Page 47
Mechanical and Electrical Installation
Disconnecting the Reference Potential of the Logic Circuits from PE
For an ungrounded configuration, you must also do the following at the digital terminal blocks: 1. Connect the PE terminal to the lower screw. 2. Remove the upper screw for an ungrounded configuration.
3
Removed
PE
Figure 3-13 Upper Screw Removed in an Ungrounded Configuration
Electrical Configuration
Figure 3-14 shows the ungrounded configuration for 24 V DC digital modules of the ET 200B:
L1 L2 L3 N PE
(1)
(2) (7) > VCM
ET 200B (3) M
L+ M
L+ (5)
(6) I/O
M
L+
Sensor/ actuator
Figure 3-14 Ungrounded Configuration for 24 V DC Digital Modules of the ET 200B
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-21
Page 48
Mechanical and Electrical Installation
3.5
Wiring the Terminal Block
Introduction
Connect the following to the terminal block:
Supply voltage for internal logic circuits Sensor supply for input channels Load voltage supply for output channels Sensors/loads
3 Wiring
The wiring of the terminal block is dependent on the electronics block used. A distinction is made between floating and non-floating electronics blocks.
Floating Electronics Block
In a floating electronics block either the circuit for the internal electronics and the load circuit are galvanically isolated from each other: All 120/230 V AC electronics blocks and floating 24 V DC electronics blocks belong to this category.
or the voltage supply of the internal logic and the analog circuits are galvanically isolated from each other: All analog electronics blocks belong to this category. Note You can use floating electronics blocks regardless of whether the reference potential of the supply voltage for the internal logic circuits is grounded or not.
Non-Floating Electronics Blocks
In non-floating electronics blocks, the internal logic circuits and the load current circuit share a common reference potential (M ground). Non-floating electronics blocks include: non-floating 24 V DC electronics blocks.
3-22
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 49
Mechanical and Electrical Installation
Conductor Crosssections
The approved conductor cross-sections for all voltage-supply and signal lines are as follows: Table 3-3
Approved Conductor Cross-sections Line
Conductor Cross-section
Supply-voltage and signal lines with ferrules max. 1.5 mm2 w/o ferrules max. 2.5 mm2 (min. 0.08 mm2 for TB3, TB4, TB4M, TB8 and min. 0.14 mm2 for TB1, TB1-4, TB2, TB2-4)
Protective earth (PE) to terminal block* with ferrule max. 2.5 mm2
*
Connections
Conductor Ferrules for TB1-4/DC or TB2-4/DC only
Some terminal blocks are fitted with screw terminals while others have spring-latch terminals (see Figure 3-15) for securing the cable conductors.
1 2 Figure 3-15 Connecting Cables to Spring-Latch Terminals
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-23
3
Page 50
Mechanical and Electrical Installation
Pin Assignments
In Chapter 7 “Range of Modules”, you will find the pin assignments of each electronics block. The following table will help you. Table 3-4
Pin Assignments of the Terminal Blocks
Assignment of ... TB1/DC, TB1-4/DC and TB3/DC
3 TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC
TB6/AC
TB8-analog
3-24
For Electronics Block ...
See ...
ET 200B-16DI
Table 7-3
ET 200B-16DO
Table 7-5
ET 200B-8DI/8DO
Table 7-9
ET 200B-8DI/8DO HWA
Table 7-10
ET 200B-8RO
Table 7-8
ET 200B-16DO/2A
Table 7-6
ET 200B-32DI, ET 200B-32DI 0.2ms
Table 7-4
ET 200B-32DO
Table 7-7
ET 200B-16DI/16DO
Table 7-12
ET 200B-24DI/8DO, ET 200B-24DI/8DO 0.2ms
Table 7-13
ET 200B-16DI-AC
Table 7-14
ET 200B-16DO-AC
Table 7-15
ET 200B-16RO-AC
Table 7-16
ET 200B-8DI/8RO-AC
Table 7-17
ET 200B-4/8AI
Table 8-37
ET 200B-4AI
Table 8-55
ET 200B-4AO
Table 8-65
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 51
Mechanical and Electrical Installation
Shielding for Analog Value Processing
For analog value processing, connect the cable shields of the signal lines directly at the TB8 to the shield connecting element (Order No.: 6ES7 193-0CD40-7XA0).
Procedure for Connecting the Shielding
Follow the steps listed below: 1. Engage the TB8 terminal block on the shield connecting element after first mounting the shield connecting element on the standard sectional rail or a smooth surface (wall) (see Section 3.1). 2. Mount the metallic terminal elements (see Section 3.1) on the bottom edge of the shield connecting element (1 and 2).
3
3. Strip the ends of the signal lines. 4. Secure the bare cable ends to the terminal elements (3 and 4). 5. Connect the shield connecting element to the protective ground conductor (PE). The cross-section of PE must be a minimum of 4 mm2 and a maximum of 10 mm2. 6. Connect the shield of the bus cable in such a way that the maximum bend radius when bent once (10 x dO; dO = outer diameter of the cable) is not exceeded.
–0031 ET
PE
4
3 1
2
4
2 Figure 3-16 Shield Connecting Element on Terminal Block TB8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-25
Page 52
Mechanical and Electrical Installation
3.6
Wiring the Bus Interface
Bus Interface
The PROFIBUS-DP bus connects to the terminal block by means of a bus connector.
Bus Connector
There are a number of bus connectors for ET 200B.
3
Table 3-5
Bus Connectors Design max. 12 Mbaud
Order Number without programmer socket
6ES7 972-0BA10-0XA01 with programmer socket
6ES7 972-0BB10-0XA01 max. 1.5 Mbaud without programmer (without terminating resistor) socket 1
PROFIBUS-DP Interface
When inserted, the installation height for the ET 200B module is not exceeded with this bus connector.
The pin assignment of the 9-pin PROFIBUS-DP interface of the terminal block is described below. Table 3-6 View2
5 9 4 8
3
7 6
2 1
2
3-26
6ES7 972-0BA30-0XA0
Pin Assignment of the PROFIBUS-DP Interface Pin No.
Signal Name
Designation
1
–
–
2
–
–
3
RxD/TxD-P
Data line B
4
RTS
Request To Send
5
M5V2
Data reference potential (from station)
6
P5V2
Supply plus (from station)
7
–
–
8
RxD/TxD-N
Data line A
9
–
–
Terminal block as viewed from in front
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 53
Mechanical and Electrical Installation
Connecting the Bus Cable
The procedure for connecting the bus cable to the bus connector is described in detail in the following manuals:
Manual ET 200 Distributed I/O System Manual S7-300 Programmable Controller Hardware and Installation Manual M7-300 Programmable Controller Hardware and Installation Manual S7-400/M7-400 Programmable Controller Hardware and Installation
Dimensional Drawings with Bus Connectors
3
Chapters 7 and 8 contain dimensional drawings of ET 200B modules with bus connectors installed.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3-27
Page 54
Mechanical and Electrical Installation
3
3-28
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c