SIMATIC ET 200B Distributed I/O Station Manual: 3 Mechanical and Electrical Installation, pages 37 to 46

Pages 37 to 46 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 37

Mechanical and Electrical Installation

Terminal Block Fuses

The fuse (F1) in the terminal block protects against:

short-circuit in the sensor supply reversed polarity of the voltage supply to the internal logic voltage spikes in the voltage supply to the internal logic If the fuse trips the module’s internal logic is deenergized.

Changing the Fuse

Proceed as follows when changing the fuse:

3

1. Switch the STOP/RUN switch to the “STOP” position. 2. Pull the electronics block off the terminal block. 3. Pry the fuse out of its base using a screwdriver. 4. Insert the new fuse. 5. Reinstall the electronics block on the terminal block. 6. Switch the RUN/STOP switch to “RUN”. Note The TB6/AC terminal block has no STOP/RUN switch. Make sure that the external power supply is switched off before removing the electronics block and changing the fuse.

Approved Fuses

Install only the fuses listed in Table 3-2. The fuses can be ordered in packs of ten. Table 3-2 Terminal Block

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Approved Fuses for Terminal Blocks Fuse

Order No. (pack of 10)

TB6/AC

Miniature fuse TR5-T 1.0; 250 V AC

6ES7 193-0DC00-0XA0

TB1/DC

Miniature fuse TR5-T 1.6; 250 V

6ES7 193-0DA00-0XA0

TB1-4/DC

Miniature fuse TR5-T 1.6; 250 V

TB3/DC

Miniature fuse TR5-T 1.6; 250 V

TB8-analog

Miniature fuse TR5-T 1.6; 250 V

TB2/DC

Miniature fuse TR5-T 2.5; 250 V

TB2-4/DC

Miniature fuse TR5-T 2.5; 250 V

TB4/DC

Miniature fuse TR5-T 2.5; 250 V

TB4M/DC

Miniature fuse TR5-T 2.5; 250 V

6ES7 193-0DB00-0XA0

3-11

Page 38

Mechanical and Electrical Installation

3.2

Installing the Electronics Block

Engaging the Electronics Block on the Terminal Block

!

3

After coding the terminal block via the coding slide switch, you can engage the electronics block on the terminal block:

Warning Avoid electrical destruction of the electronics block. Always set the STOP/RUN switch of the terminal block to the “STOP” position before engaging the electronics block on the terminal block! The TB6/DC terminal block has no STOP/RUN switch. Always switch off the external power supply before attempting to engage an electronics block (120/230 V AC) onto the TB6/DC.

1. Engage the electronics block on the terminal block (1). 2. Press the electronics block onto the terminal block (2). 3. Secure the electronics block by tightening the screws (3).

Figure 3-8

3-12

Engaging the Electronics Block on the Terminal Block

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 39

Mechanical and Electrical Installation

Labeling the Electronics Block

A labeling strip is inserted in the electronics block. Individual DIN A4 sheets consisting of several labeling strips can be ordered separately. Please refer to Appendix F for order numbers. Versions

For electronics blocks with 16DI, 16DO, 8DI/8DO, 8DI/8DO HWA, 8RO, 4/8AI, 4AI, 4AO: 10 labeling strips on one DIN A4 sheet

For electronics blocks with 16DI-AC, 16DO-AC, 32DI, 16DO/2A, 32DO, 16DI/16DO, 24DI/8DO, 16RO-AC, 8DI/8RO-AC: 7 large labeling strips and 9 small labeling strips on one DIN A4 sheet.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-13

3

Page 40

Mechanical and Electrical Installation

3.3

DismantlingtheTerminalBlockandtheElectronicsBlock

Dismantling (from the Standard Sectional Rail)

!

3

Proceed according to the following steps: 1. Remove the electronics block in the reverse sequence to that described in Figure 3-8. Warning Avoid electrical destruction of the electronics block. Always set the STOP/RUN switch of the terminal block to the “STOP” position before disengaging the electronics block from the terminal block or installing a replacement electronics block! The TB6/DC terminal block has no STOP/RUN switch. Always switch off the external power supply before attempting to disengage an electronics block (120/230 V AC) from the TB6/DC or installing a replacement electronics block.

2. Press the slide (1) on the bottom of the terminal block down using a screwdriver and 3. Swing the terminal block out of the standard sectional rail (2).

1 2 Figure 3-9

3-14

Dismantling the ET 200B

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 41

Mechanical and Electrical Installation

Dismantling (from the Shield Connecting Element)

!

Proceed according to the following steps: 1. Remove the electronics block in the reverse sequence to that described in Figure 3-8. Warning Avoid electrical destruction of the electronics block. Always set the STOP/RUN switch of the terminal block to the “STOP” position before disengaging the electronics block from the terminal block or installing a replacement electronics block! The TB6/DC terminal block has no STOP/RUN switch. Always switch off the external power supply before attempting to disengage an electronics block (120/230 V AC) from the TB6/DC or installing a replacement electronics block.

2. Remove the terminal block and the shield connecting element in the reverse sequence to that described in Figures 3-5 and 3-6.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-15

3

Page 42

Mechanical and Electrical Installation

3.4

Electrical Installation

Introduction

The ET 200B distributed I/O station allows both grounded and ungrounded configurations.

Next Sections

The following two sections explain the configuration rules and give circuit examples for

3

In Section you will find on Page

3.4.1

Grounded Configuration

3-17

3.4.2

Ungrounded Configuration

3-20

The numbers in the text cross-reference the components shown in the figures.

3-16

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 43

Mechanical and Electrical Installation

3.4.1

Grounded Configuration

Definition

In a grounded configuration, the reference potential of the ET 200B logic circuits and the protective ground conductor (PE) are galvanically interconnected.

Rules

You must note the following points for a grounded configuration:

You must provide a main switch (1) in accordance with DIN VDE 0100

3 for the ET 200B modules, the signal sensors and the actuators.

If the spur lines are a maximum of 3 m long and are ground-fault-resistant and short-circuit-proof, the supply connection for the ET 200B and the load circuit requires no additional fuse (2).

Use a Siemens load power supply unit (3) in the 6EV1 series (Catalog ET 1) for supplying the 24 V DC to the ET 200B. If you connect another load power supply unit (24 V DC), please note that the voltage must be in the range 20 to 30 V (including ripple). The load power supply unit must generate a functional low voltage with safe electrical isolation in accordance with DIN VDE 0106. In the case of non-stabilized load power supply units, you require a back-up capacitor (rating 200 per 1 A load current).

Provide a detachable connection to the protective ground conductor (4) in the secondary circuit of the load power supply unit (M terminal).

A fuse (5) is required for fusing the supply voltage. For both grounded and ungrounded configurations, the PE terminal of the ET 200B must have a low-impedance connection to the protective ground conductor or the cabinet ground (machine parts) (6).

Use a minimum cross-section of 4 mm2 and a maximum of 10 mm2 for equipotential bonding and ground connections.

All machine parts must be grounded. The PROFIBUS-DP interface of terminal blocks release 2 and later is ungrounded.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-17

Page 44

Mechanical and Electrical Installation

Connecting the Reference Potential of the Logic Circuits to PE

For a grounded configuration, you must also do the following at the digital terminal blocks: 1. Connect the PE terminal to the lower screw. 2. Tighten the upper screw. The upper screw connects the ground potential to PE.

3 PE

Figure 3-10 Both Screws Tightened in a Grounded Configuration

Electrical Configuration

The following figure shows the grounded configuration for 24 V DC digital modules of the ET 200B:

L1 L2 L3 N PE

(1)

(2)

ET 200B (3) M

L+ M

L+ (5)

(4)

(6) I/O

M

L+

Sensor/ actuator

Figure 3-11 Grounded Configuration for 24 V DC Digital Modules of the ET 200B

3-18

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 45

Mechanical and Electrical Installation

Electrical Configuration

The following figure shows the grounded configuration for 120/230 V AC digital modules of the ET 200B:

L1 L2 L3 N PE

(1)

3

(2)

(8)

ET 200B L1 N

(5)

(6) I/O

230 V AC

Sensor/ actuator

Figure 3-12 Grounded Configuration for 120/230 V AC Digital Modules of the ET 200B

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-19

Page 46

Mechanical and Electrical Installation

3.4.2

Ungrounded Configuration

Definition

In an ungrounded configuration, there is no galvanic connection between the reference potential of the ET 200B logic circuits and the protective ground conductor (PE).

Rules

You must note the following points for an ungrounded configuration:

You must provide a main switch (1) in accordance with DIN VDE 0100

3 for the ET 200B modules, the signal sensors and the actuators.

If the spur lines are a maximum of 3 m long and are ground-fault-resistant and short-circuit-proof, the supply connection for the ET 200B and the load circuit requires no additional fuse (2).

Use a Siemens load power supply unit (3) in the 6EV1 series (Catalog ET 1) for supplying the 24 V DC to the ET 200B. If you connect another load power supply unit (24 V DC), please note that the voltage must be in the range 20 to 30 V (including ripple). The load power supply unit must generate a functional low voltage with safe electrical isolation in accordance with DIN VDE 0106. In the case of non-stabilized load power supply units, you require a back-up capacitor (rating 200 per 1 A load current).

A fuse (5) is required for fusing the supply voltage. For both grounded and ungrounded configurations, the PE terminal of the ET 200B must have a low-impedance connection to the protective ground conductor or the cabinet ground (machine parts) (core cross-section of PE min. 4 mm2 and max. 10 mm2) (6).

Provide an insulation monitoring circuit against ground with voltage limitation in accordance with the regulations applying to the system, for example DIN VDE 0160 (7).

The PROFIBUS-DP interface of terminal blocks release 2 and later is ungrounded.

!

Warning The ungrounded configuration can be canceled out by grounded machine parts and grounded electrical equipment. Example: A grounded sensor or a grounded actuator connects the PE to the reference potential (M terminal) of the controller.

3-20

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c