog Block
On the front of the TB8 analog terminal block, there are an additional 5 coding switches:
1
2 2 10 3 9
8 Figure 2-2
7
6
5
4
The TB8
1 Coding slide switch 2 Fuse 3 STOP/RUN switch. The power supply for logic circuits in the electronics block can be switched on or off with the STOP/RUN switch. It can also be used to switch the ET 200B distributed I/O station on and off. 4 Terminals for power supplies 5 Terminals for inputs/outputs 6 Slide for removing the terminal block from the standard sectional rail 7 Coding connectors. You use the coding connectors to set the wiring of the TB8 for analog value processing. 8 M5 screw for connecting PE 9 PROFIBUS-DP interface 10 Switch for setting the station number (the station number is valid only after operation of the STOP/RUN switch (STOP –> RUN)).
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
2-3
Page 26
Technical Description
2.2
Design of the Electronics Block
Design Principle
All types of electronics block are built on the same design principle which is explained below using the ET 200B-16DI electronics block as a typical example:
2 6 1 5
4 Figure 2-3
3
2
ET 200B-16DI Electronics Block
1 Ventilation slots 2 Screws for mounting the electronics block on the terminal block 3 Printed schematic diagram 4 Indication of the coding slide switch setting on the top of the terminal block 5 Labeling strip; for indicating the status of the inputs or outputs in the case of digital electronics blocks with LEDs 6 LEDs for Voltage supply to the logic circuits (RUN) Bus fault (BF) Group diagnostics; short-circuit, wire break or load voltage failure (DIA, only for electronics blocks which can be diagnosed) Load voltage monitor (L1+, L2+, L3+, L4+, depending on the electronics block: see Section 5.2)
Coding
The electronics blocks are coded by the manufacturer. Some types of electronics blocks have a recess at the bottom. This recess ensures that the terminal block is assigned safely to the correct electronics block.
2-4