The text of a manual · part 4 of 41
SIMATIC ET 200B Distributed I/O Station Manual: 1 System Overview
Pages 17 to 22 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 17
1
System Overview
In this Chapter
The System Overview gives you information on the following: In Section
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c you will find on Page
1.1
What is the ET 200 distributed I/O system?
1-2
1.2
What is ET 200B?
1-3
1-1
Page 18
System Overview
1.1
1
What is the ET 200 Distributed I/O System?
Definition
The ET 200 distributed I/O system is based on the PROFIBUS standard (EN 50170, Part 1) and the PROFIBUS-DP standard (EN 50170, Part 3). The field bus on which the ET 200 distributed I/O system is based is a version of PROFIBUS known as PROFIBUS-DP (DP = Dezentrale Peripherie, or distributed I/O). This version is designed for minimum reaction times in communication with the distributed inputs and outputs.
The Components of ET 200
DP master
The distributed input/output system consists of active stations (DP masters) and passive stations (DP slaves) interconnected by the PROFIBUS-DP field bus.
S5-115/135/155U S7-300/M7-300 S7-400/M7-400
S5-95U
STEP 7 COM ET 200
PROFIBUS-DP
DP slaves
Figure 1-1
ET 200B
ET 200C
ET 200M
S5-95U
Field devices
Typical PROFIBUS-DP Configuration with SIMATIC S5/S7/M7
SINEC L2-DP = PROFIBUS-DP
1-2
PG/PC
SINEC L2-DP is the PROFIBUS-DP from Siemens.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 19
System Overview
1.2
What is the ET 200B?
Definition
The ET 200B (B stands for ”block I/O”) belongs to the ET 200 distributed I/O system with the PROFIBUS-DP field bus. ET 200B is a DP slave having IP 20 protection. The ET 200B distributed I/O station incorporates an integral port for connection to the PROFIBUS-DP bus and digital or analog inputs/outputs.
Range of Modules
The range of modules for the ET 200B includes:
24 V DC digital modules 120/230 V AC digital modules Analog modules Application
Thanks to its compact and flat design, the ET 200B distributed I/O station is primarily suited to applications where space is a priority. The ET 200B distributed I/O station can be mounted either on a standard sectional rail or directly onto the wall. Vertical and horizontal installation are both possible.
Components
The ET 200B consists of 2 parts: the terminal block and the electronics block. The terminal block (TB) incorporates the permanent wiring and does not contain any function-related electrical components. The electronics block is attached to the terminal block. The electronics block (EB) contains the logic circuits. The terminal block and the electronics block have matching mechanical coding elements to prevent destruction of the electronics block.
Electronics block
= +
Terminal block
Figure 1-2
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
ET 200B
Components of ET 200B
1-3
1
Page 20
System Overview
Compatible with
All ET 200B modules can be addressed with the PROFIBUS-DP bus protocol. ET 200B can be operated with the following systems:
1
Table 1-1
ET 200B: Range of Applications Operating with
In system SIMATIC S5
Configurable with
IM 308-B master interface (release COM ET 200 V4.x 5 and higher) version 4.0 and higher: digital modules version 4.1 and higher: analog modules IM 308-C master interface (release COM ET 200 Windows 1 and higher) (version 1.0 and higher) SIMATIC S7/M7
S7/M7 DP master with integral PROFIBUS-DP interface
STEP 7 version 2.0 and higher: digital modules version 3.0 and higher: analog modules
S7 Slave
Theanalog modules of ET 200B can be operated as S7 slaves in conjunction with SIMATIC S7/ M7 and STEP 7 (V3.0 and higher). This means that all the functions of the central S7 I/O modules are also at your disposal for the ET 200B analog modules.
The Next Sections
The next sections of this chapter contain an overview of the components of ET 200B. In Section
1-4 you will find on Page
1.2.1
Terminal Block
1-5
1.2.2
Electronics Block
1-6
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 21
System Overview
1.2.1
Terminal Block
Definition
The terminal block incorporates the permanent wiring.
Characteristics
The terminal block has the following characteristics:
1
The supply voltage for the electronics block (logic) can be switched on/ off (except for the TB6/AC terminal block).
The terminal block can be mounted both on standard sectional rails and on smooth surfaces, so direct wall mounting is possible.
The PROFIBUS-DP bus is interfaced via a SINEC L2 bus connector. Station numbers between 00 and 99 can be set with the aid of a tool such as a screwdriver: – When operating with an IM 308-B master interface, station numbers 3 to 99 are permissible. – When operating with an IM 308-C master interface or with an S7/M7 DP master, station numbers 1 to 99 are permissible.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
1-5
Page 22
System Overview
1.2.2
1
Electronics Block
Definition
The electronics block contains the logic circuits and is plugged onto the terminal block.
Characteristics
The electronics block has the following characteristics:
There is galvanic isolation between the PROFIBUS-DP bus and the internal electronics.
The block has LEDs for indicating the following: – Voltage supply to the logic circuits (RUN) – Bus fault (BF) – Group diagnostics: short-circuit, wire break or load voltage failure (DIA, only for electronics blocks which can be diagnosed) – Load voltage monitoring (L1+, L2+, L3+, L4+, only for digital electronics blocks (24 V DC) with output channels) – Status of the inputs or outputs (for digital electronics blocks only)
Labeling strips are inserted in the electronics block. Fill in the labeling strips to ensure unambiguous assignment of name, channel and LED.
1-6
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c