Page 47

Mechanical and Electrical Installation

Disconnecting the Reference Potential of the Logic Circuits from PE

For an ungrounded configuration, you must also do the following at the digital terminal blocks: 1. Connect the PE terminal to the lower screw. 2. Remove the upper screw for an ungrounded configuration.

3

Removed

PE

Figure 3-13 Upper Screw Removed in an Ungrounded Configuration

Electrical Configuration

Figure 3-14 shows the ungrounded configuration for 24 V DC digital modules of the ET 200B:

L1 L2 L3 N PE

(1)

(2) (7) > VCM

ET 200B (3) M

L+ M

L+ (5)

(6) I/O

M

L+

Sensor/ actuator

Figure 3-14 Ungrounded Configuration for 24 V DC Digital Modules of the ET 200B

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-21

Page 48

Mechanical and Electrical Installation

3.5

Wiring the Terminal Block

Introduction

Connect the following to the terminal block:

Supply voltage for internal logic circuits Sensor supply for input channels Load voltage supply for output channels Sensors/loads

3 Wiring

The wiring of the terminal block is dependent on the electronics block used. A distinction is made between floating and non-floating electronics blocks.

Floating Electronics Block

In a floating electronics block either the circuit for the internal electronics and the load circuit are galvanically isolated from each other: All 120/230 V AC electronics blocks and floating 24 V DC electronics blocks belong to this category.

or the voltage supply of the internal logic and the analog circuits are galvanically isolated from each other: All analog electronics blocks belong to this category. Note You can use floating electronics blocks regardless of whether the reference potential of the supply voltage for the internal logic circuits is grounded or not.

Non-Floating Electronics Blocks

In non-floating electronics blocks, the internal logic circuits and the load current circuit share a common reference potential (M ground). Non-floating electronics blocks include: non-floating 24 V DC electronics blocks.

3-22

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 49

Mechanical and Electrical Installation

Conductor Crosssections

The approved conductor cross-sections for all voltage-supply and signal lines are as follows: Table 3-3

Approved Conductor Cross-sections Line

Conductor Cross-section

Supply-voltage and signal lines with ferrules max. 1.5 mm2 w/o ferrules max. 2.5 mm2 (min. 0.08 mm2 for TB3, TB4, TB4M, TB8 and min. 0.14 mm2 for TB1, TB1-4, TB2, TB2-4)

Protective earth (PE) to terminal block* with ferrule max. 2.5 mm2

*

Connections

Conductor Ferrules for TB1-4/DC or TB2-4/DC only

Some terminal blocks are fitted with screw terminals while others have spring-latch terminals (see Figure 3-15) for securing the cable conductors.

1 2 Figure 3-15 Connecting Cables to Spring-Latch Terminals

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-23

3

Page 50

Mechanical and Electrical Installation

Pin Assignments

In Chapter 7 “Range of Modules”, you will find the pin assignments of each electronics block. The following table will help you. Table 3-4

Pin Assignments of the Terminal Blocks

Assignment of ... TB1/DC, TB1-4/DC and TB3/DC

3 TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC

TB6/AC

TB8-analog

3-24

For Electronics Block ...

See ...

ET 200B-16DI

Table 7-3

ET 200B-16DO

Table 7-5

ET 200B-8DI/8DO

Table 7-9

ET 200B-8DI/8DO HWA

Table 7-10

ET 200B-8RO

Table 7-8

ET 200B-16DO/2A

Table 7-6

ET 200B-32DI, ET 200B-32DI 0.2ms

Table 7-4

ET 200B-32DO

Table 7-7

ET 200B-16DI/16DO

Table 7-12

ET 200B-24DI/8DO, ET 200B-24DI/8DO 0.2ms

Table 7-13

ET 200B-16DI-AC

Table 7-14

ET 200B-16DO-AC

Table 7-15

ET 200B-16RO-AC

Table 7-16

ET 200B-8DI/8RO-AC

Table 7-17

ET 200B-4/8AI

Table 8-37

ET 200B-4AI

Table 8-55

ET 200B-4AO

Table 8-65

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 51

Mechanical and Electrical Installation

Shielding for Analog Value Processing

For analog value processing, connect the cable shields of the signal lines directly at the TB8 to the shield connecting element (Order No.: 6ES7 193-0CD40-7XA0).

Procedure for Connecting the Shielding

Follow the steps listed below: 1. Engage the TB8 terminal block on the shield connecting element after first mounting the shield connecting element on the standard sectional rail or a smooth surface (wall) (see Section 3.1). 2. Mount the metallic terminal elements (see Section 3.1) on the bottom edge of the shield connecting element (1 and 2).

3

3. Strip the ends of the signal lines. 4. Secure the bare cable ends to the terminal elements (3 and 4). 5. Connect the shield connecting element to the protective ground conductor (PE). The cross-section of PE must be a minimum of 4 mm2 and a maximum of 10 mm2. 6. Connect the shield of the bus cable in such a way that the maximum bend radius when bent once (10 x dO; dO = outer diameter of the cable) is not exceeded.

–0031 ET

PE

4

3 1

2

4

2 Figure 3-16 Shield Connecting Element on Terminal Block TB8

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-25

Page 52

Mechanical and Electrical Installation

3.6

Wiring the Bus Interface

Bus Interface

The PROFIBUS-DP bus connects to the terminal block by means of a bus connector.

Bus Connector

There are a number of bus connectors for ET 200B.

3

Table 3-5

Bus Connectors Design max. 12 Mbaud

Order Number without programmer socket

6ES7 972-0BA10-0XA01 with programmer socket

6ES7 972-0BB10-0XA01 max. 1.5 Mbaud without programmer (without terminating resistor) socket 1

PROFIBUS-DP Interface

When inserted, the installation height for the ET 200B module is not exceeded with this bus connector.

The pin assignment of the 9-pin PROFIBUS-DP interface of the terminal block is described below. Table 3-6 View2

5 9 4 8

3

7 6

2 1

2

3-26

6ES7 972-0BA30-0XA0

Pin Assignment of the PROFIBUS-DP Interface Pin No.

Signal Name

Designation

1

–

–

2

–

–

3

RxD/TxD-P

Data line B

4

RTS

Request To Send

5

M5V2

Data reference potential (from station)

6

P5V2

Supply plus (from station)

7

–

–

8

RxD/TxD-N

Data line A

9

–

–

Terminal block as viewed from in front

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 53

Mechanical and Electrical Installation

Connecting the Bus Cable

The procedure for connecting the bus cable to the bus connector is described in detail in the following manuals:

Manual ET 200 Distributed I/O System Manual S7-300 Programmable Controller Hardware and Installation Manual M7-300 Programmable Controller Hardware and Installation Manual S7-400/M7-400 Programmable Controller Hardware and Installation

Dimensional Drawings with Bus Connectors

3

Chapters 7 and 8 contain dimensional drawings of ET 200B modules with bus connectors installed.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3-27