The text of a manual · part 6 of 41
SIMATIC ET 200B Distributed I/O Station Manual: 3 Mechanical and Electrical Installation, pages 27 to 36
Pages 27 to 36 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 27
Mechanical and Electrical Installation
In the Chapter
This chapter contains information on: In Section
Technical Data
3 you will find on Page
3.1
Installing and Setting the Terminal Block
3-2
3.2
Installing the Electronics Block
3-12
3.3
Dismantling the Terminal Block and Electronics Block
3-14
3.4
Electrical Installation
3-16
3.5
Wiring the Terminal Block
3-22
3.6
Wiring the Bus Interface
3-26
You will find a detailed description of the technical data of the ET 200B modules in Sections 6, 7 and 8.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-1
Page 28
Mechanical and Electrical Installation
3.1
Installing and Setting the Terminal Block
Two Methods
You can install the terminal block either on a standard sectional rail (35
15 mm or 35
7.5 mm to
DIN EN 50022) or on smooth surfaces, i.e. direct wall mounting (for dimensions of the
3 mounting holes see Dimensional Drawings in Sections 7 and 8).
Small Electronics Block, Digital
Figure 3-1 shows the clearances required for installation of the 16DI, 16DO, 8DI/8DO, 8DI/8DO HWA, 8RO and 4/8AI, 4AI, 4AO electronics blocks (without shield connecting element):
Handling and heat dissipation For swiveling/disengaging the electronics block
Figure 3-1
3-2
Clearances Required for Installation of the 16DI, 16DO, 8DI/8DO, 8DI/8DO HWA, 8RO and 4/8AI, 4AI, 4AO Electronics Blocks (without Shield Connecting Element)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 29
Mechanical and Electrical Installation
Large Electronics Block
Figure 3-2 shows the clearances required for installation of the 16DI-AC, 16DO-AC, 32DI, 16DO/2A, 32DO, 16DI/16DO, 24DI/8DO, 16RO-AC and 8DI/8RO-AC electronics blocks:
Handling and heat dissipation For swiveling/disengaging the electronics block
3
Figure 3-2
Clearances Required for Installation of the 16DI-AC, 16DO-AC, 32DI, 16DO/2A, 32DO, 16DI/16DO, 24DI/8DO, 16RO-AC and 8DI/8RO-AC Electronics Blocks
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-3
Page 30
Mechanical and Electrical Installation
Small Electronics Block, Analog
Figure 3-3 shows the clearances required for installation of the 4/8AI, 4AI, 4AO electronics blocks (with shield connecting element):
Handling and heat dissipation For swiveling/disengaging the electronics block
3
Figure 3-3
3-4
Clearances Required for Installation of the 4/8AI, 4AI and 4AO Electronics Blocks (with Shield Connecting Element)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 31
Mechanical and Electrical Installation
Shield Connecting Element for TB8
In the case of analog value processing, we recommend that the cable shielding of the signal lines be connected directly at terminal block TB8. For this application, you can hang the TB8 onto a shield connecting element after first mounting the shield connecting element on a standard sectional rail (35 15 or 35 7.5 mm to DIN EN 50022) or a smooth surface. To secure the shield braiding, install metal terminal elements on the shield connecting element. You can order the shield connecting element and the terminal elements under the following numbers:
3
Shield connecting element → Order No. 6ES7 193-0CD40-7XA0 Terminal elements (set of two): – Single version → Order No. 6ES7 390-5BA00-0AA0 (one shield cable per terminal element with a diameter of 3 to 8 mm to be clamped) – Double version → Order No. 6ES7 390-5AB00-0AA0 (two shield cables per terminal element with a diameter of 2 to 6 mm to be clamped) Note If you mount the TB8 with shield connecting element on a standard sectional rail, you must install the ET 200B horizontally.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-5
Page 32
Mechanical and Electrical Installation
Mounting on a Standard Sectional Rail
To mount the terminal block on a standard sectional rail... 1. Hang the terminal block on the standard sectional rail (1) and 2. Swing it back until the slide on the module snaps into place (2). Note: The meanings of the coding switch settings are explained in Table 3-1.
3
Figure 3-4
3-6
Hanging the Terminal Block on the Standard Sectional Rail and Setting the Coding Slide Switch
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 33
Mechanical and Electrical Installation
Mounting the Shield Connecting Element on a Standard Sectional Rail
To mount the shield connecting element on a standard sectional rail... 1. Hang the shield connecting element on the standard sectional rail from below (1) and swing it back (2). 2. Secure the shield connecting element on the standard sectional rail by tightening the screws (3).
3
2 3 3 1
Figure 3-5
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Mounting the Shield Connecting Element on the Standard Sectional Rail
3-7
Page 34
Mechanical and Electrical Installation
Mounting the Terminal Block on the Shield Connecting Element
To mount the terminal block on the shield connecting element ... 1. Engage the terminal block in the brackets of the terminal connecting element (1). 2. Tighten the screws to secure the terminal block to the shield connecting element (2).
3 1 2
2 2 Figure 3-6
3-8
Mounting the Terminal Block on the Shield Connecting Element
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 35
Mechanical and Electrical Installation
Setting the Coding Slide Switch
In order to prevent the wrong electronics block being plugged in, the terminal block has a coding slide switch (see Section 2.1, Figure 2-1, 1). The coding switch can be engaged in 6 settings. Each setting is assigned to a module class of the ET 200B distributed I/O station: Table 3-1
Setting the Station Number
Assignment of the Electronics Blocks to the Coding Slide Switch
Setting
Module Class
1
24 V digital modules
2
24 V special modules
3
Analog modules
4
Reserved
5
Reserved
6
230 V digital modules
3
Any station number from 00 to 99 can be set with the aid of a tool such as a screwdriver (see Section 2.1, Figure 2-1, 10):
Station numbers 3 to 99 are permissible when operating with the IM308-B master interface.
Station numbers 1 to 99 are permissible when operating with the IM 308-C master interface or with the S7/M7 DP master. The station number becomes valid only after a STOP/RUN transition of the ET 200B slave station.
Setting the Coding Plug
The coding plus of the TB8 provide the means of setting the defaults for analog value measurement and analog value output for each channel in the case of analog modules (see Section 2-1, Figure 2-2, 7). The coding plugs enable you to set the input or output circuitry of the TB8 to suit the measured value sensor or load connected and the desired measuring or output method. The possible settings for the coding plugs are: ”A”, ”B”, ”C” and ”D”. The relationships between the various settings of the coding plugs and the measurement/output method and the measured value sensors and loads are detailed in the sections dealing with the individual electronics blocks (see Sections 8.4 through 8.6). The procedure for changing the settings of the coding plugs is described below.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-9
Page 36
Mechanical and Electrical Installation
Changing the Coding Plug Setting
The procedure for changing the setting of a coding plug is as follows: 1. Pull the coding plug above the channel group from its socket in the TB8 (1). Tip: It is easiest to reset the coding plugs before installing the electronics block. 2. Turn the coding plug to the appropriate position (2) and reinsert the coding plug in its socket (3).
3
Correct setting: The pointer ”∆” beside the letter ”A”, ”B”, ”C” or ”D” must point toward the electronics block.
3 1
Figure 3-7
3-10
2
Changing the Setting of the Coding Plug
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c